Viessmann VITODENS 200-W WB2B Service Instructions For Contractors page 73

80 and 105 kw, wall mounted gas fired condensing boiler, natural gas version
Hide thumbs Also See for VITODENS 200-W WB2B:
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
9C
X
X
9F
X
X
A2
X
A4
X
A7
X
System char-
Cause
acteristics
Control mode
Temperature
sensor lead
broken; con-
nects to the
Vitosolic at
S2
Control mode
Solar control
unit fault;
displayed if a
fault without
fault code
occurs at the
solar control
unit
Emergency
System
mode with in-
pressure too
sufficient sys-
low
tem pressure,
triggered by
code "0d" (see
page 41)
Control mode
Max. system
pressure ex-
ceeded
Control mode
Faulty pro-
as per deliv-
gramming
ered condition
unit.
Troubleshooting
Measures
Check the sensor
at the Vitosolic.
Check the solar
control unit (see
solar control unit
service instruc-
tions).
Top up with water
Check system
pressure.
Check the func-
tion and sizing of
the diaphragm ex-
pansion vessel.
Vent the heating
system.
Code "0E" is set
to 1 to document
the fault. After the
fault has been re-
moved, reset
manually to 0.
Replace the pro-
gramming unit.
73