INTRODUCTION
The Hansen PXV and PXVW are pulse modulating liquid
refrigerant expansion valves. The PXV uses a specially
designed, high-cycle, long life, solenoid operator. A
sophisticated 4-20 mA input signal is used to monitor
the liquid flow to the system. Unlike traditional TXVs,
the pulse design eliminates the need to maintain
minimum pressure differential. Low and varying liquid
feed pressures (head pressure) are compensated by
the basic variable valve operation. It is suitable for use
with ammonia and most common refrigerants.
The unique PXVW60 body has an integral 100 mesh
(150 micron) strainer screen and features direct weld
assembly, eliminating flange gasket leak potential. In
addition, the PXVW valve has an adjustable, integral
hand-expansion plug to regulate the flow from 15 to
60 nominal tons of ammonia. Consult the factory for
PXVW halocarbon capacities.
APPLICATIONS
The PXV modulates the flow of liquid feed to an evaporator
or chiller. It is recommended for use wherever a thermal
expansion valve (TXV) would be used. It is also ideal for
liquid make-up to small surge vessels above flooded
heat exchangers to minimize fluctuations in liquid level
and evaporator pressures, and for liquid injection for
compressor oil cooling.
key FeATUReS
• PXV5, PXV15 drop-in replacement valve for
Sporlan DA series thermostatic expansion valve
• PXV does not require minimum pressure drop to
operate; low head pressure tolerant
• PXVW60 with adjustable capacity settings from
15 to 60 nominal tons of ammonia
• Simple, compact controller programmed for liquid
level control, liquid injection oil cooling, or DX
superheat control
• Operates with 115V, 220V, or 24V AC coil
PXVW

SPeCIFICATIONS

Body:
Seat Disc: Teflon
Valve Seat: 303 Stainless Steel
Safe Working Pressure:
MOPD: 285 psi (19.7 bar)
Refrigerant Temperature: –60°F to +240°F (–50° to 115°C)
Refrigerants: ammonia, R22, R404, R507, R134a,
Specifications, Applications,
Service Instructions & Parts
PulSe wIdth control
exPAnSIon vAlve
(Pxv & Pxvw)
Pulse width Modulated liquid
level control, dx evaporator and
liquid Injection for refrigerants
FLANGED CONNECTION
DROP-IN FOR SPORLAN
DA SERIES TXV
PXVW
1/2" TO 3/4"
WELD-IN-LINE
CONNECTION
PXV: Ductile iron, ASTM A536 (Flanged Valve)
PXVW: Cast Steel, ASTM A352, grade LCB
400 psig (28 bar)
600 psig (40 bar) available upon request
CO2, and other Hansen approved refrigerants
Bulletin P249
oct 2013
PXV
STEM TO
ADJUST CAPACITY
OF VALVE

Advertisement

Table of Contents
loading

Summary of Contents for Hansen PXV Series

  • Page 1: Specifications

    Injection for refrigerants PXVW INTRODUCTION The Hansen PXV and PXVW are pulse modulating liquid refrigerant expansion valves. The PXV uses a specially designed, high-cycle, long life, solenoid operator. A sophisticated 4-20 mA input signal is used to monitor FLANGED CONNECTION the liquid flow to the system.
  • Page 2: Liquid Line Sizing

    CAPACITy INSTALLATION Match the arrow on body with system flow direction. The PXV models are available for ammonia capacities The PXV and PXVW may be installed in both horizontal up to 60 nominal tons with adjustable capacity settings. and vertical lines. For DX evaporator, install as close The PXV models available for ammonia are 5 and as possible to the distributor in vertical down-flow line 15 tons (nominal) and the PXVW has an adjustable...
  • Page 3 TyPICAL APPLICATION: DIReCT eXPANSION eVAPORATOR, PXV/PXVW FIgURe 1 PXVC - PT CONTROLLER EXPANSION VALVE DX EVAPORATOR PRESSURE TRANSDUCER (10:00 - 2:00 POSITION) TO PROTECTED SUCTION PIPE TEMPERATURE SENSOR AT 4 OR 8 O'CLOCK TEMPERATURE POSITION SENSOR INSULATION FIgURe 2 PXVC - DX CONTROLLER PXVW EXPANSION VALVE...
  • Page 4 MOD420 Output Module, or other liquid level device This controller pulses the PXV valve open and closed to the Hansen PXVC-L controller pulses the PXV valve at a rate equal to the refrigerant flow necessary to open and closed at a rate equal to the refrigerant flow maintain a set-for discharge gas temperature.
  • Page 5 OPeRATION – DX eVAPORATOR For systems using the PXVW valve, the integral hand- expansion stem capacity must be adjusted to match the (Figures 1 & 2) capacity of the evaporator. See the chart on page 2 for the Through the use of pulse width modulation, the valve approximate settings.
  • Page 6 TyPICAL WIRINg DIAgRAMS DX eVAPORATOR CONTROL (PXVC-PT) (Using Separate Pressure Transducer and Temperature Sensor) FIgURe 5 P249 OCT 2013...
  • Page 7 TyPICAL WIRINg DIAgRAMS DX eVAPORATOR CONTROL (PXVC-DX) (Using Hansen HPT 4-20 mA or Customer Supplied 4-20 mA Superheat Input) FIgURe 6 P249 OCT 2013...
  • Page 8 TyPICAL WIRINg DIAgRAMS TeMPeRATURe CONTROL FIgURe 7 P249 OCT 2013...
  • Page 9 TyPICAL WIRINg DIAgRAMS LIqUID LeVeL CONTROL FIgURe 8 P249 OCT 2013...
  • Page 10 PXV INSTALLATION DIMeNSIONS INCHeS (MILLIMeTeRS) PXV PARTS LIST ITeM DeSCRIPTION qT y PART NO. Coil kit(115V ) 1/2˝ Fit w/ Leads 70-1085 Coil kit(208/230V ) 1/2˝Fit w/ Lds 70-1086 Coil kit (24V ) 1/2˝ Fit w/ Leads 70-1087 Coil kit (Other Voltages) FACTORy Above kits consist of: Bare Coil, 115V 50/60HZ w/ Leads...
  • Page 11 PXVW INSTALLATION DIMeNSIONS INCHeS (MILLIMeTeRS) PXVW PARTS LIST ITeM DeSCRIPTION qT y PART NO. Coil kit(115V ) 1/2˝ Fit w/ Leads 70-1085 Coil kit(208/230V ) 1/2˝Fit w/ Lds 70-1086 Coil kit (24V ) 1/2˝ Fit w/ Leads 70-1087 FACTORy Coil kit (Other Voltages) Above kits consist of: 70-0580 Bare Coil, 115V 50/60HZ w/ Leads...
  • Page 12: Warranty

    CAUTION ORDeRINg INFORMATION Hansen valves are only for refrigeration systems. These CONNeCTION instructions must be completely read and understood STyLe & SIzeS before selecting, using or servicing Hansen valves. FPT, SW, WN Only knowledgeable, trained refrigeration mechanics ALSO ALSO should install, operate, or service these valves. Stated PXV5 ½˝...

This manual is also suitable for:

Pxvw seriesPxv5Pxvw60Pxv15

Table of Contents