1234 = password, 0 = zero, space counts as a character and is therefore important.
1234 N0 xxxxxxxx yyyy
Define the phone
number of the unit
(N0 = N + zero)
and (optionally)
change password
Receivers
1234 N1 11111111
Register no. 1, no.
2 and so on
1234 N2 22222222
1234 N1
Delete no. 1
Text on inputs
1234 Ax TEXT
Create
1234 Lx TEXT
1234 Ax
Delete
1234 Lx
1234 CT
Only alarm if text
is created
1234 V1 S yyyy zzzz
Create analogue
input
1234 V1 M yyyy zzzz
1234 V1 A TEXT
SET-UP
Set-up with text message
xxxxxxxx = the unit phone no. yyyy = new four
digit password
Defines unit phone no. (N0) and create new
password.
New password is not necessary.
Registers receiver 1 and 2 to receive text to phone
number 11 11 11 11 and 22 22 22 22
All in all 25 receivers.
Deletes receiver 1
TEXT on input x by opening/closing. x = 0,1, or 2
TEXT on input x by opening/closing. x = 0,1 or 2
Deletes TEXT for input x by opening/closing.
x = 0, 1 or 2.
Deletes TEXT for input x by opening/closing.
x = 0, 1 or 2
The unit ignores input that does not have text
connected to it
Set-up of the scale (yyyy = minimum zzzz =
maximum) for 0-10 V and for 0-20 mA.
Set-up of values for intervals LOW, MIDDLE and
HIGH (Point 1 and Point 2) on analogue input 1.
If the value on input becomes larger or smaller
than yyyy (Point 1) or larger or smaller than zzzz
(Point 2), an alarm is sent.
Alarm text LOW on analogue input 1 is sent when
the value becomes smaller than the value defined
in Point 1/yyyy (Vx M yyyy zzzz).