Siemens SIMATIC S7-300 Series Reference Manual page 83

Cpu specifications
Hide thumbs Also See for SIMATIC S7-300 Series:
Table of Contents

Advertisement

Address areas (I/O)
Peripheral address area,
2 KB/2 KB (freely
digital/analog
addressable)
S
Distributed
2 KB/2 KB
Process image (cannot be
128/128 bytes
customized)
Digital channels
max. 16384 (minus 1 byte
diagnostic address per DP
slave)/16384
S
Centralized
max. 1024/1024
Analog channels
max. 1024 (minus 1 byte
diagnostic address per DP
slave)/1024
S
Centralized
max. 256/128
Configuration
Rack
max. 4
Modules per
max. 8
Rack
Number of DP masters
S
integral
1
S
via CP
1
S7 message functions
Simultaneously active
max. 50
Alarm-S blocks
Time
Real-time clock
Yes
S
Backed-up
Yes
S
Accuracy
See Section 1.1.6
Operating hours counter
1
S
Number
0
S
Value range
0 to 32767 hours
S
Selectivity
1 hour
S
Retentive
Yes
Clock synchronisation
Yes
S
On PLC
Master
S
On MPI
Master/Slave
Testing and commissioning functions
Status/Modify Variables
Yes
S
Variable
Inputs, outputs, flags, DBs,
timers, counters
S
Number
Monitor Variables
max. 30
max. 14
Modify Variables
Force
Yes
S
Variable
Inputs, outputs
S
Number
max. 10
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
Monitor block
Yes
Single sequence
Yes
Breakpoint
2
Diagnostic buffer
Yes
S
Number of entries
100
(non-alterable)
Communication functions
PD/OP communication
Yes
Global data communication
Yes
S
Number of GD packets
Sender
1
Receiver
1
S
Size of GD packets
max. 22 bytes
Number of which
8 bytes
consistent
S7 basic communication
Yes
S
User data per job
max. 76 bytes
Number of which
32 bytes for X/I_PUT/_GET;
consistent
76 bytes for
X_SEND/_RCV
S7 communication
Yes (server)
S
User data per job
max. 160 bytes
Number of which
32 bytes
consistent
S7-compatible
Yes (via CP and loadable
communication
FC)
S
User data per job
Dependent on CP
Number of which
Dependent on CP
consistent
Standard communication
Yes (via CP and loadable
FC)
S
User data per job
Dependent on CP
Number of which
Dependent on CP
consistent
Number of connection
12 for PD/OP/S7 basic/S7
resources
communication
S
Reservation for
PD communication
max. 11
User-definable
from 1 to 11
1
Default
OP communication
max. 11
User-definable
from 1 to 11
1
Default
S7 basic
max. 8
communication
from 0 to 8
User-definable
8
Default
Routing connections
max. 4
CPUs
1-67

Hide quick links: