Figure 6: Riser Length Measurements - Omega VSHP SERIES Installation And Operation Manual

Vertical stacked water source heat pumps
Hide thumbs Also See for VSHP SERIES:
Table of Contents

Advertisement

OMEGA | WATER SOURCE HEAT PUMPS
Notes:
Risers are sized using a "Top" and "Base" Datum reference. A specified Top Datum Offset indicates where top of riser will be located
relative to top of cabinet. A Base Datum indicates where bottom of riser will be located relative to floor.
Upon request Omega will provide 3 inch deep swage on risers of same pipe size for connection to units on the floor below.
Risers should insert 2 inches into the 3 inch deep swage connection.
Riser Length = Floor Clearance Height + Slab Thickness + 2 inch (overlap) (Rounded up to 120" or 144").
Omega supplies two standard riser lengths, 120" (10') and 144" (12'), to be field cut on-site.
Omega does not supply extension tailpieces or transition riser pieces for joining dissimilar piping sizes.
Risers available in Type L and Type M/DWV copper.
Condensate riser comes standard with 3/8 inch thick closed cell insulation to prevent condensation.
Optional insulation on supply and return risers is available.