Page 1
ROOF TYPE AIR CONDITIONER INSTRUCTIONS FOR INSTALLATION, COMMISSIONING, MAINTENANCE and USE...
Page 2
Please read these instructions first! Dear Customer, Thank you for choosing UNTES. Please be sure that all of our products are produced in modern production facilities and subjected to a continuous quality control procedure to provide you the highest performance.
TABLE OF CONTENT TABLE OF CONTENT ..........................3 1. INTRODUCTION AND GENERAL NOTIFICATIONS ............... 7 1.1. General Warnings ............................7 1.2. Signs and Marks Used on the Product ...................... 10 1.3. Operation Limits ............................11 1.4. List of Spare Parts ............................. 12 1.5.
Page 4
4.2.3. With Side Output Return Fan ........................ 27 4.2.4. Down Output ............................28 4.2.5. With Down Output Exhaust Fan ......................29 4.2.6. With Down Output Return Fan ......................30 5. TECHNICAL AND CAPACITY DATA ....................31 5.1. Device Tables ............................31 6.
Page 5
9.5. Commissioning ............................48 9.6. Service and Maintenance .......................... 48 9.7. Failure and Troubleshooting ........................48 10. COMMISSIONING (COOLING ONLY OR HEAT PUMP) ............. 48 10.1. Pre-Controls ............................49 10.1.1. Control of Power Supply Connection ....................49 10.1.2. Control of Additional Heater Connections ..................49 10.1.3.
Page 6
12.2. Adjusting of Set Values of the Unit ......................60 12.3. Room Control Panel Lock of the Unit ....................60 12.4. Alarm Management of Room Control Unit .................... 60 12.5. Logging in PLC User’s Password ......................64 12.6. Starting and Stopping of the Unit ......................65 12.7.
1. INTRODUCTION AND GENERAL NOTIFICATIONS The manual hereby was prepared according to TS 11823/95 Standard and users need to know these instructions and the other montage instructions given with this manual before starting-up their devices. With this manual, a high-security reference guide was envisioned to be prepared for installation, commissioning, operation and maintenance of roof type devices (URTP).
Page 8
Hardness of the water being used exceeds the value of 30ºfH; water should be subjected to hardness reduction procedure. PH level of the water being used is between 6 and 8, or at the level of 7.5 if possible. ...
Page 9
The device involves cooling gas and transporting procedures should be applied by complying with all conditions of local regulations. In case of gas leakage, gas accumulation inside closed areas causes a high risk. Gas may lead to suffocation by replacing oxygen (in case it is inhaled for a long period or it is exposed of, it causes irritation on skin and at eyes, irregular heartbeat, loss of consciousness and even death) or explosions.
Limits Operation limits of the device are given at the table below. It is vital to refer to these data so that the device operates properly. External Ambient Air Mixed Air Cooling ° C ° C ° C ° C Minimum Average 21,5...
Moreover, Modbus providing communication with building automation system is procured as standard. Along with that, additional modules could be added by the use of other various building automation systems (Bacnet MS-TP, Bacnet IP, and Lonworks). 2.2. Compressors In URTP devices, hermetic scroll-type compressors were used. There are lubricant pans, pan heaters and vibration absorber wedges as standard at compressors for all models.
2.7. Thermostatic Expansion Valve Thermostatic expansion valves are cooling system elements and have functions for the system to work correctly. They are connected to the evaporator inlet on liquid line. They enable that right amount of refrigerant is sent to the evaporator and lowers pressure, evaporation pressure and temperature of refrigerant. Thermostatic expansion valves enable to have a stable superheating degree at the evaporator.
2.10. Refrigerant (R410A) In this URTP device, R410A gas is used as cooling gas. These devices are designed according to characteristics of this gas and shouldn’t be operated with another kind of gas in no way. Global heating potential of R410A gas is GWP: 1975. This gas involves fluorinated greenhouse gasses within the framework of Kyoto Protocol.
Page 16
If it needs storing for a while before install the device on its place, this storage should be a dry environment not to get affected by External air conditions. General device sizes according to models are defined below. (For more detailed size data, you may look at the “Size Data” section.) Model URTP055 URTP070 URTP090 URTP110 URTP140...
There should be left extra spaces at the width to let for maintenance works at the area where the device will be placed. Spaces to be needed for placement according to device models are seen below. Size\ Model URTP055 URTP070 URTP090...
scale of 2 x C, the wall doesn’t obstruct air flow. If two devices are to work adjacent to each other and condenser and condenser surfaces are to face each other, the distance in-between should be higher than 2 x C +300 mm. If the device is to work on a mezzanine floor, condenser air duct slice should be at least 1.5 fold of fan inlet diameter.
Details about placement of the device are given at the figures below. Necessary spaces are left on roof concrete for roof connection of the device place of which is determined. After roof connection elements are placed o at the space left, the device is placed securely with fill material. Outer surface of roof connector and ground should be covered with water-tight isolation material.
Page 20
For air duct-connection systems from the bottom; For air duct-connection systems from sides; Some points should be paid attention to in movements of air ducts right after the device. If connection is to be provided via an elbow joint (and this isn’t a preferred method), this elbow joint should absolutely have a wide curve and shouldn’t narrow right after the section.
3.5. Conservation Precautions for the Device from External Air Conditions Suitable choice of place and placement are required so that the device doesn’t get exposed to External air conditions. If the device is to operate at an area with high snow fall rate, it should be paid attention to that condenser side of the device not stay under snow.
3.7. Drainage Connection In drainage piping, it should be regarded that pipe diameter to be smaller than condensation pan outlet diameter. Connection between drainage pipe and condensation pan should be made with union flange so that dirt occurred in the condensation pan and pipes could easily be cleaned. ...
4.2. Size Data of Roof Curb Variations of roof connection elements of URTP devices are as below. 4.2.1. Side Flow Supply ROOF CONNECTOR WITH SIDE OUTPUT 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718...
4.2.2. With Side Flow Exhaust Fan ROOF CONNECTOR WITH SIDE OUTPUT AND AXIAL EXHAUST FAN 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718 1718 2192 ① ⑥ Alternative duct connection of absorption air 1 Balance Connection Extension ②...
4.2.3. With Side Flow Return Fan ROOF CONNECTOR WITH SIDE OUTPUT AND AXIAL RETURN FAN 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718 1718 2192 1100 1070 ① ⑦ Duct connection space of absorption air Axial return fans ②...
4.2.4. Down Flow Supply DOWN OUTPUT ROOF CONNECTOR 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718 1718 2192 ① Duct connection space of blow air ② Duct connection space of absorption air ③...
4.2.5. With Down Flow Exhaust Fan ROOF CONNECTOR WITH DOWN OUTPUT AND AXIAL RETURN FAN 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718 1718 2192 ① Duct connection space of blow air ②...
4.2.6. With Down Flow Return Fan ROOF CONNECTOR WITH DOWN OUTPUT AND AXIAL RETURN FAN 1619 1619 1834 1834 1988 1988 2179 1366 1366 1748 1748 2358 2358 3081 1333 1333 1718 1718 2192 1090 ① ④ Duct connection space of blow air Balance connection extension ②...
6. ELECTRICAL DATA 6.1. Power Data of Basic Elements and Options SERİ [BSC_SS] URTP URTP URTP URTP URTP URTP URTP EXPLANATION Installed Power without Option [For Low Pressure] 17081 20550 27847 32390 40830 52780 69650 Current in Nominal Capacity ** 26,1 30,5 39,9...
Sizes of power line cable to be spanned for the device panel should comply with the standards (YVV(NYY)TS 212). The Nominal cable sections are given at the table below. Regarding the voltage drop calculation, you may take this table as basis in your calculations. Power cables are used under earth, in cable ducts, at inner and outer spaces, under sweet water (under salty water in case of being specially produced), at power plants, industrial plants and switch stations.
Electric connections to be provided from outside should comply with the rules below. These rules aren’t just recommendations but the rules to be complied with in terms of user safety; Equipments and cables to be used in electricity connection should be chosen according to maximum current values given at schema and the catalogue in the following.
6.5. Motor Tables PERFORMANCE 3 phase, 400 V, 50 Hz Service type : S1 (continuous) Cycle, power factor, performance, moving rotor current Protection level : IP 55 (TEFV) 400 V,50 Hz Torque values Isolation class : F (105K) Temperature increase :Class B (80K) FULL LOAD DATA Moment...
Page 37
PERFORMANCE 3 faz, 400 V, 50 Hz Service type : S1 (continuous) Cycle, power factor, performance, moving rotor current Protection level : IP 55 (TEFV) 400 V,50 Hz Torque values Isolation class : F (105K) Temperature increase :Class B (80K) FULL LOAD DATA Moment Approximate...
Page 38
PERFORMANCE 3 faz, 400 V, 50 Hz Service type : S1 (continuous) Cycle, power factor, performance, moving rotor current Protection level : IP 55 (TEFV) 400 V,50 Hz Torque values Isolation class : F (105K) Temperature increase :Class B (80K) FULL LOAD DATA Moment of Approximate...
7. ADDITIONAL GAS-FIRED HEATING OPTION 7.1. Introduction In URTP devices, there is optionally an alternative system to water or electric heating systems with additional gas fired heating module. One of the fuel types of natural gas should be used for gas fired modules.
7.2. Gas Connection Gas connection of the device’s gas firing unit should be provided suitably to the gas pass equipments described below and in the right alignment. Gas connections should be made with gas pipes in compliance with local rules. Tightening IMPORTANT: torque values for gas pipes are as follows.
7.3. Chimney Connection Absorption and exhaust parts should by no means covered. In areas with heavy snow fall, the front part of this door and absorption grid should always be cleared. ① Gas connection inlet ② Chimney ③ bsorption grid of combustion air ④...
7.4. Operation Limits Operation gas pressures of natural gas for gas firing unit is 20mbar. Maximum compressive strength of the device’s gas pass is 60mbar and in case this value is exceeded the device’s gas pass equipment will be broken and the device will become out-of-order. And on the air side, the standard product works until -15°C without any problem.
Page 43
DESCRIPTION REASON SOLUTION Failure to ignite flame after 4 attempts performed by the equipment. Ill-timed flame • Phase and neutral reversed. • Grounding wire not connected. • Phase-phase connection without neutral. • Start-up electrode failed or badly positioned Manual reset •...
8. ADDITIONAL HOT WATER COIL OPTION 8.1. Introduction Heating heat exchangers with warm water are equipments that could be used optionally in all series of URTP devices. While completely mounting the device, there are 3-way valve and servo motor in standard on the unit delivered.
Page 45
Equipments for inner device; ① Hot Water Coil ③ Three-Way Valve By Pass Valve ② Three-Way Valve Motor ④ Three-Way Valve Equipments for outer device; ⑤ Air Discharge Purge ⑫ Discharge Tap ⑥ Connection Union ⑬ Inlet Line Temperature Thermometer ⑦...
① Warm water outlet ② Warm water inlet ØD: For all modules 1 ¼” 8.3. Operation Limits Please check the capacity table for the unit’s capacity values. Operation value on the water side for additional hot water coil is limited to 90/70 water regime. Hot water coil isn’t used for hot water or steam regimes over this.
Water level at the facility and in hot water coil should be checked, if the first water intake has occurred, dirt catcher should absolutely be checked and air should be taken out of the system. After water intake, the hot water coil should absolutely be checked against water leakages by opening the service door.
Power distribution in electric heaters is composed of two asymmetrical stages. The system activates primarily the 1. Stage according to the requirements. By the requirement increases, the 1. Stage is shut down and the 2. Stage is activated. In case the requirement exceeds the capacity of the 2. Stage, the desired capacity is acquired by activating both stages (1+2).
10.1. Pre-Controls 10.1.1. Control of Power Supply Connection It should be made sure that 3 phases are provided with neutral and grounding connections correctly. It should be checked whether the electric supply connection is at ±%5 tension tolerance. ...
① Metal sheet of low fan ⑤ Fresh air absorption damper and service motor ② Blow fan ⑥ Condensation pan and drain pipe ③ Inner coil ⑦Exhaust air absorption damper and service motor ④ Filter cradles 10.1.4. Control of Heat and Humidity Sensors ...
10.1.6. Control of Electric Equipment Before starting to work on commissioning, power circuits of the device should be checked and compliance of voltage levels should be confirmed. Later on, it should be ensured that all studs on the terminal are fixed. The same control should be performed on other equipments working linked to the terminal.
charge, it may suffice to observe through the sight glass on the liquid line whether bubbles come into being in the gas. If the gas charge is not sufficient, then bubbles will come into being in the gas (it should never be ignored that the state of gas overcharge cannot be perceived this way.).
10.2. Procedure of Start Up and Operation The operation to take the device into the circuit for the first time should always be carried out by Untes technical The operations carried out by unauthorized people will cause the device to remain out of the personnel.
11. ACCESSORIES AND OTHER OPTIONS The accessories and options usable with URTP devices are as follows: 11.1. CO2 Detector Constantly checking the system exhaling air, it activates the fresh air damper to the extent that the system allows (and if the pre-determined temperature settings are in the range) in the point that the air quality gets lower. It thereby provides more fresh air to the environment.
12. CONTROL PANEL 12.1. Installing and Using the Auto control Unit It should be applied at a 1.5-meter height of a flat wall where the device can get the temperature of the environment addressed properly, is not directly affected by the sunlight other heating/cooling sources and in the following ways.
Page 57
R1: POL Room Unit / N1: POL Controller / Medium Cable (~): Double-Helix Cable...
Page 58
The room control unit have 8 keys on it. These keys are demonstrated below by numbering. You may see the table explaining functions of buttons below. Button Image Function Number It is used to switch on and off the device and activate or deactivate time program. It displays available alarms when pressed for 5 second on the main screen.
Page 59
Figure A Figure B Figure A and Figure B demonstrate the images of the home screen of the room control unit of the "URTP" device. Figure A :Comfort mode, Cooling Mode Room Temperature 23 C, Time: 05:30, Exhaling fan operating, Day:Mon Figure B :Eco Mode, Heating mode, Room temperature 23 C, Time : 05:30, Exhaling fan operating, Day:Mon You may see explanations for images on the room control unit screen at the table below.
12.2. Adjusting of Set Values of the Unit From the room control unit of the "URTP" device, two separate set adjustments can be possible as Comfort and Eco Modes. These set points are presented below. Comfort Heating Room Temperature Set Value Comfort Cooling Room Temperature Set Value ...
Page 61
Alarm List for Room Control Unit Alarm Code Alarm Description Std. / Opt. External air temperature Sensor Error Opt. Blow Fan Error Std. Filter Contaminated Warning Opt. Blow Air Temperature Sensor Error Std. Room Air Temperature Sensor Error Opt. Room Humidity Sensor Error Opt.
Page 62
Exhaling Fan Failure: Check the feed fuse and frequency invertor of the exhaling fan motor. Resetting the alarm from the room control unit may not suffice; reset from the frequency inverter may be required as well. Filter Contaminated Warning: Check the different pressure key and the status of dirt in the filters. Exhaling Air Temperature Sensor Failure: Check the temperature value taken from the sensor.
Page 63
only from the room control unit will not suffice as the high pressure alarm requires manual reset from the high pressure Switch. Circuit 2 Low Pressure Alarm: Check the gas pressures of the system and the electrical cable connections of the low pressure Switch. Circuit 2 Compressor Thermal Alarm: Check the operative currents of the compressor and the motor protection switch.
12.5. Logging in PLC User’s Password Two separate methods could be applied for logging in password. The first method displays the password log in page when pressed on INFO button on the “Main Screen”. ÜNTES ROOFTOP Enter password Main Menu >...
Actual Device Mode Deactivated Stage1 Active Operation Mode Deactivated Stage2 Active Operation Mode Deactivated Click on “Enter Password” segment on the “Main Menu”. Main menu Enter password Enter password > Unit > Log in * * * * System Items >...
Page 66
Actual Device Mode Deactivated Stage1 Active Operation Mode Deactivated Stage2 Active Operation Mode Deactivated Service Mode Deactivated> Enter “Unit” segment when on the “Main Menu”. Main menu Unit Enter password > Inlet/ Outlet > Unit > Operation Modes > System Items >...
You may change the unit’s operation mode on “Manual Operation” segment on “Operation Modes”. Within this segment, “Auto. – Comfort – Economy – Protection” modes could be selected. On “Auto.”, mode selections made on the room control unit have special features. However, if any of “Comfort- Economy-Protection”...
Page 68
Enter the “Unit” segment when on the “Main Menu”. Main menu Unit Enter password > Inlet/ Outlet > Unit > Operation Modes > System Items > Time Program > Overview to Communication > Setting Points > Manufacturer’s Information > Operation Time >...
Page 69
Instant. Heating Temp. Setting 16 oC> 0 oC Eco. Heat. Temp. Setting Point Point Instant. Cooling Temp. Setting 8 oC> 0 oC Room Freeze Setting Point Point Instant. Temp. Setting Point 50 oC Blow Temperature Upper Limit Correction To set the time program; ...
Thursday Protection> Time 3 00:00 Friday Protection> Value 3 Protection Saturday Protection> Time 4 Pazar Protection> Value 4 Protection Exception Protection> Time 5 Value 5 Protection Time 6 Value 6 Protection 12.8. Reading of Temperature, Pressure and Instantaneous Values You may read the External air temperature, blow air temperature and room temperature values on the “Main Screen”.
Page 71
Main menu Unit Enter password > Inlet/ Outlet > Unit > Operation Modes > System Items > Time Program > Overview to Communication > Setting Points > Manufacturer’s Information > Operation Time > Alarm List > Enter “Inlet/ Outlet” segment on the “Unit”. Unit Inlet/ Outlet Inlet/ Outlet...
Stage 1 Absorption Temperature 10 oC Stage 2 Stage 2 Absorption Pressure 5 Bar Stage 2 Absorption Temperature 10 oC 12.9. Language Selection You need to enter user password to change the screen (HMI) language. After entering user password, to do the Language Selection;...
Unit > Language Selection > System Items > Application Data > Overview to Communication > Save/ Load Manufacturer’s Information > Password Management > Target Day Light Saving > Diagnosis Enter “Language Selection” segment, when on “System Items”. You may select language on HMI language section.
If there is an alarm sign on the right side of the screen, this shows that the unit has alarm system. To get information on the alarm content and reset it; Press once on the Alarm button. Enter “Alarm List” segment on the opened page. Alarming Alarm List Alarm List...
Page 75
Check the inverter user panel and if there is any error, refer to inverter instruction manual. Check cable connections. Check the power motor. (mechanic and electric connections) Check the network voltage. Room Sensor Error Check sensor cable connections. ...
All the maintenance works should be carried out by technicians trained about Üntes products and considering the Üntes quality and safety standards. Please contact the directorate of technical service. Realize all the service activities and tests throughout the working life of the unit in compliance with the national laws in effect.
WARNING: In the event that any of the parts are replaced, refer to the relevant section of the instruction manual and fulfill the requirements prior to operating the device again. 13.5. After Two Weeks of Study The following checks should be carried out following the two-week operation without any problems: ...
13.6.1. Equipments to Be Used During Cleaning The professionals working for the cleaning should be wearing the following costumes. This is required both for the protection of the workers and the device to be cleaned. A clean coverall Protective goggles ...
These parts should be washed and disinfected by using the methods to be presented later on. The cleaning operation should be carried out at least once a month. This cleaning should be repeated for the places known for bacteria to have a potential to reproduce them. Cleaning of Outer Surfaces of Devices;...
Unless otherwise stated by responsible technicians, this operation should be carried out at least once every six months regardless of the device being used or not. In this case, the cleaning and disinfection operation should be materialized independent from periodical cleaning. The following procedure should be followed for cleaning and disinfection.
direct connection to a surgery room, cleaning should be carried out only if dust and dirt exist on the outer surfaces. The outer case should be cleaned in the following manner. Stop the device and take the main switch and the service switch to the off position to cut the electricity. ...
Page 83
remains at the Switch, Blocked filter dryer, Indoor/Outdoor them if necessary, Check the filter and saturated force fan does not operate, replace it if necessary, Check the fan temperature motors, The device makes an Noisy compressor, Check it and replace it if necessary, unusual sound Badly mounted panels Compressor oil...
Page 84
Phone: +90 (312) 287 91 00 (pbx) - Fax: +90 (312) 284 91 00 Package Air Conditioners Production Factory Istanbul Yolu 37. Km Kazan – ANKARA Phone: +90 (312) 818 63 00 (pbx) - Fax : +90 (312) 818 61 50 Email: export@untes.com.tr Web: www.untes.com.tr TSB-KK-008 rev.00...