Options and Factory Defaults
Options are set using the Menu key. The MENU key is also used to set the schedule.
Scroll through the options by pressing and holding the MENU. Schedule options are displayed first, then Options. Continue to
press and hold until Option 01 is displayed. Continue to press and hold MENU to see all options. Press ENTER to return to
normal operation.
The following options are available. Some options should be set by the installer and have been indicated as Installer.
Option 1
Cleaning the touch screen
Option 2
Changing the LCD contrast
Option 3
Setting discharge air temp to detect heating
Option 4
Setting discharge air temp to detect cooling
Option 5
Setting the night time or off airflow
Option 6
Set the change in damper position per degree
Option 7
Turning on temperature in the display in
Remote Control Mode
Option 8
Set the minimum airflow allowed

Option 1: Cleaning the Touch Screen

This option disables the touchscreen for 30 seconds to enable
you to clean the touchscreen
Press and hold the MENU key to display
1.
Option 01.
Press the UP key to select On.
2.
3.
Press the ENTER key to start a 30 second
count down.
During the 30 second countdown, use a
damp, soft cloth to clean the touchscreen.
After 30 seconds, the remote thermostat
returns to normal operation.

Option 2: Changing the LCD Contrast

Factory Default
1
1.
Press and hold the MENU key to display
Option 02.
2.
Use the UP / DOWN keys to change the
LCD contrast.
3.
Press ENTER to save the changes and
return to normal operation.
Or press and hold MENU to save the
4.
changes and display the next option.
User
User
Installer
Installer
User
Installer
User
Installer
Option 3: Setting discharge air
temperature for detecting heating call
Factory Default
If the discharge air temperature is below the default of 95 degrees, a
heating call will not be detected and the thermostat will not control
airflow properly. Use this option to lower the temperature setting
for discharge air so a heating call will be detected.
1.
Press and hold the MENU key to display
Option
Option 03.
2.
Use the UP / DOWN keys to change the
heating detect setpoint temperature.
Menu
Press ENTER to save the changes and
3.
Enter
return to normal operation.
Or press and hold MENU to save the
4.
changes and display the next option.
Option 4: Setting discharge air
temperature for detecting cooling call
Factory Default
If the discharge air temperature is above the default of 65 degrees, a
cooling call will not be detected and the thermostat will not control
airflow properly. Use this option to raise the temperature setting for
discharge air so a cooling call will be detected.
Option
1.
Press and hold the MENU key to display
Option 04.
2.
Use the UP / DOWN keys to change the
Menu
cooling detect setpoint temperature.
Enter
Press ENTER to save the changes and
3.
return to normal operation.
Or press and hold MENU to save the
4.
changes and display the next option.
6
Default = Off
Options = Off or On
Default = 10
Options = 1 - 10
Default = 95
Options = 85 - 120
Default = 65
Options = 60 - 75
Default = 50%
Options = 20% - 100%
Default = 10%
Options = 5% - 25%
Default = Off
Options = Off or On
Default = 0%
Options = 0% - 50%
95
65
o
F
Option
Menu
Enter
o
F
Option
Menu
Enter