WL Circuit Breaker
Factory Installed Options

Status contact

A status contact is a mechanical switch that is suitable for
monitoring an undervoltage trip or second shut trip coil
position. The contact will be wired to the secondary contacts
of the breaker for customer connections or wired to the Breaker
Status Sensor (BSS) if communications is installed on the
breaker. Contact is 1NO configured.
Characteristics table
Signaling
Voltage
contact
Continuous current
Making current
Breaking current
Spring-charging motor
The spring charging motor is used to automatically charge the
breakers closing spring so the breaker is suitable for closing on
command. Motor charging is typically used for remote breaker
operation or as an alternative to local manual charging. The
motor assembly can be easily installed in the field and includes
an automatic cut-off switch which disconnects the current upon
full charge of the closing spring mechanism.
Characteristics table
Spring-
120 - 240VAC range
charging
24 - 240VDC range
motor
Power consumption
Max. charging time
Fuse protection rating
1
See page 85 for field install part numbers.
18
Courtesy of NationalSwitchgear.com
1
127 - 240VAX, 24 - 125VDC
3A
1A @24 - 125DVC, 5A @120 - 240VAC
1A @24 - 125DVC, 3A @120 - 240VAC
85 -110% of nominal
70 - 126% of nominal
110W
10 seconds
24-60V 6A, 120-240V 3A
(slow-blow)

Undervoltage release

In the event of loss or low level control circuit voltage, an
undervoltage release may be used to automatically open
the circuit breaker. To prevent nuisance breaker openings
from temporary voltage dips, a separate adjustable time-
delay undervoltage release is also available.
Characteristics table
Undervoltage
Operating values
release UVR
120 - 240VAC
Coil voltage tolerance
24 - 250VDC
Coil voltage tolerance
Supply voltage
Power consumption
Opening time
of breaker
UVR w/o time delay
(dual setting)
UVR with time delay
(adjustable delay)
WL Circuit Breaker Selection and Application Guide
85 - 110% breaker can be closed,
35 - 70% breaker will open
85 - 110% of nominal
85 - 126% of nominal
120, 240VAC or 24, 48, 125, 250VDC
200VA inrush/ 5VA continuous
(same in Watts for DC)
200 ms
80 ms or 200ms
0.2 to 3.2 sec.