Cpu 318-2 - Siemens SIMATIC S7-300 Series Reference Manual

Cpu specifications
Hide thumbs Also See for SIMATIC S7-300 Series:
Table of Contents

Advertisement

CPU 318-2, Technical Data
CPU and Product Version
MLFB
6ES7 318-2AJ00-0AB0
S
Hardware version
03
S
Firmware version
V 3.0
S
Matching programming
STEP 7 V 5.1 +
Service Pack 02
package
Memory
Work memory
S
integral
256 KB data/
256 KB code
S
Expandable
no
Load memory
S
integral
64 KB
S
Expandable FEPROM
Up to 4 MB
S
Expandable RAM
Up to 2 MB
Backup
Yes
S
With battery
All data
S
Without battery
max. 11 KB
Processing times
Processing times for
S
0.1 ms minimum
Bit instructions
S
0.1 ms minimum
Word instructions
S
0.1 ms minimum
Double integer
arithmetic
S
0.6 ms minimum
Floating-point
arithmetic
Timers/Counters and their retentive characteristics
S7 counters
512
S
Adjustable retentivity
from C 0 to C 511
S
Preset
from C 0 to C 7
S
Counting range
0 to 999
IEC Counters
Yes
S
Type
SFB
S7 timers
512
S
Adjustable retentivity
from T 0 to T 511
S
Preset
No retentive times
S
Timing range
10 ms to 9990 s
IEC Timers
Yes
S
SFB
Type
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
Data areas and their retentive characteristics
Retentive data area as a
max. 11 KB
whole (inc. flags, timers,
counters)
Bit memories
8192
S
Adjustable retentivity
MB 0 to MB 1023
S
Preset
MB 0 to MB 15
Clock memories
8 (1 memory byte)
Data blocks
2047 (DB 0 reserved)KB
S
Size
max. 64 KB
S
Adjustable retentivity
max. 8 DB, max. 8192 data
bytes
S
Preset
No retentivity
Local data (alterable)
max. 8192 bytes
S
Preset
3584 bytes
S
Per priority class
256 bytes (expandable to
8192 bytes)
Blocks
OBs
See Instruction List
S
Size
max. 64 KB
Nesting depth
S
Per priority class
16
S
additional levels within
3
an error OB
FBs
max. 1024
S
Size
max. 64 KB
FCs
max. 1024
S
Size
max. 64 KB
Address areas (I/O)
Peripheral address area,
max. 8 KB/8 KB (freely
digital/analog
addressable)
S
Distributed
MPI/DP Interface
max. 2 KB/2 KB
DP interface
max. 8 KB/8 KB
Process image
2048/2048 bytes
(configurable)
S
Preset
256/256 bytes
Digital channels
max. 65536 (minus 1 byte
diagnostic address per DP
slave)/65536
S
Centralized
max. 1024/1024
Analog channels
max. 4096/4096
S
Centralized
max. 256/128
CPUs
1-71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents