Operating status
The controller's operating status can be called forth by a brief (1s) activation of the
upper button. If a status code exists it will be shown. (Status codes have lower priority
than alarm codes. This means that status codes cannot be seen if there is an active
alarm code.
The individual status codes have the following meanings:
S10 (off ): Regulation stopped by the internal start/ stop.
S20: Emergency cooling is activated because of defect sensor
S42: Heat recovery or heat pump control is active
S43: Higher capacity through displacement of the pressure reference
Alarms
E1: Fault in controller
E15: Cut-out Sgc sensor
E16: Short circuited Sgc sensor
E20: Fault on the signal from Pgc
E39: Fault on the signal from Prec
A43: Step motor error. Output or phase
A45: Regulation stopped. Main switch r12 = off
A82: The Pgc gas pressure measured is higher than the maximum limit for n69
A83: The Pgc gas pressure measured is lower than the minimum limit for A65
A84: The receiver pressure measured is lower than "n71" minus "n72"
A94: Pgc gas pressure measured is outside the permitted reference
A95: Prec receiver pressure measured outside the permitted reference
EKC 326A
Manual RS8FM602 © Danfoss 02-2016
EKC State
(0 = regulation)
10
20
42
43
Controller fault
Sgc o.c.
Sgc S.C.
Sgc input err
Prec input err
Step motor err
Standby mode
PgcMax alarm
PgcMin alarm
PrecMin alarm
PgcRef alarm
PrecRef alarm