Viessmann VITODENS 200-W WB2B Service Instructions For Contractors page 79

80 and 105 kw, wall mounted gas fired condensing boiler, natural gas version
Hide thumbs Also See for VITODENS 200-W WB2B:
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
F4
X
X
F7
X
X
F8
X
X
F9
X
X
FA
X
X
System char-
Cause
acteristics
Burner in a
No flame sig-
fault state
nal.
Burner
Short circuit
blocked
or water
pressure
sensor lead
broken
Burner in a
The fuel
fault state
valve closes
too late.
Burner in a
Fan speed
fault state
too low dur-
ing the burn-
er start
Burner in a
Fan not at
fault state
standstill
Troubleshooting
Measures
Check the ionisa-
tion electrode and
cable, measure
the ionisation cur-
rent, check the
gas pressure,
check the gas
train, ignition,
ignition module,
ignition electro-
des and the con-
densate drain.
Press "E
RESET".
Check the water
pressure sensor
and the intercon-
necting cable.
Check the gas
train. Check both
control paths.
Press "E
RESET".
Check the fan,
check the fan
cables and sup-
ply; check the fan
control.
Press "E
RESET".
Check the fan, fan
connecting cables
and fan control.
Press "E
RESET".
79