Setting Of Address Switch - Mitsubishi Electric PEFY Series Technical & Service Manual

Indoor unit
Hide thumbs Also See for PEFY Series:
Table of Contents

Advertisement

7-2. Setting of address switch

< At delivery (All models)>
ON
OFF
0 1 2
G
1
2 3
FP-AD-R
3
2
1
SWA
<1> In case using M-NET remote controller, address is set by rotary switches. (SW11,SW12)
* It is not necessary setting address in case of using unit remote controller.
Indoor unit do not run without address setting in field.
<2> Indoor unit address setting rule is different by each field work.
Refer to install manual of outdoor unit , operate the address setting.
<3> Setting the address is combination of SW11 (1st digit address setting) and SW12 (2nd digit
address setting).
Address "3" setting is composed SW11 "3" and SW12 "0".
Address "25" setting is composed SW11 "5" and SW12 "2".
HWE12120