1. INTRODUCTION

If additional information is desired please contact your local
Slant/Fin Sales Representative or Slant/Fin Technical Services.
Slant/Fin may be found on the web at www.slantfin.com
This application manual is intended to provide the piping and control
method for applying multiple Jaguar J-390C boilers to a space heat-
ing and domestic hot water heating system. Use this manual, in
conjunction with the Jaguar J-390C Installation and Operating
Instructions, publication J-40.
The following sections of the Installation and Operating Instructions
(J-390C) must be adhered to:
1. Boiler location and foundation
2. Clearances to combustibles
3. Contamination prevention
4. Air supply and ventilation
5. Venting application and materials*
6. Water treatment
7. Condensate disposal
8. Operating instructions
9. Care and Maintenance

2. RATINGS AND DIMENSIONS

Table 1: Gas multiple boiler ratings and dimension/hot water model 50 psi maximum working pressure
Consists of
Model
No.
No. of Htg.
Boiler
Boiler
Model No.
J-390C 2B
2
J-390C
J-390C 3B
3
J-390C
J-390C 4B
4
J-390C
J-390C 5B
5
J-390C
J-390C
J-390C 6B
6
J-390C
J-390C 7B
7
J-390C
J-390C 8B
8
Model
Water
Ship
No.
Content
Wt.
(gal.)
Lbs.
J-390C 2B
4
600
J-390C 3B
6
900
J-390C 4B
8
1200
J-390C 5B
10
1500
J-390C 6B
12
2340
14
2730
J-390C 7B
16
3120
J-390C 8B
CSA Input
CSA output
(MBH)
Max
Min
Max
780
110
704
1170
110
1056
1560
110
1408
1950
110
1760
2340
110
2112
2730
110
2464
3120
110
2816
Water
Vent
Air
Correction
Conn
Intake.
at Boiler
4"
4"
1-1/4
4"
4"
1-1/4
4"
4"
1-1/4
4"
4"
1-1/4
4"
4"
1-1/4
4"
4"
1-1/4
4"
4"
1-1/4
Jaguar Caravan Multiple and Cascading Boilers
*Common venting of these appliances is not permitted. Direct vent
terminals cannot be clustered together or stacked vertically. Direct
vent terminals can be mounted side by side horizontally, provided
there is a 12" minimum distance between them.
There are two methods available to control J-390C Caravan boilers:
1. Jaguar link method to operate up to 8 boilers. An optional system
sensor is required for operation of this method. Supply water
system sensor (Part no. 833433000) max be ordered to
Slant/Fin boiler distributor.
2. External signal (0-10 Vdc input). Control such as Tekmar control
265 or 275 (operates up to 4 boilers). Energy Management
System may be used with this method. One optional interface
control is required for operation of each boiler in the system.
Part number for interface control kit is 830130000.
Jaguar boilers may also be used in a heating system with a
Caravan cast iron modular boiler system. Since high efficiency con-
densing boilers only condense when the return water temperature is
low, around 130 F or lower, it makes sense to use a lower cost
Caravan cast iron boiler at higher water temperature. We call a com-
bination Caravan Cast Iron Modular Boiler used in a system with a
Jaguar Multiple Boiler a "Hybrid Boiler System". We address Hybrid
Boiler Systems within this manual.
I=B=R Net
(MBH)
(MBH)
Min
Max
106
612
106
918
106
1224
106
1530
106
1836
106
2142
106
2448
**
**
Space
Length
Min.
Btwn.
with
Header
Boilers
Header
Size
3-1/4
50-1/2"
2"
3-1/4
77-3/4"
2"
3-1/4
104-1/4"
3"
3-1/4
131-1/8"
3"
3-1/4
158"
3"
3-1/4
184-7/8"
3"
3-1/4
211-3/4"
3"
Combustion
Efficiency
Min
Max
Min
92
91.6
96.7
92
91.6
96.7
92
91.6
96.7
92
91.6
96.7
92
91.6
96.7
92
91.6
96.7
92
91.6
96.7
System Turndown
Model
Turndown
No.
Ratio
J-390C 2B
7 to 1
J-390C 3B
10.6 to 1
J-390C 4B
14.2 to 1
J-390C 5B
17.7 to 1
J-390C 6B
21.3 to 1
J-390C 7B
24.8 to 1
J-390C 8B
28.4 to 1
Boiler
Horse-
Power
21
31.5
42
52.6
63.1
73.6
84.1