Error messages of FB MODBUSCP
STATUS
Event text
(Hex)
An exception telegram with exception code 1 was
A091
received (only if CP is client)
An exception telegram with exception code 2 was
A092
received (only if CP is client)
An attempt to an invalid or non existing address at the
communication partner was made.
An exception telegram with exception code 3 was
A093
received (only if CP is client)
An exception telegram with exception code 4 was
A094
received (only if CP is client)
An exception telegram with an unknown exception
A095
code was received (only if CP is client).
OPEN MODBUS / TCP communication via CP343-1 and 443-1
2XV9450-1MB00; Manual edition 4.3
Remedy
The communication partner does
not support the requested
function.
Correct LENGTH or
START_ADDRESS at the call of
the FB.
The communication partner can't
process the received request
(e.g. doesn't support the
requested length).
The communication partner is in
a state, in which the received
request can't be processed.
Check the error message of the
communication partner and verify
the data with a telegram trace if
needed.