Water control
It is necessary to analyse the quality of water by checking pH, electrical conductivity, ammonia ion content, sulphur
content, and others. The following is the recommended standard water quality.
Item
Standard Quality pH(25°C)
Electrical Conductivity(ms/m) (25°C)
(μS/cm) (25°C) {2}
Chlorine lon (mg CL¯/l)
Sulphur Acid lon (mg SO ¯/l)
The Amount of Acid Consumption
(pH4.8)(mg CaCO3/l)
Total Hardness(mg CaCO3/l)
Calcium Hardness(mg CaCO3/l)
Silica L(mg SO¯/l)
Reference Quality Total iron(mg Fe/l)
Total Copper(mg Cu/l)
Sulphur Ion(mg S2-/l)
Ammonium Ion(mg NH4-/l)
Remaining Chlorine(mg Cl/l)
Floating Carbonic Acid (mg CO2/l)
Index of Stability
NOTE
•The mark "" in the table means the factor concerned with the tendency of corrosion or deposits of scales.
•The value showed in "{}" are for reference only according to the former unit.
Chilled Water System
Circulating Water
Supply Water
(20°C Less than)
6.8~8.0
Less than 40
Less than 43
Less than 400
Less than 400
Less than 50
Less than 50
Less than 50
Less than 50
Less than 50
Less than 50
Less than 70
Less than 70
Less than 50
Less than 50
Less than 30
Less than 30
Less than 1.0
Less than 0.3
Less than 1.0
Less than 0.1
It shall not be detected
Less than 1.0
Less than 0.1
Less than 0.3
Less than 0.3
Less than4.0
Less than4.0
6.8~8.0
50
Corrosion Deposits of Scales
6.8~8.0
●
●
●
●
●
●
●
●
●
●
-
●
Tendency
●
●
●
●
●
●
●
●
Need help?