Leuze electronic MA 21 Technical Description page 18

Connector unit as multinet plus slave and as protocol converter
Table of Contents

Advertisement

Specifications of the MA 21
Service DIP switch
In order to activate the service mode DIP switch 3 must be set to the "ON" position. The
switch must always be in this position if commands are to be sent from a PC to the MA 21
via the service interface. If the switch is set to "OFF", you can passively listen the data.
o
n
1 2
Figure 3.8: Position of the DIP switch and the jumper in the service network
Notice!
To be able to configure the connected device (RS 232) directly via the service interface, DIP
switch 4 must also be set to "ON".
Attention!
Upon activation of the service mode the connection to the host computer is interrupted.
Data format of the service interface
If DIP switch 3 is set to "Service", the service interface always functions with the fixed data
format
• 9600 baud
• 8 data bits
• 1 stop bit
• no parity
• no handshake
ASCII address
Attention!
Please note that to communicate in the network, the Frame format/Address mode/ASCII
address option must always be activated and the correct address must be selected.
Data frame Structure
The data frame on the service interface is structured as follows:
ASCII
HEX
16
S
3 4
B
MA
Prefix 1
Addr. HI Addr. LO
STX
0
02h
30h
Data
1
CODE
31h
43h 4Fh 44h 45h
MA 21
Terminator 1 Terminator 2
CR
0Dh
0Ah
Leuze electronic