Technical Data - JUMO iTRON B 70.2040 Operating Instructions Manual

Compact microprocessor controllers
Table of Contents

Advertisement

8

Technical data

Input for thermocouple
Designation
Fe-Con
L
Fe-Con
J
Cu-Con
U
Cu-Con
T
NiCr-Ni
K
NiCrSi-NiSi
N
Pt10Rh-Pt
S
Pt13Rh-Pt
R
Pt30Rh-Pt6Rh B
Measurement accuracy: ≤ 0.4% / 100ppm/°C
Cold junction:
1. These ranges refer to the ambiente temperature of 20°C
Input for standard signals
Designation
Range
Voltage
0 — 10V, R
2 — 10V, R
R
- input resistance
E
4 — 20mA, voltage drop ≤ 3V
Current
0 — 20mA, voltage drop ≤ 3V
Measurement accuracy: ≤ 0.1% / 100ppm/°C
2.
0—1V, R
>10MΩ for Type 702040/41 with 2 relays
E
3.
0.2—1V, R
>10MΩ for Type 702040/41 with 2 relays
E
Range
-200 to + 900°C
EN 60584
-200 to +1200°C
-200 to + 600°C
EN 60584
-200 to + 400°C
EN 60584
-200 to +1372°C
EN 60584
-200 to +1300°C
EN 60584
0 — 1768°C
EN 60584
0 — 1768°C
EN 60584
0 — 1820°C
Pt100 internal
2
> 100kΩ
E
3
> 100kΩ
E
Input for resistance thermometer
1
Designation
Pt100 EN 60751
Pt1000 EN 60751
KTY11-6
Measurement accuracy:
Pt100/1000:
KTY11-6:
Sensor lead
resistance:
Meas. current:
Outputs
Relay:
n.o.(make) contact; 3A at 250V AC resistive load;
150,000 operations at rated load
Logic 0/5V:
Current limiting: 20mA; R
Logic 0/12V:
Current limiting: 20mA; R
Supply
110 — 240V AC -15/+10% 48 — 63Hz, or
20 — 53V AC/DC 48 — 63Hz, or
10 — 18V DC (Connect to SELV or PELV)
Range
-200 to +850°C
-200 to +850°C
-50 to +150°C
≤ 0.1% / 50ppm/°C
≤ 1.0% / 50ppm/°C
20Ω max. per lead
250µA
≥250Ω
load
≥600Ω
load
39