Analog in 15 bit voltage/current 8ch

Advertisement

Process Data Output Words OUT[0] and OUT[1]
The terminal must be configured using the two
process data output words. The word OUT[0]
contains the command and the word OUT[1]
contains the parameters for this command.
The following configurations are possible:
Selecting a measuring range according to
the input signal
Selecting the mean-value generation (filte-
ring)
Changing the formats for the representation
of measured values
Current or voltage measurement is
selected by applying the measured si-
gnal to the current or voltage input
and then configuring the measuring
range.
Figure 6
Process data output words
MSB Most significant bit
Set all reserved bits to 0.
6226B_GE
ANALOG IN 15 BIT VOLTAGE/CURRENT 8CH IC220ALG221
LSB Least significant bit
After applying voltage (power up) to
the VersaPoint station, the message
"Measured value invalid" (diagnostic
code 8004
) appears in the process
hex
data input words for every channel
scanned. The message is displayed
until the appropriate channel has
been configured.
If the configuration is changed, the
message "Measured value invalid"
(diagnostic code 8004
a maximum of 100 ms.
Please note the extended runtime
when a channel is configured for the
first time and every time a channel is
reconfigured.
) appears for
hex
7