Description of blocks
3.2 Driver module DRV_3WL
I/O (parameter)
POS_CB
QDISCON
QOP_POS
QTEST_POS
QNO_CB
ST_CB
QNOT_RDY
QOFF
QON
QTRIP
QLOC_OFF
QRDY_ON
QUNV_REL
QSPR_CHAR
QOVLD_WRN
QSP_EXCEED
QWRN
QWR_PROT
QFREE_COM15
LST_TRIP
QTR_OVLD
QTR_ISC
QTR_STD_C
QTR_GF
QTR_EXT_F
QTR_OVLD_N
QLD_SHED
E_TIME_SYC
STON_GFNA
STON_GFOFF_QC
STON_GFOFF_NA
STON_GFOFF_STOFF_GFON
STOFF_GFON_QC
STOFF_GFON_NA
N_ACT_LD
N_ACT_LD_QC
38
Comment
Position of circuit breaker
1 = Disconnected
1 = Operating position
1 = Test position
1 = Circuit breaker not present
Status of circuit breaker
1 = Circuit breaker not ready
1 = Main contacts disconnected
1 = Main contacts closed
1 = Circuit breaker has tripped
1 = Local turn off of circuit breaker
1 = Ready to switch on
1 = Voltage applied to undervoltage
release
1 = Storage spring is charged
1 = Overload warning present
1 = An activated setpoint value has been
exceeded
1 = A warning signal is currently present
1 = Write operations are prohibited
1 = Status of the free user input on the
COM15 module
Reason for last trip
1 = Overload tripping (L)
1 = Instantaneous short-circuit (I)
1 = Short-time-delay short-circuit (S)
1 = Ground fault (G)
1 = Trip as a result of extended protection
function
1 = Overload in neutral conductor
1 = Load shedding warning
1 = Error time synchronization
Short time on / Ground fault off
Quality code of STON_GFOFF
Short time on / Ground fault off not
available
Short time off / Ground fault off
Quality code of STOFF_GFON
Short time off / Ground fault on not
available
DR 91: Number of switch actions under
load
Quality code of N_ACT_LD
Data type
Default
BYTE
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
WORD
0
BYTE
0
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
Function Manual, 11/2008, A5E02316914A-01
Type
OCM
O
x
O
x
O
O
O
x
O
x
O
O
O
O
O
x
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
x
O
O
x
O
x
O
O
x
O
x
O