Figure 28 - Installing Power Cables For Four Ac Dual-Live Wire Inputs; Figure 29 - Installing Power Cables For Three Ac Dual-Live Wire Inputs - La Marche DCPS Installation And Operation Manual

Dc power system
Hide thumbs Also See for DCPS:
Table of Contents

Advertisement

(Optional) Installing Power Cables for Four AC Dual–Live Wire Inputs
Step 1
Route AC input cables through an appropriate cable hole on the rear of the subrack.
Step 2
Secure the AC input cables to the AC input wiring terminals, as shown in Figure 28
Figure 28 – Installing Power Cables for four AC dual-live Wire Inputs
Reinstall the AC input protective cover.
Step 3
Reinstall the rear cover for the DCPS.
Step 4
(Optional) Installing Power Cables for Three AC Dual–Live Wire Inputs
Install short-circuit copper bars. Connect AC input terminals 3-L1 and 4-L1 by using short-circuit
Step 1
copper bar 1. Connect AC input terminals 3-L2 and 4-L2 by using short-circuit copper bar 2.
Then secure the copper bars by using screws.
Step 2
Route AC input power cables through an appropriate cable hole on the rear of the subrack.
Secure the AC input OT terminals to the corresponding short-circuit copper bars and AC input
Step 3
wiring terminals, as shown in Figure 29.
Figure 29 – Installing Power Cables for three AC dual-live Wire Inputs
(1) Short-Circuit Copper Bar 1
(2) Short-Circuit Copper Bar 2
19