 TP04P-21EX1R
Analog Input
Current input
-20mA~+20mA
Shiel ded
cable *1
Shield ed cable*4
Pt100
2-wire
*1: The cables connected to the analog input terminals should be kept separate from other
power cables and cables which generate noise.
*2: If the text panel is connected to a current signal, the terminals V3+ and I3+ must be
short-circuited.
*3: If the ripple in the input voltage results in the noise interference with the wiring, please
connect the text panel to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF
with a working voltage of 25 V.
*4: Please connect the ground terminal on a power supply module and the analog input terminal
FE to the system ground, and then ground the system ground or connect the system ground
to a distribution box.
 RS-485 Wiring
1
Master station
Note: 1. The terminal resistor should be connected to the master station and the last slave
station. The resistance of the terminal resistor should be 120.
2. To ensure communication quality, it is suggested that users should use double shielded
twisted pair cables (20AWG) for wiring.
 Communication Connection
TP04P may connect to a PC by using USB adaptor cable.
Please use an AM/BM USB adaptor cable.
 Battery's Life
Temperature (°C)
Life (Year)
 Precision of the Real Time Clock
(Second/Month)
Temperature (°C/°F)
Maximum error (Second)
CH0
Figu r e 1 7
D+ D-
2
D+ D-
3
-20
2.0
0/32
-117
Analog Output
I0+
I0-
FE
AC moto r drive, re co rde r,
propo rti oni ng va lve...
Pt100
Pt100
L3+
L3-
I3 -
FE
3-wire
D+ D-
3
Slave station
0
2.5
- 8 -
Cu rrent ou tput
0mA~20mA
Shiel ded
cabl e*1
Shie lded cable*4
2
Figure 20
Terminal resistor
20
2.7
25/77
52
CH2
I2
AG
FE
Figu r e 1 8
L4+
L4-
I4 -
FE
Figu re 1 9
Figure 21
60
2.8
55/131
-132

Advertisement