Principle of Operation

Type CSB400 Base Regulator Operation
Refer to Figure 5. When downstream demand
decreases, the pressure under the regulator
diaphragm increases. This pressure overcomes
the regulator setting (which is set by the regulator
control spring). Through the action of the pusher post
assembly, lever, and valve stem, the valve disk
moves closer to the orifice and reduces gas flow.
If demand downstream increases, pressure under
the regulator diaphragm decreases. Spring force
pushes the pusher post assembly downward, the
valve disk moves away from the orifice, and the gas
flow increases downstream as the regulator opens in
response to the decreased pressure underneath the
regulator diaphragm.
Type numbers with a "T", for example, Type CSB400IT,
provide a token or low capacity relief. The Token relief
provides relief from minor overpressure caused by
nicks or dents on the orifice or by thermal expansion
of gas in the downstream line. Token relief also
provides a token or signal, in the form of odor, that an
overpressure situation is occurring.
UPSO aDjUSTIng SCREW
UPSO SPRIng
SEnSE BLOCKIng
SCREW
SLaM-SHUT DISK
REgULaTOR aDjUSTIng SCREW
REgULaTOR COnTROL SPRIng
SLaM-SHUT
ORIFICE
VaLVE STEM
REgULaTOR ORIFICE
Type CSB403 Integral Monitor Operation
Type CSB403 combines the operation of a
conventional two-regulator wide-open monitor set into
one body, see Figure 6. The Integral True-Monitor™
is installed on the inlet side of the body and serves to
throttle flow and maintain an acceptable downstream
pressure in the case where the primary regulator
ceases to regulate downstream pressure. During
normal operation the Integral Monitor is in a wide-open
state as its setpoint is set higher than the primary
regulator. See Table 6 for guidance regarding the
setpoints of the regulator and associated integral
monitor sets. If the downstream pressure should rise
to the setpoint of the Internal Monitor due to a loss of
pressure control by the primary regulator, the Integral
Monitor will assume control and regulate the flow to
the downstream system. If token relief is present, it
will relieve a small amount of gas to the atmosphere
as an indication that the Integral Monitor is controlling
the downstream pressure.
The Type CSB403 provides the option of internal or
external downstream pressure registration. External
registration requires a downstream sensing line. See
Figure 10 for guidance regarding installation of the
downstream control line. Refer to the Type TM600
Instruction Manual for additional details of integral
monitor operation.