ELECTRICAL INSTALLATION

ELECTRICAL CONNECTIONS
Proceed carefully when installing the electrical
system, paying close attention to the following:
All electrical connections must be made by a
certified electrician in accordance with local,
provincial/state and federal building/electrical
code regulations.
Make connections as shown below. Make
connections in the control box before connecting
to power supply.
This unit is connected a 240 V circuit.
The unit' s electrical system must be connected
to a circuit protected by a 40 Amperes Class A
ground fault circuit interrupter (GFCI). These com-
ponents must be new.
Connections must be minimum No. 8 AWG
copper conductors rated minimum 194 °F (90 °C).
WARNING
12
• Under no circumstances should a substitution be made for any Vedana
1 800 463.2187
From 8 a.m. to 6 p.m. Monday to Thursday (EST) . From 8 a.m. to 5 p.m. on Friday (EST)
Some products, specifications, and services mentioned in this manual are described in pending patent applications or are protected by patents.
OW NER 'S M ANU AL | VED A NA
Alternative
Power Entry
240 V (1 1/16"
Knock-out)
Power Entry
240 V
Printed in Canada. Copyright © July 2019 BainUltra
®
component.
®
®
. All rights reserved. 45200496