*1: There is no internal protection circuit in the output relay of the PLC; therefore when activating
an inductive load, we suggest you parallel connect a reverse current protection diode to extend
the life of the contact.
- The diode has to be able to endure max. 5 ~ 10 times of load voltage.
- The positive current of the diode has to be bigger than load current.
*2: Manual exclusive output uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.
*3: There is no internal protection circuit in the output relay of the PLC; therefore when activating
an inductive load, we suggest you parallel connect a surge absorber (0.1uF + "100ohm to
120ohm") to reduce the noise on AC load and extend the life of the contact.
 Wiring Transistor Output Terminals (Sink)
C0
5
7
3
2
3
*1: Manual exclusive output uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.
*2: Use a Zener diode (39V) in the PLC to protect the transistor output. When activating
inductive load, we suggest you parallel connect a reverse current protection diode.
 Wiring Analog I/O and Temperature Sensor
 TP04P-22XA1R
Analog Input
Voltage in put
-10V~+10V
Shiel ded
cable *1
Current in put
-20mA~+20mA
Shiel ded
cable *1
Y0
C1
Y1
C2
Y2
Y3
MC2
2
8
7
MC 1
MC 2
5
4
1 0
Y2
Y0
C1
Y1
C2
Y3
MC2
6
8
MC1
MC2
4
CH0
V0 +
*3
I0
V0-
FE
CH3
V3 +
*2
I3
V3-
FE
Figu r e 1 5
Y4
Y 5
1
MC 1
7
6
1 1
[ F igu re 1 3 ]
Y4
Y5
1
MC1
6
9
[ Figure 14 ]
Analog Output
*3
AC motor dr ive, reco rder,
p ropor tioning va l v e ...
AC motor d rive, re corder ,
propo rtionin g v a lve...
- 7 -
DO NOT wire empty
terminal
Fuse
Reverse current
protection diode*1
Manual exclusive
output*2
Emergency stop: by
external switch
Surge absorber*3
Inductive load
Indicator: incandescent
light
DC power supply
AC power supply
Resistive load
11
DO NOT wire empty
terminal
Emergency stop
Fuse
Manual exclusive output*1
DC power supply
Indicator: incandescent light
Reverse current protection
diode*2
Inductive load
Resistive load
Voltag e output
-1 0V~ +10V
Sh ielded
cable* 1
Cur rent o utput
0mA~20 mA
Shielded
cab le*1
CH4
V4
I4
AG
FE
CH5
V5
I5
AG
FE
F ig ur e 1 6