Table 1.5 Detail Of Specifications - Mitsubishi Electric 9900CX SERIES Owner Technical Manual

Inclusive parallel operation system application
Table of Contents

Advertisement

Table 1.5 Detail of Specifications

Rated Output kVA
Rated Output kW
Configuration
Voltage
Frequency
Reflected Current THD
Configuration
Voltage
Frequency
Type
Ride Through
Nominal Voltage
Minimum Voltage
Number of Cells
Configuration
Voltage
Voltage Stability
Frequency
Frequency Stability
Power Factor
Power Factor Range
Voltage THD
Transient Response
Transient Recovery
Voltage Unbalance
Phase Displacement
Inverter Overload
System Overload
(with bypass available)
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
1050
1000
AC INPUT
3 phase, 3 wire
480 V
+15% to -20%
60 Hz +/-10%
3% max. at 100% load
STATIC BYPASS INPUT
3 phase, 3 wire
480 V
+/-10%
60 Hz +/-5%
BATTERY
Lead Acid
Application Specific
480 Vdc
400 Vdc
240
AC OUTPUT
3 phase, 3 wire
480 V
+/-1%
60 Hz
+/-0.01% in free running mode
0.95
0.7 lagging to 0.8 leading
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Less than 20ms
2% maximum at 100% unbalanced load
1deg. maximum at 100% load
125% for 10 minutes
150% for 60 seconds
500% for 1 cycle
ENVIRONMENTAL
Forced Air
32゚F to 104゚F ( 0゚C to 40゚C).
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C)
5% ~ 95% Non Condensing
0 to 6500 feet No Derating at 40゚C
Indoor (free from corrosive gases and dust)
Munsell 5Y7/1 (Beige)
MITSUBISHI ELECTRIC 9900CX SERIES UPS
1400
1750
1330
1660