Redline RL-101 Installation And Operation Manual page 5

Table of Contents

Advertisement

3. Calibration
Press Menu button or
use reed switch twice to
enter "CAL" mode
To place the Rl101 into CAL Mode press the MENU button twice "CAL" will flash on the display.
The RL101 Head unit monitors the gas level but does not send messages to the monitor when in
CALIBRATION mode. When calibration gas is applied, the unit will display the reading. Use the Up and
Down buttons to adjust the reading to match the value of the calibration gas. Pressing MENU will place
the unit in Normal Operation and will begin sending messages to the monitor.
4. Assign Radio (Head) to Channel
To access to this feature
press TEST button or use
reed switch once
To access to this feature press TEST once, "Adr" will flash on the display when in that mode.
Use the UP and Down buttons to adjust the Address of the Head unit. There must be a corresponding
address set in the Monitor.
Use the Up and Down buttons to
adjust the reading to match the value
of the calibration gas
Use the UP and Down buttons or reed
switch to adjust the Address of the
Head unit.
5