Page 2
Version Date Modification V1.0.0 July 15,2015 First Draft V1.0.1 July 16,2015 Update HMI Model Information (43 & C series) V1.0.2 July 16,2015 Update Hitachi and Schneider V1.0.3 July 17,2015 Add Siemens S7-1200 and fix maximum value of bitsInBytedeivce V1.0.4 July 20,2015 Fix P5043 series Both Male Diagram V1.0.5...
PIN# COM3 COM3 COM4 (RS-422) (RS-485) DATA+ DATA- ISO_GND ISO_GND ISO_GND DATA+ DATA- 2. PLC Connection 2.1 FATEK Automation Corp. FBs/B1/B1z/HB1 2.1.1.1 Communication Setting Item Default Setting Remark Signal Level RS232 Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No.
Page 7
Communication Method FATEK Communication Protocol 2.1.1.2 Memory Resource Review Device Data Bits Address Min. Max. Description Format DDDD Input Discrete DDDD Output Relay DDDD 2001 Internal Relay DDDD Step Relay DDDD Timer Discrete DDDD Counter Discrete DDDD Input Discrete...
Page 8
Under the PLC tab, select the Setting option and choose Port 0. Here, the Baud rate and other parameters of the serial port can be configured. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 9
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select FATEK Automation Corp Under Product Series select FATEK FBs/B1/B1z/HB1 Under Port select COM1 Verify the other parameters are consistent with the settings on the PLC.
Page 10
PLC RS232 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 3 TX 3 TX 4 RX 5 GND 2 GND Wiring Diagrams:All P5Series...
RS232 / RS485 Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Must match PLC port setting Communication Method FATEK Communication Protocol 2.1.2.2 Memory Resource Review Device Data Bits Address Min. Max. Description Format DDDD Input Discrete...
Page 12
DDDD Output Relay DDDD 2001 Input Relay DDDD Step Relay DDDD Timer Register DDDD Counter Register DDDD Counter Register DDDD 8071 Data Register DDDD 4095 Data Register 2.1.2.3 Connecting to PLC Configuring the PLC Use the application WinProLadder (ver. 3.25) to configure the serial port of the PLC. Connect the PLC to a computer.
Page 13
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner:...
Page 14
Under Interface Type select Serial Under Manufacturer select FATEK Automation Corp. Under Product Series select FATEK FBe Under Port select the port corresponding to the connection to the PLC Verify the other parameters are consistent with the settings on the PLC 2.1.2.4 Wiring Diagrams...
Wiring Diagrams:P5043S/P5043N/P5070VS/P5102VS FBs/B1/B1z/HB1 (TCP) 2.1.3.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 192.168.1.3 Port PLC Station No. Communication Method 2.1.3.2 Memory Resource Review Device Data Bits Address Min. Max. Description Format DDDD Input Discrete DDDD Output Relay DDDD 2001 Internal Relay...
Page 18
2.1.3.3 Connecting to HMI Configuring IP Address on PLC Use the application FATEK Ethernet Module Configuration Tool to configure the IP address of the PLC. Connect an Ethernet cable to the PLC. Under Attached Media, select LAN and press scan.
Page 19
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select FATEK Automation Corp Under Product Series select FATEK FBs/B1/B1z/HB1 (TCP)
2.1.4.3 Connecting to HMI Configuring IP Address on PLC Use the application FATEK Ethernet Module Configuration Tool to configure the IP address of the PLC. Connect an Ethernet cable to the PLC. Under Attached Media, select LAN and press scan.
Page 21
Select the PLC to connect to and right click or press Properties to change the IP. Note: The default IP address for the PLC has 1 for its third octet. If the IP address of the computer has a different number at that position, the PLC will not show up in the scan. Configure network settings on the computer to be able to see the PLC in the local network.
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select FATEK Automation Corp Under Product Series select FATEK FBe (TCP) Use the IP address assigned on the PLC Leave the Port at the default value FBs/B1/B1z/HB1 (UDP) 2.1.5.1 Communication Setting...
Page 23
2.1.5.3 Connecting to HMI Configuring IP Address on PLC Use the application FATEK Ethernet Module Configuration Tool to configure the IP address of the PLC. Connect an Ethernet cable to the PLC. Under Attached Media, select LAN and press scan.
Page 24
configured. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select FATEK Automation Corp Under Product Series select FATEK FBe (UDP) Use the IP address assigned on the PLC Leave the Port at the default value...
FX2N CPU 2.2.1.1 Communication Setting Item Default Setting Remark Signal Level RS485 4W Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method Programming Protocol 2.2.1.2 Memory Resource Review Device Description Data bit Min. Max. Input Discrete Output Relay Internal Relay 7999...
Page 27
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select Mitsubishi FX2N Under Port select COM3 2.2.1.4 Wiring Diagrams PLC RS422 Pinout *View from soldering point of the cable PIN# Signal...
Page 30
Signal Level RS485 Baud Rate 19200 Data Length Stop Bit Parity Even PLC Station No. TX Control Form1 Without CR,LF Checksum Communication Method Computer Link 2.2.2.2 Memory Resource Review Device Description Data bit Min. Max. Input Discrete Output Relay Internal Relay 3071 Special Relay 8000...
Page 31
Select Serial USB in the Transfer Setup Communication window. Select the RS-232C radio button and select the COM Port that the PLC is connected at. Click Connection Test to verify the connection and then press OK.
Page 32
After confirming the Parameter option is checked, press Execute in the Online Data Operation window. Under the Project Sidebar, expand Parameter and select PLC Parameter.
Page 33
Navigate to the PLC System(2) tab and configure it to the settings detailed below. Check Operate Communication Setting to enable configuration Set Protocol to Dedicated Protocol Set Parity to Even...
Page 34
Set Transmission Speed to 19200 Set H/W Type to RS-485 Check the Sum Check checkbox Verify the Station Number is consistent with the one set in FvDesigner. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation...
FX3U CPU 2.2.3.1 Communication Setting Item Default Setting Remark Signal Level RS485 4W Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method Programming Protocol 2.2.3.2 Memory Resource Review Device Description Data bit Min. Max. Input Discrete Output Relay Internal Relay 7999...
Page 38
Counter Discrete Input Discrete Output Relay Internal Relay 7664 Step Relay 4080 Timer Memory Counter Memory Data Register 7999 Special Data Register 8000 8511 Extended Register 32767 Counter Memory 2.2.3.3 Connecting to HMI Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select Mitsubishi FX3U/3G...
Page 39
2.2.3.4 Wiring Diagrams PLC RS422 Pinout *View from soldering point of the cable PIN# Signal HMI COM3 Pinout *Looking into HMI Device PIN# COM3 (RS-422/RS-485) ISO_GND P5070S/P5070N/P5070N1/P5102N/P5102N1...
FX3U-485BD 2.2.4.1 Communication Setting Item Default Setting Remark Signal Level RS485 Baud Rate 19200 Data Length Stop Bit Parity Even PLC Station No. TX Control Form1 Without CR,LF Checksum Communication Method Computer Link 2.2.4.2 Memory Resource Review Device Description Data bit Min.
Page 42
Internal Relay 7664 Step Relay 4080 Timer Memory Counter Memory Data Register 7999 Special Data Register 8000 8511 Extended Register 32767 Counter Memory 2.2.4.3 Connecting to HMI Configuring the PLC Use MELSOFT GX Works2 to configure the port of the PLC. Under the Online menu option, select Read from PLC Select the FXCPU PLC series.
Page 43
Select the RS-232C radio button and select the COM Port that the PLC is connected at. Click Connection Test to verify the connection and then press OK. After confirming the Parameter option is checked, press Execute in the Online Data Operation window.
Page 44
Under the Project Sidebar, expand Parameter and select PLC Parameter. Navigate to the PLC System(2) tab and configure it to the settings detailed below.
Page 45
Check Operate Communication Setting to enable configuration Set Protocol to Dedicated Protocol Set Parity to Even Set Transmission Speed to 19200 Set H/W Type to RS-485 Check the Sum Check checkbox Verify the Station Number is consistent with the one set in FvDesigner. Note: For more detailed information please refer to the PLC manual.
Page 46
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select Mitsubishi FX3U/3G-485BD. Under Port select COM3 2.2.4.4 Wiring Diagrams PLC RS422 Pinout HMI COM3 Pinout...
P5043S/P5043N/P5070VS/P5102VS HMI COM2 PLC RS422 Port 9 RX- 4 RX+ 6 TX- 1 TX+ 5 GND Wiring Diagrams:P5043S/P5043N/P5070VS/P5102VS FX3U Ethernet 2.2.5.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 Port 5001 PLC Station No. Communication Method MC protocol Binary/ASCII 2.2.5.2 Memory Resource Review...
Page 49
Device Description Data bit Min. Max. Input Discrete Output Relay Internal Relay 7679 Special Relay 8000 8511 Step Relay 4095 Timer Discrete Counter Discrete Input Discrete Output Relay Internal Relay 7664 Step Relay 4080 Timer Memory Counter Memory Data Register 7999 Special Data Register 8000...
Page 50
Select the RS-232C radio button and select the COM Port that the PLC is connected at. Click Connection Test to verify the connection and then press OK. After confirming the Parameter option is checked, press Execute in the Online Data Operation window.
Page 51
Under the Project Sidebar, expand Parameter and select PLC Parameter. In the Ethernet Port tab, set an open IP address.
Page 52
Click Open Setting and set the entire Open System column to MC Protocol. For the Host Station Port No., set row 1 to 5001, row 2 to 5002 and so on. Under the Online menu option, select Write to PLC to save the settings to the PLC. Press Execute in the Online Data Operation window.
Page 53
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select one of the Mitsubishi FX3U-ENET-ADP options. The last part of the series name (BINARY or ASCII) should be consistent with the Connection Data Code set in the Ethernet Port for the PLC.
Page 55
TX Control Form1 Without CR,LF Checksum Communication Method MC Protocol 3C 2.2.6.2 Memory Resource Review Device Description Data Input Min. Max. Format Input Relay OOOO 1777 Output Relay OOOO 1777 Internal Relay DDDDD 32767 Link Relay HHHH 7FFF Annunciator DDDDD 32767 Link Special Relay HHHH...
Page 56
SC_Word Retentive Timer DDDD 1008 Coil CS_Word Counter Contact DDDD 1008 CC_Word Counter Coil DDDD 1008 SM_Word Special Relay DDDD 9984 Timer Current DDDD 1023 Value Retentive Timer DDDD 1023 Current Value Counter Current DDDD 1023 Value Data Register DDDD 7999 Link Register HHHH...
Page 57
In the connection window, select Ethernet Board. Click PLC Module and in the dialog window, select the Ethernet Port Direct Connection radio button.
Page 58
Click Connection Test to verify the connection and then press OK. Click Select All in the Online Data Operation window and press Execute. Allow the read to finish.
Page 59
In the Project sidebar, expand Parameter, FX5UCPU, and Module Parameter and select 485 Serial Port. Under Basic Settings, change Communication Protocol Type to MC Protocol. Under Fixed Setting, change Message Pattern to Pattern 1 and verify the station number is consistent with the one set in FvDesigner.
Page 60
Under the Online menu option, select Write to PLC to save the settings to the PLC. Click Select All and press Execute in the Online Data Operation window. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation...
FX5U Ethernet 2.2.7.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 Port 1025 PLC Station No. Communication Method MC protocol 3E Binary/ASCII 2.2.7.2 Memory Resource Review Device Description Data Input Min. Max. Format Input Relay OOOO 1777 Output Relay OOOO...
Page 65
Under the Online menu option, select Read from PLC. Select the FX5CPU option for the Series. In the connection window, select Ethernet Board. Click PLC Module and in the dialog window, select the Ethernet Port Direct Connection radio button.
Page 66
Click Connection Test to verify the connection and then press OK. Click Select All in the Online Data Operation window and press Execute. Allow the read to finish.
Page 67
In the Project sidebar, expand Parameter, FX5UCPU, and Module Parameter and select Ethernet Port. The IP Address of the PLC can be obtained here. Switch the Communication Data Code to the mode needed (Binary or ASCII). Double click “<Detailed Setting>” under External Device Configuration to get the port information.
Page 68
If the user needs to change the IP Address, edit the IP address under the Own Node Settings. Then enter the Detailed Settings and press Close with Reflecting the Setting. Under the Online menu option, select Write to PLC to save the settings to the PLC. Click Select All and press Execute in the Online Data Operation window.
Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select one of the Mitsubishi FX5U-ENET options. The last part of the series name (BINARY or ASCII) should be consistent with the Connection Data Code set in the Ethernet Port for the PLC.
Page 70
TX Control Procedure Form4 Without CR,LF Sum Check Communication Method MC Protocol 3C 2.2.8.2 Memory Resource Review Device Description Data bit Input Max. Max. fromat Input Relay HHHH 1fff Output Relay HHHH 1fff Internal Relay DDDDD 61439 Latch Relay DDDD 32767 Link Relay HHHH...
Page 71
TC_Word Timer Coil DDDD 32752 SS_Word Retentive Timer DDDD 32752 Contact SC_Word Retentive Timer Coil DDDD 32752 CS_Word Counter Contact DDDD 32752 CC_Word Counter Coil DDDD 32752 SM_Word Special Relay DDDD 2032 Timer Current Value DDDD 32752 Retentive Timer DDDD 32752 Current Value Counter Current...
Page 72
Configure it to the settings detailed below. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 73
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select Mitsubishi QSeries-Serial Communication(Link Port). Verify the parameters match the window above. 2.2.8.4 Wiring Diagrams QJ71C24N RS232 Pinout * Looking into PLC Device PIN# Signal...
Page 74
QJ71C24N RS422/485 Pinout HMI COM1 pinout *Looking into COM1 Port PIN# COM1 (RS232) HMI COM3 pinout...
3 GND Wiring Diagrams:RS485 QSeries-Serial Communication(CPU Port) 2.2.9.1 Communication Setting Item Default Setting Remark Signal Level RS232 Baud Rate 19200 Data Length Stop Bit Parity PLC Station No. 2.2.9.2 Memory Resource Review Device Description Data bit Input Min. Max. format Input Relay HHHH 1fff...
Page 79
Index Register File Register HHHHH 9ffff 2.2.9.3 Connecting to HMI Configuring IP Address on PLC Use MELSOFT GX Works2 to configure the port of the PLC. In the Project sidebar, expand Parameter and expand PLC Parameter. Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Page 80
Within the Link configuration window in FvDesigner: Under Interface Type select Direct Link(Serial) Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select one of the Mitsubishi QSeries-Series Communication(CPU Port). Verify the parameters match the window above. 2.2.9.4 Wiring Diagrams PLC RS232 Pinout *View from soldering point of the cable...
Page 81
HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232) All P5 Series HMI COM1 PLC RS232 Port 2 RX 1 TXD 3 TX 2 RXD 5 GND 4 GND 5 RTS circuit 6 CTS Wiring Diagrams:All P5Series...
Q/L Series-ENET 2.2.10.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 Port 4999 PLC Station No. Communication Method MC protocol 3E Binary/ASCII 2.2.10.2 Memory Resource Review Device Description Data Input Min. Max. Format Input Relay HHHH 1fff Output Relay HHHH...
Page 84
Value Data Register DDDDD 39935 Link Register HHHH 9bff Link special 7FFF Register Special Register DDDD 2047 File Register DDDDD 32767 Index Register File Register HHHHH 9fff Address increased by 0, 20, 40, 60… 2.2.10.3 Connecting to HMI Configuring IP Address on PLC Use MELSOFT GX Works2 to configure the port of the PLC.
Page 85
Click Open Setting and set the entire Open System column to MC Protocol. For the Host Station Port No 4999. Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Mitsubishi Electric Corporation Under Product Series select one of the Mitsubishi Q/L Series-ENET(BINARY 或 ASCII). The last part of the series name (BINARY or ASCII) should be consistent with the Connection Data Code set in the Ethernet Port for the PLC.
Page 87
Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method FINS 2.3.1.2 Memory Resource Review Device Description Data bit Min. Max. Timer Area 4095 Counter Area 4095 CIO Area 6143 Work Area Holding Bit Area Auxiliary Bit Area Timer Area 4095 Counter Area...
Page 88
Navigate to 序列埠 1 tab and configure it to the settings detailed below. After click 傳輸到 PLC to write in PLC. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 89
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Omron Corporation Under Product Series select Sysmac CP Series (FINS) Under Port select COM1 2.3.1.4 Wiring Diagrams PLC RS232 Pinout *Looking into male RS232 Cable PIN# Signal...
Page 90
HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232) All P5 Series HMI COM1 PLC RS232 Port 2 RX 2 TX 3 TX 3 RX 5 GND 9 GND Wiring Diagrams:All P5Series...
Omron SYSMAC CP Series Ethernet 2.3.2.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 To be configured Port 9600 PLC Station No. Communication Method FINS/TCP 2.3.2.2 Memory Resource Review Device Description Data bit Min. Max. Task Flag Timer Area 4095 Counter Area...
Page 92
2.3.2.3 Connecting to HMI Configuring IP Address on PLC Use CX-Programmer to configure the IP of the PLC. 專案 設定 In the Task sidebar, expand Navigate to 內置乙太網路 tab, the IP address and other parameters can be set. After click 傳輸到 PLC to write in PLC.
Page 93
Note: For more detailed information please refer to the PLC manual. 設定...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Omron Corporation Under Product Series select Sysmac CP Series (FINS/TCP) Enter the IP Address that was written into the PLC Enter 9600 for the Port Omron SYSMAC CS/CJ Series 2.3.3.1 Communication Setting Item...
Page 95
EM Bank 5 32767 EM Bank 6 32767 EM Bank 7 32767 EM Bank 8 32767 EM Bank 9 32767 EM Bank 10 32767 EM Bank 11 32767 EM Bank 12 32767 Current EM Bank 32767 Data Register Index Register 2.3.3.3 Connecting to HMI Configuring the PLC Use CX-Programmer to configure the port of the PLC.
Page 96
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Omron Corporation Under Product Series select Sysmac CS/CJ Series (FINS) Under Port select COM3 2.3.3.4 PLC Message When the first 4 error codes are 200A, it means that the last 4 error codes are created by PLC.
Omron SYSMAC CS/CJ Series Ethernet 2.3.4.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 To be configured Port 9600 PLC Station No. Communication Method FINS/TCP 2.3.4.2 Memory Resource Review Device Description Data bit Min. Max. Task Flag Timer Area 4095 Counter Area...
Page 100
Index Register 2.3.4.3 Connecting to HMI Configuring the PLC Use CX-Programmer to configure the IP of the PLC. In the 專案 Task 工具區 sidebar, expand IO 表及模組設定. Expand 內建埠/嵌入板, and expand EtherNet/IP Port...
Page 101
IP address and other parameters can be set. Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Page 102
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Omron Corporation Under Product Series select Sysmac CS/CJ Series (FINS/TCP) Enter the IP Address that was written into the PLC Enter 9600 for the Port...
Omron SYSMAC CPM Series 2.3.5.1 Communication Setting Item Default Setting Remark Signal Level RS232 Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method HOSTLINK 2.3.5.2 Memory Resource Review Device Description Data bit Min. Max. Timer Area Counter Area IR area HR area...
Page 104
Navigate to 序列埠 1 tab and configure it to the settings detailed below. After click 傳輸到 PLC to write in PLC.
Page 105
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Omron Corporation Under Product Series select Sysmac CPM Series (HOSTLINK) Under Port select COM1 2.3.5.4 Wiring Diagrams...
Page 106
Omron PLC Pinout *Looking into Omron PLC Cable PIN# Signal HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232) All P5 Series...
HMI COM1 Omron PLC Port 2 RX 8 TX 3 TX 4 RX 5 GND 7 GND Wiring Diagrams:All P5Series 2.4 Siemens Siemens S7-200 SMART 2.4.1.1 Communication Setting Item Default Setting Remark Signal Level RS485 2W Baud Rate 9600 Data Length Stop Bit Parity Even...
Page 108
Output Bit Memory Variable Memory 20479 Counter Timer Sequential Control Relays Special Memory Bit 1535 Input Output Timer Counter Word Memory V Memory 20479 Special Memory 1535 Analog Input Analog Output 2.4.1.3 Connecting to HMI Configuring the PLC Use Step7 microWIN smart to configure the port of the PLC. Under the Project Sidebar, expand CPU model and configure it to the settings detailed below.
Page 109
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner:...
Page 110
Under Interface Type select Serial Under Manufacturer select Siemens Corporation Under Product Series select S7-200 SMART PPI Under Port select the port number that corresponds to the RS485 connection on the HMI. 2.4.1.4 Wiring Diagrams PLC RS485 Port *Looking into male RS485 Cable PIN# Signal DATA+...
Siemens S7-200 SMART Ethernet 2.4.2.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 To be configured Port PLC Station No. Communication Method ISO TCP 2.4.2.2 Memory Resource Review Device Description Data bit Min. Max. Input 31.7 Output 31.7 Bit Memory...
Page 114
Counter Word Memory V Memory 20479 Special Memory 1535 Analog Input Analog Output 2.4.2.3 Connecting to HMI Configuring IP Address on PLC Use the application STEP 7-MicroWIN SMART to configure the IP address of the PLC. Under the Project, press the Communications option to connect to the PLC over the local network.
Page 115
Under Network interface, select one of the options to scan the local network. The IP address of the PLC will show up. The MAC address can be verified with the one on the PLC. Navigate to the PLC tab and select to upload the PLC program onto the computer. On the sidebar, right click CPU CR40 and select the first option.
Page 116
In the dialog window, the IP address can be changed. Press OK to confirm the setting.
Page 117
In the PLC tab, select to download the settings onto the PLC. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Siemens Corporation Under Product Series select S7-200 SMART ISO TCP Enter the IP Address that was written into the PLC.
Siemens S7-1200 Ethernet 2.4.3.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 To be configured Port PLC Station No. Communication Method ISO TCP 2.4.3.2 Memory Resource Review Device Description Data bit Min. Max. Input 1022.7 Output 1022.7 Bit Memory 1022.7...
Page 119
2.4.3.3 Support Data block type Data block type Size Bool Byte 8-bit SInt 8-bit USInt 8-bit Word 16-bit 16-bit UInt 16-bit DWord 32-bit DInt 32-bit UDInt 32-bit Real 32-bit String Length = 254 byte Please make sure that proper setting is in TIA: [DB Properties]→[Attributes]→[ Optimized block access] is unchecked [PLC program Properties]→[Protection]→[Permit access with PUT/GET communication from remote partner (PLC,HMI,OPC,…] is checked.
Page 120
Under the device in the project tree, select Device configuration and click the Ethernet port on the device image. Under the Ethernet addresses menu option, the IP address can be configured.
Page 121
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Siemens Corporation Under Product Series select S7-1200 Enter the IP Address that was written into the PLC. Enter the Port number that was set on the PLC.
Siemens S7-200 2.4.4.1 Communication Setting Item Default Setting Remark Signal Level RS485 2W Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method PPI 2.4.4.2 Memory Resource Review Device Description Data Bit Min. Max. Input Output Bit Memory Variable Memory 10239...
Page 123
Counter Timer Sequential Control Relays Special Memory Bit Input Output Timer Counter Word Memory V Memory 10238 Special Memory Analog Input Analog Output Input Output Word Memory V Memory 10236 Special Memory 2.4.4.3 Connecting to HMI Configuring the PLC Use Step7 MicroWIN SP9 to configure the port of the PLC. After choose the PLC type, click communication in the view field, then double click the ‘’double click to refresh’’...
Page 124
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 125
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Siemens Corporation Under Product Series select S7-200 Under Port select the port number that corresponds to the RS485 connection on the HMI. 2.4.4.4 Wiring Diagrams PLC RS485 Port...
Page 126
*Looking into male RS485 Cable PIN# Signal DATA+ DATA- HMI (ex.P5043N) COM2 Pinout *Looking into HMI PIN# COM2 (RS485) DATA+ DATA- HMI (ex.P5070N1) COM3 Pinout...
Siemens LOGO 2.4.5.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 0.0.0.0 To be configured Port PLC Station No. Communication Method ISO TCP Model 0BA8 0BA7/0BA8 Local TSAP 1000 Remote TSAP 2100 2.4.5.2 Memory Resource Review Device Description Data bit Min.
Page 130
1466 2.4.5.3 Connecting to HMI Configuring IP Address on PLC Use the application LOGO!Soft Comfort V8.1 to configure the IP address of the PLC. Under the Online menu option, select Ethernet Connections. Right chick Ethernet Connections and Add server connections. Enable Accept all connection requests, And setting TSAP for Remote Properties(Client)
Page 131
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Siemens Corporation Under Product Series select LOGO Enter the IP Address that was written into the PLC. Enter the Port number that was set on the PLC.
2.5 Hitachi EHV Series 2.5.1.1 Communication Setting Item Default Setting Remark Signal Level RS232C Baud Rate 19200 Data Length Stop Bit Parity Even PLC Station No. Communication Method h protocol 2.5.1.2 Memory Resource Review Device Description Data Input Min. Max. format Input bit DDDDD...
Page 133
HMI. 2.5.1.4 Wiring Diagrams HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232)
Page 134
PLC RS232 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 5 TxD 3 TX 6 RxD 5 GND 1 SG 8 CTS 8 RTS Wiring Diagrams:All P5Series...
EHV Series ( Ethernet ) 2.5.2.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 192.168.1.100 Port 3004 PLC Station No. Communication Method h protocol ( Ethernet ) 2.5.2.2 Memory Resource Review Device Description Data Input Min. Max. format Input bit DDDDD...
Link word Timer / Counter DDDD 2559 2.6 Schneider MODBUS RTU 2.6.1.1 Communication Setting Item Default Setting Remark Signal Level RS485 2W Baud Rate 19200 Data Length Stop Bit Parity None PLC Station No. Communication Method MODBUS RTU(Zero-based) 2.6.1.2 Memory Resource Review Device Description Data bit...
Page 137
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial...
Page 138
Under Manufacturer select Schneider Under Product Series select MODBUS RTU Enter the IP Address that was written into the PLC. 2.6.1.4 Wiring Diagrams HMI (ex.P5043N) COM2 Pinout *Looking into HMI PIN# COM2 (RS485) DATA+ DATA- HMI (ex.P5070N1) COM3 Pinout *Looking into HMI Device PIN# COM3 (RS-422/RS-485)
Page 139
DATA+ DATA- PLC RS485 Pinout *Looking into PLC PIN# Signal DATA+ DATA- P5070S/P5070N/P5070N1/P5102N/P5102N1 HMI COM3 Port PLC RS485 Port 6 DATA+ 1 DATA+ 7 DATA- 2 DATA- 5 GND 5 GND Wiring Diagrams:P5070S/P5070N/P5070N1/P5102N/P5102N1...
P5043S/P5043N/P5070VS/P5102VS HMI COM2 Port PLC RS485 Port 1 DATA+ 1 DATA+ 6 DATA- 2 DATA- 5 GND 5 GND Wiring Diagrams:P5043S/P5043N/P5070VS/P5102VS MODBUS TCP 2.6.2.1 Communication Setting Item Default Setting Remark...
Page 141
Signal Level Ethernet Internet Protocol 192.168.0.2 Port PLC Station No. Communication Method MODBUS TCP(Zero-based) 2.6.2.2 Memory Resource Review Device Description Data Input Min. Max. format Memory bit DDDDD 65535 Memory word DDDDD 65535 2.6.2.3 Connecting to HMI Configuring IP Address on PLC Use TwidoSuite to configure the IP of the PLC.
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Schneider Electric. Under Product Series select Modbus TCP. Enter the IP Address that was written into the PLC. 2.7 Allen-Bradley CompactLogix/ControlLogix/FlexLogix Tag Series 2.7.1.1 Communication Setting Item Default Setting Remark...
Page 143
DataType bits Description BOOL Boolean SINT Single integer Integer DINT Double integer REAL Float number STRING Length of string DATA Character data of string COUNTER Preset value Accumulatedvalue Count up flag Count down flag Done flag Overflowflag Underflowflag TIMER Preset value Accumulatedvalue Enable flag Timing flag...
Page 144
Driver and close out of the dialog window. Under the new Ethernet driver, the PLC connected to the local network should be visible. Right click the main module of the PLC and select Module Configuration. Navigate to the Port Configuration tab. Here, the IP address and other parameters can be set.
Page 145
Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Allen-Bradley. Under Product Series select CompactLogix/ControlLogix/FlexLogix Taq.
Enter the IP Address that was written into the PLC. To access variables in the program, tags will have to be imported. Tags are created in the program RSLogix 5000. Right click 控制器标签(controller tag) in the controller sidebar and select 导出 (Export) Tag.
Page 147
Item Default Setting Remark Signal Level Ethernet Internet Protocol 192.168.0.1 Port 44818 Communication Method EtherNet/IP 2.7.2.2 PLC Resource Review Device Description Data bit Input Min. Max. format Output File 1/16 O F:S.D O0:0.0 O0:30.255 Intput File 1/16 I F:S.D I1:0.0 I1:30.255 Status File 1/16...
Page 148
Under the new Ethernet driver, the PLC connected to the local network should be visible. If the status of the device is OK, open up RSLogix 500. In RSLogix 500, under the Comms menu option, select Who Active go Online. In the dialog window that appears, select the PLC device connected through RSLinx.
Page 149
Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Allen-Bradley Under Product Series select SLC (Ethernet/IP) Enter the IP Address that was written into the PLC. Keep the Port at the default setting. SLC Series 2.7.3.1 Communication Setting Item Default Setting...
Page 151
Communication Method 2.7.3.2 PLC Resource Review Device Description Data bit Input Min. Max. format Output File 1/16 O F:S.D O0:0.0 O0:30.255 Intput File 1/16 I F:S.D I1:0.0 I1:30.255 Status File 1/16 S F:E S2:0 S2:163 Bit File 1/16 B F:E B3:0 B255:255 Timer File...
Page 152
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 153
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Allen-Bradley Under Product Series select SLC. Verify the parameters match the window above. 2.7.3.4 Wiring Diagrams HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232)
Page 154
PLC RS232 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 7 TXD 3 TX 4 RXD 5 GND 2 GND Wiring Diagrams:All P5Series...
MicroLogix Series (EtherNet/IP) 2.7.4.1 Communication Setting Item Default Setting Remark Signal Level Ethernet Internet Protocol 192.168.0.1 Port 44818 Communication Method EtherNet/IP 2.7.4.2 PLC Resource Review Device Description Data bit Input Min. Max. format Output File 1/16 O F:S.D O0:0.0 O0:30.255 Intput File 1/16 I F:S.D...
Page 156
2.7.4.3 Connecting to HMI Configuring IP Address on PLC If the IP address needs to be configured, follow the steps below. Use the applications RSLinx Classic Lite and RSLogix 500 to configure the IP address of the PLC. First open RSLinx Classic Lite to set up a connection between the computer and PLC. An Ethernet cable needs to be connected to the PLC and the computer must be online.
Page 157
Press Create New File in the dialog window that appears after pressing OK. On the left side of the program, double click Channel Configuration to access the PLC’s Ethernet settings. Under the Channel 1 tab, the IP address can be changed.
Page 158
Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Allen-Bradley Under Product Series select Micrologix (Ethernet/IP) Enter the IP Address that was written into the PLC. Keep the Port at the default setting. MicroLogix Series 2.7.5.1 Communication Setting Item Default Setting...
Page 160
Communication Method DF1 Protocol 2.7.5.2 PLC Resource Review Device Description Data bit Input Min. Max. format Output File 1/16 O F:S.D O0:0.0 O0:30.255 Intput File 1/16 I F:S.D I1:0.0 I1:30.255 Status File 1/16 S F:E S2:0 S2:163 Bit File 1/16 B F:E B3:0 B255:255...
Page 161
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 162
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Allen-Bradley Under Product Series select Micrologix Under Port select COM1 Verify the other parameters are consistent with the ones set on the PLC. 2.7.5.4 Wiring Diagrams HMI COM1 Pinout *Looking into COM1 Port PIN#...
Page 163
PLC RS232 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 7 TXD 3 TX 4 RXD 5 GND 2 GND Wiring Diagrams:All P5Series...
2.8 Taiwan Instrument & Control Co., Ltd. FY Series 2.8.1.1 Communication Setting Item Default Setting Remark Signal Level RS485 2W Baud Rate 38400 Data Length Stop Bit Parity PLC Station No. Communication Method MODBUS RTU 2.8.1.2 Memory Resource Review Device Description Data Input...
Page 165
Program Segment Display TIMR Program Countdown Display SV_1 Set Point of Seg.1(Pattern 1) TM_1 Run Time of Seg.1(Pattern 1) OUT1 Output Limit of Seg.1(Pattern 1) SV_2 Set Point of Seg.2(Pattern 1) TM_2 Run Time of Seg.2(Pattern 1) OUT2 Output Limit of Seg.2(Pattern 1) SV_3 Set Point of...
Page 166
Seg.6(Pattern 1) OUT6 Output Limit of Seg.6(Pattern 1) SV_7 Set Point of Seg.7(Pattern 1) TM_7 Run Time of Seg.7(Pattern 1) OUT7 Output Limit of Seg.7(Pattern 1) SV_8 Set Point of Seg.8(Pattern 1) TM_8 Run Time of Seg.8(Pattern 1) OUT8 Output Limit of Seg.8(Pattern 1) SV_12 Set Point of...
Page 167
OUT42 Output Limit of Seg.4(Pattern 2) SV_52 Set Point of Seg.5(Pattern 2) TM_52 Run Time of Seg.5(Pattern 2) OUT52 Output Limit of Seg.5(Pattern 2) SV_62 Set Point of Seg.6(Pattern 2) TM_62 Run Time of Seg.6(Pattern 2) OUT62 Output Limit of Seg.6(Pattern 2) SV_72 Set Point of...
Page 168
OUT2 Integral Time OUT2 Derivative Time CYT2 OUT2 Cycle Time HYS2 OUT2 Hysteresis GAP1 OUT1 Control Gap GAP2 OUT2 Control Gap Function Lock INP1 Input Type Selection ANL1 Linear Input Zero Calibration ANH1 Linear Input Span Calibration Decimal Point Position LSPL Lower Set Point Limit 16 USPL...
Page 169
CLO3 TRS Lower Calibration CHO3 TRS Upper Calibration RUCY Full run time of motor valve WAIT Full run time of proportional motor valve SETA Protocol Selection BITS Communication Bits IDNO ID Number BAUD Baud rate SVOS SV Compensation PVOS PV Compensation UNIT Unit of PV and SV PVFT...
Page 170
SET8 Hide/ Display parameter SET9 Hide/ Display parameter SET0 Hide/ Display parameter INP2 Hide/ Display parameter OUTY Hide/ Display parameter Output mode selection OUT% Firmware Version OBIT Output percentage CT Current Value Process Value 2.8.1.3 Connecting to HMI Configuring the PLC Note: For more detailed information please refer to the PLC manual.
Page 171
Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Taiwan Instrument & Control Co.,Ltd. Under Product Series select TAIE FY100/900 Series. Verify the parameters match the window above. 2.8.1.4 Wiring diagrams HMI (ex.P5043N) COM2 Pinout...
Page 172
*Looking into HMI PIN# COM2 (RS485) DATA+ DATA- HMI COM3 Pinout *Looking into HMI Device PIN# COM3 (RS-422/RS-485) ISO_GND DATA+ DATA- P5070S/P5070N/P5070N1/P5102N/P5102N1 HMI COM3 Port PLC RS485 Port 6 DATA+ 12 DATA+ 7 DATA- 11 DATA-...
2.9 Delta DVP Series 2.9.1.1 Communication Setting Item Default Setting Remark Signal Level RS232C Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method MODBUS ASCII 2.9.1.2 Memory Resource Review Device Description Data Input Min. Max. format Input relay Output relay...
Page 175
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Delta Electronics, Inc Under Product Series select DVP Series Make sure the other parameters are set at the values in the figure. 2.9.1.4 Wiring Diagrams HMI COM1 Pinout *Looking into COM1 Port PIN#...
Page 176
PLC RS232 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 5 TXD 3 TX 4 RXD 5 GND 8 GND Wiring Diagrams:All P5Series...
AH500 Series 2.9.2.1 Communication Setting Item Default Setting Remark Signal Level RS232C Baud Rate 9600 Data Length Stop Bit Parity Even PLC Station No. Communication Method MODBUS ASCII 2.9.2.2 Memory Resource Review Device Description Data Input Min. Max. format DDD.D 511.15 Input relay DDD.D...
Page 178
Relay Stepping Relay DDDD 2047 Timer DDDD 2047 Timer memory DDDD 2047 Counter DDDD 2047 Counter memory DDDD 2047 32-bit Counter 32-bit Counter memory Special data register DDDD 2047 Index register 2.9.2.3 Connecting to HMI Configuring the PLC Use the application ISPSoft (Ver. 2.05) to configure the PLC. The application COMMGR is used to establish the connection between the PLC and the computer.
Page 179
In ISPSoft, under the Tools menu option, select Communication Settings. Select the name of the connection configured in COMMGR and press OK. Under the PLC menu option, select Transfer and Upload. If there is a program on the PLC, it will be uploaded and the system settings can be configured. If there is no program present on the PLC one will have to be downloaded.
Page 180
If program has to be downloaded onto the PLC, press open and select a program. In the active folder, there are example programs. The device associated with the example program may not be the same as the device connected. Under Tools, select PLC Type and select the device currently used.
Page 181
Under the PLC menu option, the program and PLC configurations can be downloaded onto the device. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 182
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Delta Electronics, Inc Under Product Series select Delta AH500 Series Select the appropriate Port to establish connection with the PLC. Verify the other parameters are configured correctly. 2.9.2.4 Wiring Diagrams HMI COM1 Pinout *Looking into COM1 Port...
Page 183
PLC COM1/COM2 Pinout *Looking into PLC PIN# Signal All P5 Series HMI COM1 PLC RS232 Port 2 RX 3 TXD 3 TX 2 RXD 5 GND 5 GND Wiring Diagrams:All P5Series...
2.10 Panasonic FP Series 2.10.1.1 Communication Setting Item Default Setting Remark Signal Level RS232C Baud Rate 9600 Data Length Stop Bit Parity PLC Station No. Communication Method MEWTOCOL (computer link) 2.10.1.2 Memory Resource Review Device Description Data Input Min. Max. format External input relay DDDD...
Page 185
Internal relay Link Relay Data register DDDDD 99999 Link data register DDDD 8447 Timer/Counter set DDDD 3071 value area Timer/Counter DDDD 3071 elapsed value area File register DDDDD 99999 2.10.1.3 Connecting to HMI Configuring the PLC If the PLC does not connect based on the default communication settings, configuration of the PLC settings is needed.
Page 186
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Panasonic Corporation Under Product Series select FP Series Select COM1 for the port Select 1 for the station number Verify the other settings are consistent with the settings on the PLC.
Page 187
2.10.1.4 Wiring Diagrams PLC RS232 Pinout *View looking into PLC PIN# Signal HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232) All P5 Series HMI COM1 PLC RS232 Port 2 RX 2 TXD 3 TX 3 RXD...
5 GND 1 GND Wiring Diagrams:All P5Series FP Series (Ethernet) 2.10.2.1 Communication Setting Item Default Setting Remark Signal Level Ethernet With AFPX-COM5 Internet Protocol 192.168.1.100 Port 9094 PLC Station No. Communication Method MEWTOCOL (computer link) 2.10.2.2 Memory Resource Review Device Description Data Input...
Page 189
Counter DDDD 3071 External input relay External output relay 16 Internal relay Link Relay Data register DDDDD 99999 Link data register DDDD 8447 Timer/Counter set DDDD 3071 value area Timer/Counter DDDD 3071 elapsed value area File register DDDDD 99999 2.10.2.3 Connecting to HMI Configuring IP Address on PLC Use the application Configurator WD to view/change the IP address on the PLC.
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Panasonic Corporation Under Product Series select FP Series(Ethernet) Enter the IP Address that was written into the PLC. Enter the Port number that was set on the PLC. 2.11 YASKAWA Extended MEMOBUS 2.11.1.1 Communication Setting...
Page 191
2.11.1.2 Memory Resource Review Device Description Data Input Min. Max. format Input bits(Read only) HHHHH FFFFF Data bits DDDDDH 0 65534F Input registers(Read HHHH FFFF only) Data registers DDDDD 65534 Input registers HHHH FFFF (DWord / Read only) Data registers DDDDD 65533 (Dword)
Page 192
Double click 218IFA, or chick 218IFA then chick Edit-Setting the IP address and other parameters can be set. Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select YASKAWA Electric Corporation. Under Product Series select Extended MEMOBUS. Enter the IP Address that was written into the PLC. Verify the parameters match the window above. MP Series Extension (Ethernet) 2.11.2.1 Communication Setting Item...
Page 194
Device Description Data Input Min. Max. format System bits DDDDH 8191F Data bits DDDDDH 0 65534F Input bits HHHHH FFFFF Output bits HHHHH FFFFF System registers DDDD 8191 Data registers DDDDD 65534 Input registers HHHH FFFF Output registers HHHH FFFF Data registers(Dword) DDDDD 65533...
Page 195
the IP address and other parameters can be set. Note: For more detailed information please refer to the PLC manual. Connect PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select YASKAWA Electric Corporation. Under Product Series select MP Series Extension (Ethernet). Enter the IP Address that was written into the PLC. Verify the parameters match the window above. 2.12 Keyence KV-3000/5000/5500/7500(Ethernet) 2.12.1.1 Communication Setting...
Page 197
COMMUNICATION 2.12.1.2 Memory Resource Review Device Description Data Input Min. Max. format Relay DDDdd 99915 Link relay HHHH 7FFF Internal auxiliary DDDDdd 399915 relay Latch relay DDDdd 99915 Timer DDDD 3999 Counter DDDD 3999 CTC_sts High-speed counter comparator (contact) Control relay DDdd 7915 Work relay...
Page 198
comparator (set value) Digital trimmer 2.12.1.3 Connecting to HMI Configuring IP address on PLC Use the application KV Studio to configure the IP address of the PLC. Select the connection between the PLC and the computer. A USB connection was used in this case.
Page 199
On the right side of the dialog window, the IP address and Port can be changed. When done, close out of the window and select ‘Yes’ to save the settings. Under Monitor/Simulator, select Transfer to PLC to download the changes onto the PLC.
Page 200
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Ethernet Under Manufacturer select Keyence Corporation Under Product Series select KV-3000/5000/5500/7500(Ethernet) Set the IP address and Port to the values configured on the PLC. KV-L21V/3000/5000/5500 (host link) 2.12.2.1 Communication Setting Item Default Setting Remark...
Page 202
2.12.2.2 Memory Resource Review Device Description Data Input Min. Max. format Relay DDDdd 99915 Link relay HHHH 7FFF Internal auxiliary DDDDdd 399915 relay Latch relay DDDdd 99915 Timer DDDD 3999 Counter DDDD 3999 CTC_sts High-speed counter comparator (contact) Control relay DDdd 7915 Work relay...
Page 203
value) Digital trimmer 2.12.2.3 Connecting to HMI Configuring the PLC Use the application KV Studio to configure the serial connection of the PLC. Select the connection between the PLC and the computer. A USB connection was used in this case. Under the Monitor/Simulator menu option, select Read from PLC and execute the operation.
Page 204
On the right side of the dialog window, verify the baud rate is 115200bps. Close out of the window and select ‘Yes’ to save the settings. Under Monitor/Simulator, select Transfer to PLC to download the changes onto the PLC. Confirm the execution of the operation...
Page 205
Note: Port 2 of the PLC can also be configured following the steps above. The parameters for Port 2 are under the parameters for Port 1 in the dialog window. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Page 206
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Keyence Corporation Under Product Series select KV-L21V/3000/5000/5500(host link) Under Port select required COM port. Verify the baud rate is the same as the value set on the PLC.
Page 207
HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232) All P5 Series HMI COM1 PLC RS232 Port 2 RX 3 TXD 3 TX 2 RXD 5 GND 5 GND Wiring Diagrams:All P5Series...
Page 208
Using Port 2 HMI COM3 Pinout *Looking into HMI Device PIN# COM3 (RS-422/RS-485) ISO_GND PLC RS485 Port (PORT2) SDA(-) SDB(+)
KV-Nano (host link) 2.12.3.1 Communication Setting Item Default Setting Remark Signal Level RS232C OP-26486 Baud Rate 115200 Data Length Stop Bit Parity Even PLC Station No. Communication Method HOST-LINK COMMUNICATION 2.12.3.2 Memory Resource Review Device Description Data Input Min. Max. format Relay DDDdd...
Page 211
Timer DDDD Counter DDDD CTC_sts High-speed counter comparator (contact) Control relay DDdd 8915 Work relay HHHH 1FFF Data memory DDDDD 32767 Link register HHHH 3FFF Temporary data memory Control memory DDDD 8999 Work memory DDDDD 9999 Index register Timer (current DDDD value) Timer (set value)
Page 212
Choose KV mode (Host Link) and set the Baud rate to 115200. Download the settings back onto the PLC and reset it. Required register ranges...
Page 213
Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI Link settings screen to connect PLC to HMI...
2.12.3.4 Wiring Diagrams Port 1: RS232 Serial COM1 RS-232 RS232 Interface 9 pin D-SUB Female 6 pin Looking into PLC PIN# Signal PIN# Signal Wiring Diagrams:Port 1: RS232 2.13 Beckhoff Automation Twincat(Ethernet) 2.13.1.1 Communication Setting Item Default Setting Remark Signal Level Ethernet...
Page 215
192.168.1.100 Port PLC Station No. Communication Method ADS 2.13.1.2 Memory Resource Review Device Description Data Bits Address Min. Max. Format Input DDDDD.O 0.0 27484.7 Output DDDDD.O 0.0 27484.7 Bit Memory DDDDD.O 0.0 27484.7 DDDDD 65534 DDDDD 65534 DDDDD 65534 DDDDD 65532 DDDDD 65532...
Page 216
2. Use CERHOST to connect with plc, enter IP and Password of plc. After connecting success with plc, click startcontrol panel...
Page 217
Click Network and Dial-up Connections, display information of plc, click plc to ensure the IP. Note: For more detailed information please refer to the PLC manual. Connecting PLC to HMI...
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select FATEK Automation Corp. Under Product Series select FATEK FBe Under Port select the port corresponding to the connection to the PLC Verify the other parameters are consistent with the settings on the PLC 2.14 Koyo...
Page 219
Stop Bit Parity or even, no PLC Station No. 1-90 DirectNET, K sequence 1-247 Modbus RTU Communication Method K sequence (slave), DirectNET (master/slave), Modbus 2.14.1.2 Memory Resource Review Device Data bit Data format Max. Min. Description OOOO 3777 Global Input Bits OOOO 3777 Global Output Bits...
Page 220
2. choose model and build project. click PLC on the top, select ‘’connect’’ to connect.
Page 221
connect success, as shown below. HMI Setting...
Page 222
Within the Link configuration window in FvDesigner: Under Interface Type select Serial Under Manufacturer select Koyo Corporation Under Product Series select Koyo Direct Under Port select required COM port. Verify the baud rate is the same as the value set on the PLC.
Page 223
PIN# Signal Power+ 5V Rx (RS-232C) Tx (RS-232C) Power+ 5V HMI COM1 Pinout *Looking into COM1 Port PIN# COM1 (RS232)
Page 224
All P5 Series HMI COM1 PLC Port 2 RX 4 Tx (RS-232C) 3 TX 3 Rx (RS-232C) 5 GND 1 GND Wiring Diagrams:All P5Series...