AIR CARE SEMINAR TRAINING Sullair Air Care Seminars are courses that provide hands-on instruction for the proper operation, maintenance, and servicing of Sullair products. Individual seminars on Industrial compressors and compressor electrical systems are offered at regular intervals throughout the year at Sullair’s corporate headquarters training facility located at Michigan City, Indiana.
Page 3
TABLE OF CONTENTS SECTION 1—SAFETY SAFETY INFORMATION SECTION 2—RH SERIES REFRIGERATED HIGH TEMPERATURE COMPRESSED AIR DRYER SPECIFICATIONS INTRODUCTION TYPICAL INSTALLATION SAFETY REGULATIONS REFRIGERANT DRYER FEATURES DRYER OPERATION PROCEDURE ED—RH15-50 ED—RH75-100 ID—RH15-50 2.10 ID—RH75-100 2.11 P&I—RH15-75 2.12 P&I—RH100 2.13 WIRING DIAGRAM 2.14...
Page 7
The equipment design, development, production, compressed air service. Also all “end user” safety assembly and customer service fall under the Sullair rules for the same type of service must be adhered quality control system.
Page 9
RH SERIES—HIGH TEMPERATURE Section 2 RH SERIES REFRIGERATED HIGH TEMPERATURE COMPRESSED AIR DRYER RH-0015-115-60-A RH-0025-115-60-A RH-0035-115-60-A RH-0075-115-60-A RH-0100-115-60-A...
Page 10
If your application does not match the above criteria, with an automatic drain. The hot saturated air is then contact your Sullair distributor and they will be able to passed directly into the RH series of dryers. provide the right dryer for your application.
Page 11
SECTION 2 RH SERIES—HIGH TEMPERATURE TYPICAL INSTALLATION The RH series of Dryers operate without the need for any after-coolers.
Page 12
6. All safety precautions mentioned in this Contact your Sullair representative/dealer for manual must be adhered to at all times and suitable filter. by all personnel working on the dryer 2.4.5 S...
Page 13
SECTION 2 RH SERIES—HIGH TEMPERATURE 2.4.6 M 2.4.7 M AINTENANCE BY AN NGINEER AINTENANCE BY THE USER ECHNICIAN 1. Keep the dryer clean. 1. Maintenance and repairs should only be 2. In case of more than 4 pounds of refriger-...
Page 14
RH SERIES—HIGH TEMPERATURE SECTION 2 2.4.9 R 2.4.11 C EFRIGERANT CIRCUIT OMPRESSED AIR CIRCUIT The refrigerant circuit can be divided into 3 parts: 1. The hot, saturated, compressed air from the compressor is forced into the air-cooled 1. Low pressure section with an evaporator...
Page 15
SECTION 2 RH SERIES—HIGH TEMPERATURE REFRIGERANT DRYER IGH PRESSURE SECURITY SWITCH FEATURES Refrigerant circuits are protected against excessive pressure by a security switch that stops the 2.5.1 C OMPRESSOR compressor in case of too high a pressure. In case this safety switch has tripped, it has to be manually...
Page 16
RH SERIES—HIGH TEMPERATURE SECTION 2 2.5.7 C -1 H 2. An Evaporator which is an air-to- refrigerant OMPACT EAT EXCHANGER heat exchanger that cools the pre-cooled The dryers are equipped with compact heat compressed air. exchangers. This compact 3-in-1 setup has been 3.
Page 17
NOTES DRYER OPERATION PROCEDURE 1. Starting of a Single phase dryer for the first time a. Make sure all air connections are intact and have no leaks b. Double check wiring connections c. Set the rocker switch to “I” 2. Daily starting and shut-down a.
Page 19
ED—RH15-50 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION SEE REF. TABLE COMPRESSOR COMPRESSOR OVERLOAD SEE REF. TABLE PROTECTOR M-CON-0050H CONDENSOR M-STR-0050-115-1-60 COMPRESSOR START RELAY M-FMT-0150-115-1-60-A FAN MOTOR M-FAN-0150 FAN BLADE M-GRL-0150 FAN GRILL M-DRI-0200 DRIER DEHYDRATOR M-EXC-0035 HEAT EXCHANGER TMR-3000 TIMER M-SLV-0150-115 SOLENOID VALVE M-WSP-050...
Page 21
ED—RH75-100 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION SEE REF. TABLE COMPRESSOR SEE REF. TABLE COMPRESSOR START CAPACITOR M-CEB-115-1-60-A COMPRESSOR ELECTRIC BOX COMPRESSOR OVERLOAD SEE REF. TABLE PROTECTOR M-CON-100H CONDENSOR SEE REF. TABLE COMPRESSOR START RELAY M-FMT-0150-115-1-60-A FAN MOTOR M-FAN-0200 FAN BLADE M-GRL-0200 FAN GRILL M-DRI-0200...
Page 27
2.11 ID—RH15-75 COMPRESSOR REFRIGERANT CONDENSER AFTERCOOLER FAN MOTOR FAN MOTOR SWITCH DEHYDRATOR THERMOSTATIC EXPANSION VALVE EVAPORATOR AIR-AIR EXCHANGER DEW POINT INDICATOR NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION. MODEL REFRIGERANT TYPE RH15 1.102 RH25 1.102 RH35 1.102 RH50 0.992 RH75 R134A 1.543...
Page 31
2.13 WIRING DIAGRAM COMP DESCRIPTION Compressor starting capacitor Compressor motor start relay A20-1 Electronic drain power supply-1 A20-2 Electronic drain power supply-2 Compressor motor M10-1 Fan motor 1 M10-2 Fan motor 2 Main switch Fan pressure switch High pressure safety switch High air temperature thermostat Compressor protection Indicates high pressure...
Page 32
RH SERIES—HIGH TEMPERATURE SECTION 2 2.14 TROUBLESHOOTING IMPORTANT Before starting maintenance activity or repair on the dryer, the main power switch and ON/ OFF switch must be turned OFF. Also, the compressed air must be vented from the sys- tem and the inlet and outlet valves must be closed.
Page 33
SECTION 2 RH SERIES—HIGH TEMPERATURE PROBLEM POSSIBLE CAUSE REPAIR COMMENTS Dryer-on light is lit but Clogged condenser fins Clear fins of all obstruc- The clogged fins in the condenser will refrigerant compressor is tions restrict the air passage and reduce...
Page 34
RH SERIES—HIGH TEMPERATURE SECTION 2 PROBLEM POSSIBLE CAUSE REPAIR COMMENTS Water in system Inlet and outlet connec- Check inlet and outlet This dryer is designed for air flow in tions are reversed connections one direction only. Inlet and outlet directions are identi- fied on the dryer and cannot be inter- changed.
Page 35
SECTION 2 RH SERIES—HIGH TEMPERATURE PROBLEM POSSIBLE CAUSE REPAIR COMMENTS Water in system Clogged condenser fins Clean fins of all obstruc- The clogged fins in the condenser will tions restrict air passage and reduce refrig- erant capacity causing water down- stream.
Page 36
RH SERIES—HIGH TEMPERATURE SECTION 2 PROBLEM POSSIBLE CAUSE REPAIR COMMENTS The unit will not run or Line disconnect switch is Close the start or discon- If the dryer is not operating, check the cycles ON and OFF open. nect switch disconnect switch or circuit breaker to be certain it is turned ON.
Page 37
4 sec / 5 min Table 2-1: DP Power 60H STANDARD Capacity SCFM @ WATER COOLED Rated Pressure Absorbed GROUP AIR COOLED MODEL REF SULLAIR PART SULLAIR PART Port Size VOLTAGE Rated Conditions MODEL REF Flow [1] Drop Power scfm...
Page 38
2.16 SPARE PARTS Component Name RH-0015-115-1-60-A RH-0025-115-1-60-A RH-0035-115-1-60-A RH-0050-115-1-60-A RH-0075-115-1-60-A RH-0100-115-1-60-A Refrigerant Gas R134a R134a R134a R134a R134a R134a compressor M-CMP-0050-115-1-60-A M-CMP-0050-115-1-60-A M-CMP-0050-115-1-60-A M-CMP-0075-115-1-60-A M-CMP-0075-115-1-60-A CAE4461Y/115V compressor electric box M-CEB-0100-115-1-60 Condenser M-CON-0050H M-CON-0050H M-CON-0050H M-CON-0050H M-CON-0100H M-CON-0100H Fan motor 2x M-FMT-0150-115-1-60 2x M-FMT-0150-115-1-60 2x M-FMT-0150-115-1-60 2x M-FMT-0150-115-1-60...
Page 39
Component Name RH-0015-115-1-60-A RH-0025-115-1-60-A RH-0035-115-1-60-A RH-0050-115-1-60-A RH-0075-115-1-60-A RH-0100-115-1-60-A On/off Button M-ONB-0200 M-ONB-0200 M-ONB-0200 M-ONB-0200 M-ONB-0200 M-ONB-0200 Component Name RH-0015-115-1-60-A RH-0025-115-1-60-A RH-0035-115-1-60-A RH-0050-115-1-60-A RH-0075-115-1-60-A RH-0100-115-1-60-A Main Switch Contactor Phase protection relay Fan Contactor Transformer Secondary contact Timer 2 x M-TMR-3000 2 x M-TMR-3000 2 x M-TMR-3000 2 x M-TMR-3000 2 x M-TMR-3000...
Page 41
Heat If your application does not match the above criteria, Exchanger) contact your Sullair distributor and they will be able to • Integrated Separator (located at the coldest point provide the right dryer for your application. to maximize moisture extraction)
Page 42
INSPECTION observe all local safety instructions and rele- vant regulations. Sullair dryers are factory tested prior to shipment. 2. Prior to installation, the dryer and the com- However, during shipment, there are chances that pressed air system are to be depressurized...
SECTION 3 PRODUCT USER MANUAL INSTALLATION LAYOUT REQUIREMENTS 3.10 PRODUCT FEATURES 1. The dryer must be installed horizontally. A 3.10.1 R minimum of at least 1 ½ feet clearance EFRIGERANT COMPRESSOR around the dryer is necessary to allow free The refrigerant compressor is fully hermetically air circulation and easy access for servicing.
Page 44
PRODUCT USER MANUAL SECTION 3 3.10.5 C design heat exchangers. This assembly has been RANKCASE HEATER specially designed to dry compressed air and 3-Phase dryers are equipped with an electric consists of: crankcase heater. The heater provides preliminary 1. An air/air heat exchanger which pre-cools pre-heating refrigerant compressor...
SECTION 3 PRODUCT USER MANUAL 3.11 PRINCIPLE OF OPERATION refrigerant is sucked into the compressor and the cycle carries on. The refrigerant circuit can be divided in 3 parts: 9. In order to keep the evaporation pressure 1. Low pressure section with an evaporator steady, and maintain the refrigerant tempera- (heat exchanger) ture in the heat exchanger, a hot gas by-pass...
PRODUCT USER MANUAL SECTION 3 Figure 3-1: Typical Installation Diagram 3.13 PIPE/CONNECTION 3.15 OPERATING PRECAUTIONS REQUIREMENTS Refer to Product Models and Specifications— WARNING Table 3-2, Table 3-3, Table 3-4, Table 3-5. Verify that the operating parameters match 3.14 ELECTRICAL CONNECTION with the nominal values stated on the data REQUIREMENTS nameplate of the dryer (voltage, frequency,...
PRODUCT USER MANUAL SECTION 3 3.17 STEPS TO UNDERTAKE 6. Remove any packaging and other material BEFORE OPERATING which could obstruct the area around the dryer. 1. Read this manual completely. 7. Activate the mains switch. 2. Review all safety precautions. 8.
SECTION 3 PRODUCT USER MANUAL 3.19 STARTUP AND SHUT DOWN SEC 3.24 S HUT DOWN PROCEDURE 1. Shut down the air compressor. 2. After few minutes, shut down the dryer pressing the button "0 - OFF" of the ON/OFF WARNING switch For short periods of inactivity, (max 2-3 NOTE...
3.21 ED—RN 25 PART NUMBER DESCRIPTION DRYER PART POWER RATINGS COOLING DECAL NUMBER M-CMP-0035-115-1-60 COMPRESSOR 02250193-812 115V/1Ph/60Hz AIR COOLED RN25 M-CON-0035 CONDENSER 02250193-870 220V/1Ph/50Hz AIR COOLED RN25 M-FMT-0075-115-1-60 FAN MOTOR 02250193-835 208/230V/1Ph/60Hz AIR COOLED RN25 M-FAN-0075 FAN BLADE M-GRL-0075 FAN GRILL M-DRI-0200 DRIER DEHYDRATOR M-EXC-0025...
Page 55
3.22 ED—RN 35-50 PART NUMBER DESCRIPTION DRYER PART POWER RATINGS COOLING DECAL NUMBER M-CMP-0035-115-1-60 COMPRESSOR AIR COOLED 02250193-813 115V/1Ph/60Hz RN35 M-CON-0035 CONDENSER M-FMT-0075-115-1-60 FAN MOTOR AIR COOLED 02250193-836 208-230V/1Ph/60Hz RN35 M-FAN-0075 FAN BLADE AIR COOLED 02250193-871 220V/1Ph/50Hz RN35 M-GRL-0075 FAN GRILL AIR COOLED 02250193-814 115V/1Ph/60Hz...
3.23 ED—RN 75 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0075-115-1-60 COMPRESSOR COMPRESSOR OVERLOAD M-COP-0100-115-1-60 PROTECTOR M-CON-0075 CONDENSER M-CSR-0100-115-1-60 COMPRESSOR START RELAY M-FMT-0075-115-1-60 FAN MOTOR M-FAN-0075 FAN BLADE DRYER PART M-GRL-0075 FAN GRILL POWER RATINGS COOLING DECAL NUMBER M-DRI-0200 DRIER DEHYDRATOR AIR COOLED 02250193-815 115V/1Ph/60Hz...
3.24 ED—RN 100 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0100-115-1-60 COMPRESSOR M-FAS-3000 CABINET FASTENER M-CEB-0100-115-1-60 COMPRESSOR ELECTRIC BOX M-CSC-0100-115-1-60 COMPRESSOR START CAPACITOR M-CON-0100 CONDENSER M-CSR-0100-115-1-60 COMPRESSOR START RELAY M-FMT-0150-115-1-60 FAN MOTOR COMPRESSOR OVERLOAD M-COP-0100-115-1-60 PROTECTOR M-FAN-0150 FAN BLADE M-GRL-0150 FAN GRILL DRYER PART M-DRI-0200 DRIER DEHYDRATOR...
3.25 ED—RN 125 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0125-115-1-60-A COMPRESSOR M-SMS-3000 SHEET METAL SCREW M-CEB-0125-115-1-60 COMPRESSOR ELECTRIC BOX M-STU-3000 CABINET STUD AND NUT M-CON-0150 CONDENSER M-FAS-3000 CABINET FASTENER M-FMT-0150-115-1-60 FAN MOTOR COMPRESSOR START M-CSC-0150-115-1-60 CAPACITOR M-FAN-0150 FAN BLADE M-CSR-0150-115-1-60 COMPRESSOR START RELAY M-GRL-0150 FAN GRILL...
3.26 ED—RN 150 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0150-115-1-60-A COMPRESSOR M-FAS-3000 CABINET FASTENER M-CEB-0150-115-1-60 COMPRESSOR ELECTRIC BOX M-CSC-0150-115-1-60 COMPRESSOR START CAPACITOR M-CON-0150 CONDENSER M-CSR-0150-115-1-60 COMPRESSOR START RELAY M-FMT-0150-115-1-60 FAN MOTOR COMPRESSOR OVERLOAD M-COP-0150-115-1-60 PROTECTOR M-FAN-0150 FAN BLADE M-GRL-0150 FAN GRILL DRYER PART M-DRI-0200 DRIER DEHYDRATOR...
3.27 ED—RN 175 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0200-220-1-50-A COMPRESSOR M-FAS-3000 CABINET FASTENER M-CEB-0200-220-1-50 COMPRESSOR ELECTRIC BOX M-CSC-0200-220-1-60 COMPRESSOR START CAPACITOR M-CON-0175 CONDENSOR M-CSR-0200-220-1-60 COMPRESSOR START RELAY M-FMT-0200-220-1-50 FAN MOTOR ASSEMBLY COMPRESSOR OVERLOAD M-COP-0200-220-1-60 ROTECTOR M-FAN-0200 FAN BLADE M-RUN-0325-220-1-60 RUN CAPACITOR M-GRL-0200 FAN GRILL...
3.28 ED—RN 200 PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0200-220-1-50-A COMPRESSOR M-FAS-3000 CABINET FASTENER M-CEB-0200-220-1-50 COMPRESSOR ELECTRIC BOX M-CSC-0200-220-1-60 COMPRESSOR START CAPACITOR M-CON-0200 CONDENSOR M-CSR-0200-220-1-60 COMPRESSOR START RELAY M-FMT-0200-220-1-50 FAN MOTOR ASSEMBLY COMPRESSOR OVERLOAD M-COP-0200-220-1-60 ROTECTOR M-FAN-0200 FAN BLADE M-RUN-0200-220-1-60 RUN CAPACITOR M-GRL-0200 FAN GRILL...
Page 69
3.29 ED—RN 250 PART NUMBER DESCRIPTION M-CRE-0400 CABINET REAR PART NUMBER DESCRIPTION M-CTO-0400 CABINET TOP M-CBA-0400 CABINET BASE SEE REF. TABLE COMPRESSOR M-CBL-0150 CABINET LEG M-CON-0325 CONDENSOR M-HP1-0400 CABINET HORIZONTAL PROFILE 1 SEE REF. TABLE FAN MOTOR ASSEMBLY M-HP2-0400 CABINET HORIZONTAL PROFILE 2 M-DRI-1000 DRIER DEHYDRATOR M-CPS-3000...
3.30 ED—RN 325 (230) PART NUMBER DESCRIPTION PART NUMBER DESCRIPTION M-CMP-0325-460-3-60-A COMPRESSOR M-COP-0325-460-3-60-A COMPRESSOR START CAPACITOR M-CON-0325 CONDENSOR M-STR-0325-230-60 COMPRESSOR START RELAY M-FMT-0700-460-3-60 FAN MOTOR ASSEMBLY M-RUN-0325-230-60 RUN CAPACITOR M-DRI-1000 DRIER DEHYDRATOR DRYER PART M-EXC-0200 HEAT EXCHANGER POWER RATINGS COOLING DECAL NUMBER M-EXV-0850...
Page 75
3.32 ID—RN5-15 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-807 115V/1Ph/60Hz AIR COOLED 02250193-809 115V/1Ph/60Hz AIR COOLED RN10 02250193-810 115V/1Ph/60Hz AIR COOLED RN15 02250193-869 220V/1Ph/50Hz AIR COOLED RN15 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT WEIGHT 13.8” x 13.8” x 24” 17.52”...
Page 77
3.33 ID—RN25 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-812 115V/1Ph/60Hz AIR COOLED RN25 02250193-870 220V/1Ph/50Hz AIR COOLED RN25 02250193-835 208/230V/1Ph/60Hz AIR COOLED RN25 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT WEIGHT 15.55” x 13.8” x 24” 17.52” x 18.9” x 31.5” 95 LB 74 LB 350mm x 395mm x 610mm...
Page 79
3.34 ID—RN35/50 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-813 115V/1Ph/60Hz AIR COOLED RN35 02250193-836 208-230V/1Ph/60Hz AIR COOLED RN35 02250193-871 220V/1Ph/50Hz AIR COOLED RN35 02250193-814 115V/1Ph/60Hz AIR COOLED RN50 02250193-838 208-230V/1Ph/60Hz AIR COOLED RN50 02250193-872 220V/1Ph/50Hz AIR COOLED RN50 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT...
Page 81
3.35 ID—RN75-100 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-815 115V/1Ph/60Hz AIR COOLED RN75 02250193-839 208-230V/1Ph/60Hz AIR COOLED RN75 02250193-873 220V/1Ph/50Hz AIR COOLED RN75 02250193-816 115V/1Ph/60Hz AIR COOLED RN100 02250193-841 208-230V/1Ph/60Hz AIR COOLED RN100 02250193-874 220V/1Ph/50Hz AIR COOLED RN100 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE DRYER...
Page 83
3.36 ID—RN125 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-817 115V/1Ph/60Hz AIR COOLED RN125 02250193-842 208-230V/1Ph/60Hz AIR COOLED RN125 02250193-875 220V/1Ph/50Hz AIR COOLED RN125 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT WEIGHT 17.52” x 21.46” x 31.7” 21.65” x 25.2” x 38.98” 197 LB 176 LB 445mm x 545mm x 805mm...
Page 85
3.37 ID—RN150 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-818 115V/1Ph/60Hz AIR COOLED RN150 02250193-843 208-230V/1Ph/60Hz AIR COOLED RN150 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT WEIGHT 17.52” x 23.42” x 31.7” 21.26” x 26.77” x 39.37” 215 LB 194 LB 445mm x 595mm x 805mm 540mm x 680mm x 1000mm...
Page 87
3.38 ID—RN175-200 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-876 220V/1Ph/50Hz AIR COOLED RN175 02250193-845 208-230V/1Ph/60Hz AIR COOLED RN175 02250193-877 220V/1Ph/50Hz AIR COOLED RN200 02250193-846 208-230V/1Ph/60Hz AIR COOLED RN200 GROSS WITHOUT PALLET SIZE WITH PALLETT SIZE WEIGHT WEIGHT 21.46” x 23.42” x 34.25” 25.6”...
Page 89
3.39 ID—RN250-400 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-880 230V/3Ph/60Hz AIR COOLED RN250 02250193-847 208-230V/1Ph/60Hz AIR COOLED RN250 02250193-979 460V/3Ph/60Hz AIR COOLED RN250 02250193-134 575V/3Ph/60Hz AIR COOLED RN250 02250193-878 220V/1Ph/50Hz AIR COOLED RN250 02250193-848 208-230V/1Ph/60Hz AIR COOLED RN325 02250193-980 460V/3Ph/60Hz AIR COOLED RN325...
Page 91
3.40 P&I—RN250-400 DESCRIPTION COMPRESSOR REFRIGERANT CONDENSOR FAN MOTOR FAN MOTOR SWITCH AIR/FREON HEAT EXCHANGER SEPARATOR PRESSURE REGULATOR DEHYDRATOR REFRIGERANT MODEL TYPE 0.617 RN10 0.617 R134A RN15 0.661 RN25 0.705 NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION...
Page 93
3.41 P&I—RN35-75 DESCRIPTION COMPRESSOR REFRIGERANT CONDENSOR FAN MOTOR FAN MOTOR SWITCH EVAPORATOR AIR-AIR EXCHANGER PRESSURE REGULATOR DEHYDRATOR DEW POINT INDICATOR REFRIGERANT MODEL TYPE RN35 0.881 RN50 R134A 0.881 RN75 1.102 NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION...
Page 95
REFRIGERANT CONDENSOR FAN MOTOR FAN MOTOR SWITCH EVAPORATOR AIR-AIR EXCHANGER PRESSURE REGULATOR DEHYDRATOR DEW POINT INDICATOR BY-PASS VALVE REFRIGERANT MODEL TYPE RN100 1.543 RN125 2.866 RN150 R134A 2.866 RN175 2.866 RN200 2.866 NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION...
3.48 WIRING DIAGRAM—RN5-10-15-20-25 COMP DESCRIPTION Start capacitor Compressor motor starter relay Main switch Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
3.49 WIRING DIAGRAM—RN30-50-75-100 COMP DESCRIPTION Drain timer supply Start capacitor Compressor motor starter relay Main switch Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
Page 107
3.50 WIRING DIAGRAM—RN125-150 COMP DESCRIPTION Drain timer supply Start capacitor Compressor motor starter relay Main switch Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
Page 109
3.51 WIRING DIAGRAM—RN175 COMP DESCRIPTION Drain timer supply Starting capacitor resistance A40-1 Start capacitor A40-2 Run capacitor Compressor motor starter relay Main switch Remote control start Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
Page 111
3.52 WIRING DIAGRAM—RN200 COMP DESCRIPTION Drain timer supply Starting capacitor resistance A40-1 Start capacitor A40-2 Run capacitor Compressor motor starter relay Main switch Remote control start Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
Page 113
3.53 WIRING DIAGRAM—RN250-325 COMP DESCRIPTION Drain timer supply Compressor chankaser heater Starting capacitor resistance A40-1 Start capacitor A40-2 Run capacitor Compressor motor starter relay Main switch Remote control start Fan pressure control switch Safety control switch Compressor motor Fan motor Compressor motor protector Indicates high pressure in the circuit...
Page 117
3.55 WIRING DIAGRAM—RN250-325 (230-3-60-A) COMP DESCRIPTION Control circuit protection Compressor motor relay Fan motor relay Thermal protection of compressor Thermal protection of fan S02-1 Start button on control panel S02-2 Remote control start button S03-1 Stop button on control panel S03-2 Remote control stop button Fan high pressure control switch...
Page 121
3.57 WIRING DIAGRAM—RN250-325 (460-3-60-A, 400-3-50-A) COMP DESCRIPTION Control circuit protection Economizer protection Compressor motor relay Fan motor relay Economizer relay Thermal protection of compressor Thermal protection of fan S02-1 Start button on control panel S02-2 Remote control start button S03-1 Stop button on control panel S03-2 Remote control stop button...
Page 123
3.58 CONTROL CIRCUIT—RN250-325 COMP DESCRIPTION COMP DESCRIPTION Control circuit transformer HP-BP security control A10-1 Running lamp on control Security thermostat A10-2 Remote control Running lamp (Green) S30-1 Fan protector I A10-3 Dual button control lamp (Green) S30-2 Fan protector II A11-1 Stand-by lamp on control panel (red) A11-2...
Page 125
3.59 POWER CIRCUIT—RN250-325 COMP DESCRIPTION Control circuit transformer Compressor chankaser heater Main terminal block EMR4 Phase protection relay F1,F2 A01 Primary protection Compressor contactor (24V) Fan contactor (24V) Water motor Compressor Fan motor Thermal protection of Overload protector Water motor protection Main switch...
PRODUCT USER MANUAL SECTION 3 3.60 MAINTENANCE 3.60.2 M AINTENANCE BY THE USER 1. Keep the dryer clean. 3.60.1 M AINTENANCE BY AN NGINEER 2. In case of more than 4 pounds of refriger- ECHNICIAN ant, the dryer should be regularly checked 1.
PRODUCT USER MANUAL SECTION 3 3.62 TROUBLESHOOTING Problem Possible Cause Repair Comments Dryer is switched on, 3-phase dryers: The con- Invert two phases 3-phase dryers are equipped with indicator light is lit but the nection has inverted a phase controller to avoid the refrigerant compressor phases fans from turning in the opposite...
Page 129
SECTION 3 PRODUCT USER MANUAL Problem Possible Cause Repair Comments Dryer-on light is lit but Clogged condenser fins Clear fins or water The clogged fins in the con- Refrigerant Compressor or clogged water condenser of all denser will restrict the air pas- does not run.
Page 130
Mem- branes of pneumatically assisted drain have to be checked or replaced every 6 months. Sullair zero loss drain has to be cleaned with soft water when needed. Bypass system is open...
Page 131
SECTION 3 PRODUCT USER MANUAL Problem Possible Cause Repair Comments Water in system Excessive free moisture Check the separator In some system there may be an and drain system and com- accumulation of free moisture in pressor after cooler the line ahead of the dryer. If this ahead of the dryer.
Page 132
Some contamination may require extra maintenance of the heat exchanger. Contact your Sullair Distributor. The unit will not run or Line disconnect switch is Close the start or disconnect If the dryer is not operating, cycles off and on.
Page 133
SECTION 3 PRODUCT USER MANUAL Problem Possible Cause Repair Comments The unit will not run or Excessive compressed air Design conditions and correc- The dryer is designed for working cycles off and on. inlet temperature. tion factors are described in into calculated design conditions.
3.63 SETTINGS Superheat of Refrigerant Water flow valve Evaporating Security high Security low MODEL thermostatic Fan pressure switch temperature Drain timer (if water pressure pressure switch pressure switch expansion valve switch condenser) C° F° C° F° Open / Close RN-0005 5-10°C 41-50°F 2.05 bar...
Page 135
Table 3-2: DP Power 60H Rated STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbed GROUP SULLAIR PART SULLAIR PART Flow Port Size VOLTAGE Rated Conditions MODEL REF Drop Power scfm (psid) (kW) (in) Non- 115/1/60 RN-0005-115-60-A 02250193-807 0.14...
Page 136
Table 3-2: DP Power 60H Rated STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbed GROUP SULLAIR PART SULLAIR PART Flow Port Size VOLTAGE Rated Conditions MODEL REF Drop Power scfm (psid) (kW) (in) Non- 208-230/1/60 250.0 RN-0250-230-60-A 02250193-880 250.0...
Page 137
Table 3-2: DP Power 60H Rated STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbed GROUP SULLAIR PART SULLAIR PART Flow Port Size VOLTAGE Rated Conditions MODEL REF Drop Power scfm (psid) (kW) (in) Non- 575/3/60 1000.0 RD-1000-575-60-A...
Page 138
Table 3-3: DP Power 50H Rated STANDARD Capacity SCFM @ AIR COOLED MODEL WATER COOLED Pressure Absorbe GROUP SULLAIR PART SULLAIR PART Flow Port Size VOLTAGE Rated Conditions MODEL REF Drop d Power scfm (psid) (kW) (in) Non-Cycling 220/1/50 15.0...
Page 139
Table 3-4: Models 60HZ Capacity WATER Rated STANDARD SCFM @ AIR COOLED SULLAIR SULLAIR Pressure Absorbed GROUP COOLED Flow Port Size Width Height Depth Weight VOLTAGE Rated MODEL REF PART PART Drop Power MODEL REF Conditions scfm (psid) (kW) (in)
Page 140
Table 3-4: Models 60HZ Capacity WATER Rated STANDARD SCFM @ AIR COOLED SULLAIR SULLAIR Pressure Absorbed GROUP COOLED Flow Port Size Width Height Depth Weight VOLTAGE Rated MODEL REF PART PART Drop Power MODEL REF Conditions scfm (psid) (kW) (in)
Page 141
Table 3-4: Models 60HZ Capacity WATER Rated STANDARD SCFM @ AIR COOLED SULLAIR SULLAIR Pressure Absorbed GROUP COOLED Flow Port Size Width Height Depth Weight VOLTAGE Rated MODEL REF PART PART Drop Power MODEL REF Conditions scfm (psid) (kW) (in)
Page 142
Table 3-5: Models 50Hz Capacity SCFM Rated STANDARD AIR COOLED MODEL SULLAIR WATER COOLED SULLAIR Pressure Absorbed Port GROUP @ Rated Flow Width Height Depth Weight VOLTAGE PART MODEL REF PART Drop Power Size Conditions scfm (psid) (kW) (in) mm lbs...
E-680 CONTROLLER FOR REFRIGERANT DRYERS Section 4 E-680 CONTROLLER FOR REFRIGERANT DRYERS DESCRIPTION channel temperatures, set points, input and output states. Modbus protocol used The RD product is effectively the RN product with a communication. E-680 Controller. Refer to Section 3. The front panel of the controller contains a four line E-680 is designed as a controller for refrigerant type 20 character LCD display and 10 buttons that are...
Page 160
E-680 CONTROLLER FOR REFRIGERANT DRYERS SECTION 4 LED. “drain off” periods. When button is pressed the drain output is activated even if the dryer is in off buttons are used for starting and stopping state. the dryer respectively. If the dryer is stopped manually, it can not be started before “restart delay”...
Page 161
Remote Start (Press and operation screen is displayed as shown below. Release) D. INPUT 2 Remote Stop (Press and Release) D. INPUT 3 Compressor Fault SULLAIR D. INPUT 4 Compressor Overload D. INPUT 5 Fan Fault DEW POINT 16°C D. INPUT 6 Fan Overload D.
Page 162
E-680 CONTROLLER FOR REFRIGERANT DRYERS SECTION 4 ..INLET AIR TEMP. TOTAL TIME : 22.2 20°C ECO TIME EXCHANGER.TEMP. RUN TIME 22.2 18°C HIGH FILTER TIME: 22.2 LOW PRES.LINE TEMP. 1. REMOTE DISABLE 18°C 2. INLET AIR TEMP.HI HIGH PRES.LINE TEMP. 3.
Page 163
‘SENSOR BREAK’ message is displayed. The fourth screen displays the states of the compressor motor, fan motor, the phase sequence SULLAIR and remote disable. This information is compiled ECO(SEC.) from the digital inputs. (Digital Inputs 3 to 8) DEW POINT 8°C...
Page 164
E-680 CONTROLLER FOR REFRIGERANT DRYERS SECTION 4 4.2.3 4. Exchanger Temp. / High Alarm Setpoint ONFIGURATION (68°F/20°C) In order to enter into configuration mode, button 5. Low Pressure Line Temp. / Low Alarm Setpoint must be pressed at least 3 second duration. After this (23°F/-5°C) operation security code is asked.
Page 173
ED—RD700 AIR COOLED PART NUMBER DESCRIPTION M-CSI-0850 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-0850 CABINET REAR SEE REF. TABLE COMPRESSOR M-CTO-0700 CABINET TOP M-CON-0700 CONDENSER M-CBA-0850 CABINET BASE SEE REF. TABLE FAN MOTOR ASSEMBLY M-CBL-0850 CABINET LEG M-DRI-1200 DRIER-DEHYDRATOR M-HP1-0850 CABINET HORIZONTAL PROFILE 1 M-EXC-0200 HEAT EXCHANGER M-HP2-0850...
Page 177
ED—RD850 AIR COOLED PART NUMBER DESCRIPTION M-CSI-0850 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-0850 CABINET REAR SEE REF. TABLE COMPRESSOR M-CTO-0850 CABINET TOP M-CON-0850 CONDENSER M-CBA-0850 CABINET BASE SEE REF. TABLE FAN MOTOR ASSEMBLY M-CBL-0850 CABINET LEG M-DRI-1200 DRIER-DEHYDRATOR M-HP1-0850 CABINET HORIZONTAL PROFILE 1 M-EXC-0200 HEAT EXCHANGER M-HP2-0850...
Page 181
4.10 ED—RD1000 AIR COOLED PART NUMBER DESCRIPTION M-CSI-1000 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-1000 CABINET REAR SEE REF. TABLE COMPRESSOR M-CTO-1000 CABINET TOP M-CON-1000 CONDENSER M-CBA-1000 CABINET BASE SEE REF. TABLE FAN MOTOR ASSEMBLY M-CBL-1000 CABINET LEG M-DRI-1000 DRIER-DEHYDRATOR M-HP1-1000 CABINET HORIZONTAL PROFILE 1 M-EXC-1000 HEAT EXCHANGER...
Page 183
4.11 ED—RD1200 AIR COOLED PART NUMBER DESCRIPTION M-CRE-1000 CABINET REAR PART NUMBER DESCRIPTION M-CTO-1000 CABINET TOP M-CMP-1200-460-3-60-A COMPRESSOR M-CBA-1000 CABINET BASE M-CON-1000 CONDENSER M-CBL-1200 CABINET LEG SEE REF. TABLE FAN MOTOR ASSEMBLY M-HP1-1200 CABINET HORIZONTAL PROFILE 1 M-DRI-1200 DRIER-DEHYDRATOR M-HP2-1200 CABINET HORIZONTAL PROFILE 2 M-EXC-1200 HEAT EXCHANGER...
Page 185
4.12 ED—RD1600 AIR COOLED PART NUMBER DESCRIPTION M-CSI-6000 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-6000 CABINET REAR M-CMP-1600-460-3-60-A COMPRESSOR M-CTO-6000 CABINET TOP M-CON-1600 CONDENSER M-CBA-6000 CABINET BASE M-FMT-1600-460-3-60-A FAN MOTOR ASSEMBLY M-CBL-6000 CABINET LEG M-DRI-2400 DRIER-DEHYDRATOR M-HP1-2000 CABINET HORIZONTAL PROFILE 1 M-EXC-2000 HEAT EXCHANGER M-HP2-2000...
Page 187
4.13 ED—RD2000 AIR COOLED PART NUMBER DESCRIPTION M-CRE-2000 CABINET REAR PART NUMBER DESCRIPTION M-CTO-2000 CABINET TOP M-CMP-2000-460-3-60-A COMPRESSOR M-CBA-2000 CABINET BASE M-CON-2400 CONDENSER M-CBL-2000 CABINET LEG M-FMT-2000-460-3-60-A FAN MOTOR ASSEMBLY CABINET HORIZONTAL PROFILE M-DRI-2400 DRIER-DEHYDRATOR M-HP1-2000 M-EXC-2000 HEAT EXCHANGER CABINET HORIZONTAL PROFILE M-HP2-2000 M-EXV-2000 EXPANSION VALVE...
Page 189
4.14 ED—RD2400 AIR COOLED PART NUMBER DESCRIPTION M-CSI-2400 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-2400 CABINET REAR M-CMP-2400-460-3-60-A COMPRESSOR M-CTO-2400 CABINET TOP M-CON-2400 CONDENSER M-CBA-2400 CABINET BASE M-FMT-2000-460-3-60-A FAN MOTOR ASSEMBLY M-CBL-2400 CABINET LEG M-DRI-2400 DRIER-DEHYDRATOR M-HP1-2400 CABINET HORIZONTAL PROFILE 1 M-EXC-2400 HEAT EXCHANGER M-HP2-2400...
Page 191
4.15 ED—RD3000 AIR COOLED PART NUMBER DESCRIPTION M-CSI-3000 CABINET SIDE PART NUMBER DESCRIPTION M-CRE-3000 CABINET REAR M-CMP-300-460-3-60-A COMPRESSOR M-CTO-3000 CABINET TOP M-CON-3000 CONDENSER M-CBA-3000 CABINET BASE M-FMT-2000-460-3-60-A FAN MOTOR ASSEMBLY M-CBL-6000 CABINET LEG M-DRI-3800 DRIER-DEHYDRATOR M-HP1-3000 CABINET HORIZONTAL PROFILE 1 M-EXC-3000 HEAT EXCHANGER M-HP2-3000...
Page 193
4.16 ED—RD3800 AIR COOLED PART NUMBER DESCRIPTION M-SCI-3800 CABIENT SIDE-LEFT PART NUMBER DESCRIPTION M-SCI-3800 CABINET SIDE-RIGHT M-CMP-3800-460-3-60-A COMPRESSOR M-CRE-3800 CABINET REAR M-CON-3800 CONDENSER M-CTO-3800 CABINET TOP M-FMT-2000-460-3-60-A FAN MOTOR ASSEMBLY M-CBA-3800 CABINET BASE M-DRI-3000 DRIER-DEHYDRATOR M-CBL-6000 CABINET LEG M-EXC-3800 HEAT EXCHANGER M-HP1-3800 CABINET HORIZONTAL PROFILE 1 M-EXV-3800...
Page 195
4.17 ED—RD5000 AIR COOLED PART NUMBER DESCRIPTION M-CSI-5000 CABINET SIDE-RIGHT PART NUMBER DESCRIPTION M-CRE-5000 CABINET REAR M-CMP-5000-460-3-60-A COMPRESSOR M-CTO-5000 CABINET TOP M-CON-5000 CONDENSER M-CBA-5000 CABINET BASE M-FMT-5000-460-3-60-A FAN MOTOR ASSEMBLY M-CBL-6000 CABINET LEG M-DRI-5000 DRIER-DEHYDRATOR M-HP1-5000 CABINET HORIZONTAL PROFILE 1 M-EXC-5000 HEAT EXCHANGER M-HP2-5000...
Page 197
4.18 ED—RD6000 AIR COOLED PART NUMBER DESCRIPTION 5-CTO-6000 CABINET TOP PART NUMBER DESCRIPTION M-CBA-6000 CABINET BASE M-CMP-6000-460-3-60-A COMPRESSOR M-CBL-6000 CABINET LEG M-CON-6000 CONDENSER M-HP1-6000 CABINET HORIZONTAL PROFILE 1 M-FMT-6000-460-3-60-A FAN MOTOR ASSEMBLY M-HP2-6000 CABINET HORIZONTAL PROFILE 2 M-DRI-6000 DRIER-DEHYDRATOR M-CTC-6000 CABINET TOP CORNER M-EXC-6000 HEAT EXCHANGER...
Page 201
4.20 ID—RD500-850 DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-918 400v/3Ph/50Hz AIR COOLED RD500 02250193-850 230V/3Ph/60Hz AIR COOLED RD500 02250193-982 460V/3Ph/60Hz AIR COOLED RD500 02250193-137 575V/3Ph/60Hz AIR COOLED RD500 02250193-919 400V/3Ph/50Hz AIR COOLED RD700 02250193-851 230V/3Ph/60Hz AIR COOLED RD700 02250193-983 460V/3Ph/60Hz AIR COOLED RD700...
Page 203
4.21 ID—RD1000-1200 AIR COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-921 400V/3Ph/50Hz AIR COOLED RD1000 02250193-985 460V/3Ph/60Hz AIR COOLED RD1000 022501934-140 575V/3Ph/60Hz AIR COOLED RD1000 02250193-922 400V/3Ph/50Hz AIR COOLED RD1200 02250193-986 460V/3Ph/60Hz AIR COOLED RD1200 02250194-141 575V/3Ph/60Hz AIR COOLED RD1200 GROSS WITHOUT PALLET SIZE...
Page 205
4.22 ID—RD1000-1200 WATER COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-949 400V/3Ph/50Hz WATER COOLED RD1000 02250194-109 460V/3Ph/60Hz WATER COOLED RD1000 02250194-163 575V/3Ph/60Hz WATER COOLED RD1000 02250193-950 400V/3Ph/50Hz WATER COOLED RD1200 02250194-110 460V/3Ph/60Hz WATER COOLED RD1200 02250194-164 575V/3Ph/60Hz WATER COOLED RD1200 GROSS WITHOUT PALLET SIZE...
Page 207
4.23 ID—RD1600-200 AIR COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-923 400V/3Ph/50Hz AIR COOLED RD1600 02250193-988 460V/3Ph/60Hz AIR COOLED RD1600 02250194-142 575V/3Ph/60Hz AIR COOLED RD1600 02250193-924 400V/3Ph/50Hz AIR COOLED RD2000 02250193-989 460V/3Ph/60Hz AIR COOLED RD2000 02250194-143 575V/3Ph/60Hz AIR COOLED RD2000...
Page 209
4.24 ID—RD1600-2000 WATER COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-951 400V/3Ph/50Hz WATER COOLED RD1600 02250194-113 460V/3Ph/60Hz WATER COOLED RD1600 02250194-165 575V/3Ph/60Hz WATER COOLED RD1600 02250193-953 400V/3Ph/50Hz WATER COOLED RD2000 02250194-114 460V/3Ph/60Hz WATER COOLED RD2000 02250194-166 575V/3Ph/60Hz WATER COOLED RD2000...
Page 211
4.25 ID—RD2400-3000 AIR COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-925 400V/3Ph/50Hz AIR COOLED RD2400 02250193-990 460V/3Ph/60Hz AIR COOLED RD2400 02250194-144 575V/3Ph/60Hz AIR COOLED RD2400 02250193-926 400V/3Ph/50Hz AIR COOLED RD3000 02250193-991 460V/3Ph/60Hz AIR COOLED RD3000 02250194-145 575V/3Ph/60Hz AIR COOLED RD3000...
Page 213
4.26 ID—RD2400-3000 WATER COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-954 400V/3Ph/50Hz WATER COOLED RD2400 02250194-115 460V/3Ph/60Hz WATER COOLED RD2400 02250194-167 575V/3Ph/60Hz WATER COOLED RD2400 02250193-955 400V/3Ph/50Hz WATER COOLED RD3000 02250194-116 460V/3Ph/60Hz WATER COOLED RD3000 02250194-168 575V/3Ph/60Hz WATER COOLED RD3000...
Page 215
4.27 ID—RD3800 AIR COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-927 400V/3Ph/50Hz AIR COOLED RD3800 02250193-992 460V/3Ph/60Hz AIR COOLED RD3800 02250194-146 575V/3Ph/60Hz AIR COOLED RD3800...
Page 217
4.28 ID—RD3800 WATER COOLED DRYER PART NUMBER POWER RATINGS COOLING DECAL 02250193-956 400V/3Ph/50Hz WATER COOLED RD3800 02250194-117 460V/3Ph/60Hz WATER COOLED RD3800 02250194-169 575V/3Ph/60Hz WATER COOLED RD3800...
Page 219
4.29 P&I—RD400 POS. DESCRIPTION COMPRESSOR REFRIGERANT CONDENSER FAN MOTOR FAN MOTOR SWITCH EVAPORATOR AIR-AIR EXCHANGER PRESSURE REGULATOR DEHYDRATOR DEW POINT INDICATOR BY-PASS VALVE LIQUID RECEIVER NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION MODEL REFRIGERANT TYPE RD400 6.613 R134A...
Page 221
REFRIGERANT CONDENSER FAN MOTOR FAN MOTOR SWITCH EVAPORATOR AIR-AIR EXCHANGER PRESSURE REGULATOR DEHYDRATOR DEW POINT INDICATOR BY-PASS VALVE LIQUID RECEIVER LIQUID SEPARATOR NOTE: MARK/TAG COMPONENT/CONTAINER WITH SULLAIR P/N AND REVISION MODEL REFRIGERANT TYPE RD500 R134A 8.818 RD700 9.369 RD850 11.023...
4.47 POWER CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000 02250195-307...
Page 255
4.47 CONTROL CIRCUIT—RD400-500-700-850-1000-1200-1600-2000-2400-3000-3800-5000-6000 COMP DESCRIPTION Control circuit transformer A30-1/A30-2 Compressor chankaser heaters Main terminal block EMR4 Phase protection relay F1,F2 A01 primary protection Compressor contactor (24V) K10-1 Fan contactor (24V) K10-2 Fan contactor (24V) Water motor M01-1/M01-2 Compressors (400V-440V) M10-1 Fan motor (400V-440V) M10-2 Fan motor (400V-440V)
Page 256
Capacity Rated SCFM @ AIR COOLED WATER COOLED Pressure Absorbed Port SULLAIR PART SULLAIR PART Flow Width Height Depth Weight Rated MODEL REF MODEL REF Drop Power Size Conditions scfm (psid) (kW) (in) 400.0 RD-0400-230-3-60-A 02250193-849 400.0 2.13 2" NPT 23.5 49.6 1260 28.3...
Page 257
Capacity STANDARD SCFM @ AIR COOLED SULLAIR WATER COOLED SULLAIR Rated Pressure Absorbed GROUP VOLTAGE Rated MODEL REF PART MODEL REF PART Flow [1] Drop Power Conditions scfm (psid) (kW) Non-Cycling 400/3/50 400.0 RD-0400-400-3-50-A 02250193-917 400.0 1.92 Non-Cycling 400/3/50 500.0...
Page 268
Always air. Always there. WWW.SULLAIR.COM SULLAIR CORPORATION 3700 East Michigan Boulevard • Michigan City, Indiana, 46360 U.S.A. Telephone: 1-219-879-5451 Printed in the U.S.A. Specifications subject to change without prior notice. E11EP...