Unit Start-Up; Checklist; Initial Start-Up - Omega VSHP SERIES Installation And Operation Manual

Vertical stacked water source heat pumps
Hide thumbs Also See for VSHP SERIES:
Table of Contents

Advertisement

OMEGA | WATER SOURCE HEAT PUMPS
strainers or mechanical filtration system has been in-
stalled and commissioned. The chassis should be at
o
room temperature (68
F) prior to start up.
Once the installation of the cabinet and chassis units is
complete the riser shut-off valves can be opened. The
riser loop system should be filled and all trapped air
should be bled from the system prior to unit start-up.
Water flow failure will cause the unit to trip on the safety
devices. Repeated water flow failures can cause equip-
ment damage.

CHECKLIST

Before energizing the unit ensure all steps are verified in
the following checklist:
___High voltage power supply is correct and in accord-
ance with unit nameplate ratings.
___Unit is electrically grounded and circuit protection is
the correct size.
___Low voltage control wiring is correct as per unit wir-
ing diagram.
___Riser loop system is clean, filled, and vented of any
air.
___Chassis unit high and low pressure caps are firmly
secure and in place.
___Chassis matches the cabinet model number.
___Protective cardboard air coil cover is removed and
unit service cover panel and filter are in place.
___There is a proper seal between chassis service cov-
er panel and unit cabinet.
___Riser shut-off valves are in the OPEN position.
___Riser loop system has been vented for any air intro-
duced during chassis installation.
___Riser loop water is circulating through all units and at
design conditions.
___Unit condensate drain hose is securely attached to
drain pan and condensate riser.
___Indoor unit blower spins freely.
___All ductwork is complete.
___Clean filters are installed.
___All cutting, sanding, drywalling, patching work is
complete.
___Unit blower spins freely.
___Thermostat is in the OFF position.
9
INITIAL UNIT START-UP
1.
Close disconnect switch.
2.
Set thermostat to a high setting (above current room
temperature), set system to COOL with fan on AU-
TO. The compressor should not run.
3.
Lower the thermostat temperature setting until the
fan and compressor energize. Verify the following
results:
Leaving water temperature (LWT) in the heat ex-
changer water coil is warmer than the entering wa-
ter temperature (EWT) by approximately 9
Blower is running smoothly.
Compressor and blower amps are within nameplate
data.
Suction line is cool and no frosting is forming in the
refrigeration circuit.
4.
Set thermostat to the OFF position. Unit compressor
and fan should stop running.
5.
Allow the system to equalize for approximately 5
minutes.
6.
Set thermostat to the lowest setting and switch to
the HEAT position.
7.
Adjust thermostat temperature higher until the fan
and compressor energize. The following should
occur:
Warm air will flow from the supply register.
Leaving water temperature (LWT) in the heat ex-
changer water coil is cooler than the entering water
temperature (EWT) by approximately 5
Blower and compressor operation is smooth and no
frost development is visible in the refrigeration cir-
cuit.
8.
Set the thermostat to the desired temperature.
9.
Check for any water leaks at the hose connections.
o
o
F—12
F.
o
o
F—9
F.
www.omega-heatpump.com