Jaguar Caravan Multiple and Cascading Boilers
11
**
**
Figure 6. Alternative multiple side wall air intake & exhaust venting.
Note:
• Air intake opening must be 12 inches minimum above snow line or grade if it does not snow in
area boilers are located.
• No minimum horizontal distance between outlets or inlets.
• Exhaust termination to extend beyond air intake, prevent condensation from falling onto air intake
** Knowledge of local conditions will reveal the maximum height that repeated snowfalls
accumulate to. This height should be used as the snow line.