Viessmann VITODENS 200-W WB2B Service Instructions For Contractors page 75

80 and 105 kw, wall mounted gas fired condensing boiler, natural gas version
Hide thumbs Also See for VITODENS 200-W WB2B:
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
bF
X
C2
X
X
C5
X
X
C6
X
C7
X
X
Cd
X
X
CE
X
X
System char-
Cause
acteristics
Control mode
Incorrect
LON com-
munication
module
Control mode
Communica-
tion fault,
solar control
unit
Control mode,
Communica-
max. pump
tion fault,
speed
variable
speed circu-
lation pump
in the heat-
ing circuit
connection
set
Control mode,
Communica-
max. pump
tion fault,
speed
variable
speed circu-
lation pump,
heating
circuit M2
Control mode,
Communica-
max. pump
tion fault,
speed
variable
speed circu-
lation pump,
heating
circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault
ext. exten-
sion
Troubleshooting
Measures
Replace the LON
communication
module.
Check connec-
tions and coding
address "54".
Check the setting
of coding address
"30"
Check setting of
coding address
"E5"
Check setting of
coding address
"E5"
Check connec-
tions and the
Vitocom 100.
Check connec-
tions and settings
of coding address
"2E".