 The device shouldn't be inclined so to lean sideward more
than 15 degrees. This situation damages the device
compressor.
 When your device is deactivated, make sure that the
dampers aren't turned off.
 The device should be kept where the relative humidity rate
doesn't exceed 80% and ambient temperature should be
kept between -25 and 55
 Dust, gas, steam and chemical materials such as abrasives
shouldn't be contacted with the device and device elements.
 Roof-type air conditioners might generally get damaged
generally during transport, loading and lowering and especially in case a crane is used. Pallet truck or
forklift should be used while lifting and transporting small devices by considering device weights
determined at tables given on delivery note or size information section.
 In transports with forklift, the device should be placed evenly on knives. In case it is placed under knives,
the bottom of device will get damaged.
 After placing the device on roof connector, lifting legs (a quantity of four) could be taken off.
 Lifting and lowering of big devices should be carried on with a crane by using suitable equipments.
 Silk rope suitable to device size and weight should be used for device security and so that the device
doesn't get damaged while lifting and lowering with the crane, additional profiles should be used to
prevent ropes from tightening on the device body and the device should be transported by considering its
weight and having taken the necessary security precautions to prevent turning over and slipping.
 During lifting and transporting the device, no one should stand under the device and at movement area,
crush hazard should be paid attention to.
 Before packaging, markings and warning tags showing notification values of the device should have been
placed properly. While lifting the device, the weight defined in KG at the tag should be paid attention to.
 Devices should be wrapped with nylon and they should be packaged on lift feet against risks of getting
scratched, getting deflected and deformed while loading, transporting and shipping them. Palletized
boxes used against probable quakes and future damages on them while shipping devices are bigger than
the devices in size. Parts of the devices with low body endurance are supported with styropor
(polystyrene) of 1 cm and rapped with nylon.
 If it needs storing for a while before install the device on its place, this storage should be a dry
environment not to get affected by External air conditions.
 General device sizes according to models are defined below. (For more detailed size data, you may look
at the "Size Data" section.)
Model
URTP055
Sizes
1858*1730*
1253
[W*L*H] [mm]
WARNING: No damage caused on the device due to wrong transport and storage isn't covered by the
warranty.
o
C.
URTP070
URTP090
1858*1730*
2334*1951*
1253
1253
URTP110
URTP140
2334*1951*
2926*2165*
1253
1253
16
URTP180
URTP230
2926*2165*
3853*2267*
1453
1453