The same applies to the use of accessories. General dangers of failing to follow the safety instructions The ML71BS6 CAN bus module complies with the state of the art and is fail-safe. The device may give rise to further dangers if it is inappropriately installed and operated by untrained personnel.
Page 5
G36.35.0) Conversions and modifications No modifications that affect the design or the technical safety of the ML71BS6 CAN bus module may be carried out without our express agreement. Any modification shall exclude all liability on our part for any resulting damage.
MGCplus−ML71BS6 Introduction The ML71BS6 is an MGCplus system module that takes measurement data from the MGC and outputs it as CAN messages. It records up to 128 measured values per CAN port, scales them and outputs them at the CAN bus.
MGCplus−ML71BS6 Connections WARNING Before starting the device, read the safety instructions. 2.1 Pin assignment The CAN bus is connected to the AP71 connection board by a 9-pin Sub-D connector. You can connect two independent CAN field bus systems (female connectors CAN1 and CAN2). Both the CAN interfaces are used to output the MGCplus measurement data.
MGCplus−ML71BS6 Front panel The front panel LEDs have a dual function: In Level mode, the signal level at the analogue output is displayed. In Status mode, the LEDs are assigned as shown below: LED caption Colour Meaning in Status mode ML71 CHAN.
MGCplus−ML71BS6 Parameterization 4.1 Settings CAN1 /CAN2 The baud rate, the transmission formats, the number of signals and the output rate of the 1st CAN bus are set here. The same menu is applied correspondingly to the 2nd CAN bus. The maximum number of signals for a bus is 128 signals.
Page 10
MGCplus−ML71BS6 Use the shift key to change to set-up mode and then press the function key . Use the cursor keys to select “Settings CAN1” and confirm with Settings CAN1 CHANNEL3 Baud rate 1000 kBaud Format Float 1000 kBaud Number of signals...
MGCplus−ML71BS6 4.1.1 Panel output signals CAN 1 This is where to set the sources for the signals to be transmitted and if necessary, scaling for the output values. Use the shift key to change to set−up mode and then press the function key .
Page 12
MGCplus−ML71BS6 Formats 2 and 3; 32-bit integers and 16-bit integers You must also specify scaling here. Use the shift key to change to set−up mode and then press the function key . Use the cursor keys to select “Sources CAN1” and...
MGCplus−ML71BS6 Menu structure in set-up mode The set−ups for the MGCplus unit are subdivided into groups according to their function. Pressing the shift key takes you to the set-up dialogue, and the selection bar is displayed. Setup for channel Display in Setup mode...
MGCplus−ML71BS6 CAN protocol Up to 128 measured values can be transmitted at each bus. A number of signals is assigned to each bus. This determines the signal transmission rate at the particular CAN port (in the case of CAN port 2, the operating mode of CAN port 1 is also a factor).
Page 15
MGCplus−ML71BS6 Measurement data messages CAN port 1: Absolute values in Float (identifier: default values) Identifier 8−byte data field 0x200−0x23F 4−byte measured value 1 (absolute 4−byte measured value 2 (absolute Float) Float In digits from 7680000 (= 24−bit) as Long Identifier 8−byte data field...
MGCplus−ML71BS6 Specifications CAN interface Number of CAN interfaces Protocol CAN 2.0B Baud rate Baud 125k 250k 500k Line length 1000 1000 1000 500 Hardware bus link individually selecta- Standard High Speed ISO 11898−24 V ble for each CAN interface Fault Tolerant Low Speed Connection technique 2x 9−pin DSUB, individual potential separation...