Siemens MXG461B Series Technical Instructions page 3

Modulating control valves with magnetic actuators, positioning control and position feedback for domestic water
Hide thumbs Also See for MXG461B Series:

Advertisement

MXG461B Series Modulating Control Valve
with Magnetic Actuator
Control
Basic Diagram
Spring Return Action
LED
Green
Red
Both
Siemens Industry, Inc.
The magnetic actuator can be driven by any controller with a 0/2 to 10 Vdc or 0/4 to
20 mA output signal.
To achieve optimum control performance, it is recommended to use a 4-wire connection
for the valve.
NOTE: When using a dc power supply a 4-wire connection is mandatory.
The controller's signal ground terminal M must be connected to the valve's terminal M.
Terminals M and G0 have the same potential and are internally interconnected in the
valve's
electronics.
CAUTION:
You must use a four-wire connection with Vdc power supply.
If the power or positioning signal is switched off or fails, the valve control path
(port A → AB) is automatically closed by the force of the spring.
Table 2. Indication of Operating State.
Indication
Operating State,
Function
Lit
Control mode
Calibration
Flashing
In manual control
Calibration error
Lit
Internal error
Mains fault
Flashing
DC Supply -/+
No power supply
Dark
Electronics faulty
Remarks, Troubleshooting
Normal operation; everything OK.
Wait until calibration is finished
(green or red LED will be lit).
Hand wheel in Man or Off position.
Recalibrate (bridge contacts behind the
calibration slot).
Replace electronics module.
Check electric main network (outside the
frequency or voltage range);
Vdc supply +/- connection polarity.
Check electric main network, check wiring.
Replace electronics module.
Technical Instructions
Document Number 125-4461
October 23, 2018