Analog in 15 bit voltage/current 8ch

Advertisement

Examples of Measured Value Representation in Various Data Formats
Measuring range:
Measured value:
Input data word:
Format
IB IL
IB ST
IB RT
Standardized display
Measuring range:
Measured value:
Input data word:
Format
IB IL
IB ST
IB RT
Standardized display
6226B_GE
ANALOG IN 15 BIT VOLTAGE/CURRENT 8CH IC220ALG221
0 mA to 20 mA
10 mA
hex Value
3A98
4000
4000
2710
±10 V
+5 V
hex Value
3A98
4000
4000
2710
dec Value
15,000
16,384
16,384
10,000
dec Value
15,000
16,384
16,384
5,000
Measured Value
10 mA
10 mA
10 mA
10 mA
Measured Value
5 V
5 V
5 V
5 V