Comparison Of The Jumper Assignments Of 6Es5244-3Aa22/-3Ab31 - Siemens SIMATIC S5 Manual

Ip 244 temperature controller with function block fb 162
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Operation

3.4.5 Comparison of the Jumper Assignments of 6ES5244-3AA22/-3AB31

6ES5244-3AB31
Thermal e.m.f. measurement with reference junction via channel 15
1–2, 3–4, 5–6:
51,2 mV input sensitivity
5
6
7–8: not used
7
8
9–10, 11–12, 13–14, 15–16:
13
14
Thermal e.m.f measurement
15
16
X9
1
2
Channel 13: 1:400 voltage divider active
3
4
Channel 14: 1:400 voltage divider active
Channel 15: Reference point temperature measurement with Pt 100 in
3-wire circuit
5
6
6ES5244-3AB31
Pt 100 measurement in 4-wire circuit
1–2, 3–4, 5–6:
512 mV input sensitivity
5
6
7–8: not used
7
8
9–10, 11–12, 13–14, 15–16:
Pt 100 resistance-type sensor
13
14
4-wire circuit
15
16
X9
Channel 13: Same sensitivity as selected at X8 (1:400 divider
1
2
inactive)
3
4
X10
Channel 14: Same sensitivity as selected at X8 (1:400 divider
1
2
inactive)
3
4
Channel 15: normal input channel
Same sensitivity as selected at X8
5
6
6ES5244-3AB31
1–2: not used
3–4: jumper D
5–6: inserted
5
6
7
8
7–8: not inserted
1–2: not used
3–4: jumper D (see Programming Instructions)
5–6: not inserted
5
6
7
8
7–8: inserted
1–2: BASP not effective
3–4: for test purposes only, must remain open
X12
1–2: BASP has an effect on digital outputs
1
2
3–4: for test purposes only, must remain open
3
4
3–30
Thermocouple mode (delivery state)
Pt 100 mode
General selections
50 Hz Netzunterdrückung
60 Hz Netzunterdrückung
6ES5244-3AA22
1–1, 2–2, 3–3:
3
5–5, 6–6, 7–7, 8–8:
7
8
R83 and R84 in
delivery state
R85 and R86 in
delivery state
6ES5244-3AA22
3
7
8
R83 shorted,
R84 removed
R85 shorted
R86 removed
6ES5244-3AA22
1–1
2–2
inserted 3–3
3
4
not inserted 4–4
1–1
2–2
not inserted 3–3
3
inserted 4–4
4
4–4
C79000–B8576–C865–01
3
7
8
3
7
8
3
4
3
4
IP244B