Logic Input - JUMO iTRON B 70.2040 Operating Instructions Manual

Compact microprocessor controllers
Table of Contents

Advertisement

5.2

Logic input

Key inhibit
Level inhibit
Ramp stop
Setpoint switching
Timer control
Symbol
Notes
C117
Function of the logic input
On Type 702040/41, the parameter C117 is masked out if output 2 has been programmed as
controller output (C113) or the limit comparator has been configured (C114) (double assign-
ment; not on Type 702040/41 with 2 relay outputs (option)).
Operation is possible from keys.
Access to the parameter and
configuration levels is possible.
Starting self-optimization is possible.
Ramp running
SP 1
Setpoint
is active
The appropriate symbols
level.
Acknowledge start/stop/continue/timer run-down (edge-triggered)
vpage 33
No operation from keys.
No access to the parameter and
configuration levels.
Starting self-optimization is not possible.
Ramp stopped
Setpoint
SP 1
SP 2
and
SP 2
is active
are displayed at the operating
18