Nebs Compliance; Power Supplies; Installation Grounding Requirement (Dc Power Supplies Only) - Cisco UCS C240 M3 Service Note

Nebs server
Hide thumbs Also See for UCS C240 M3:
Table of Contents

Advertisement

Features Specific to the Cisco UCS C240 M3 NEBS Server

NEBS Compliance

The Cisco UCS C240 M3 NEBS Server has been certified for the following levels of NEBS compliance:

Power Supplies

The Cisco UCS C240 M3 NEBS server can use either AC or DC power supplies.
650 W AC Power Supply
The NEBS server can use one or two 650 W AC power supplies (Cisco PID UCSC-PSU-650W).
930 W DC Power Supply
The NEBS server can use one or two 930 W, –48 VDC power supplies (Cisco PID
UCSC-PSU-930WDC).

Installation Grounding Requirement (DC Power Supplies Only)

The 650 W AC power supplies have internal grounding and so no additional grounding is required when
the supported AC power cords are used.
When using the DC power supply, additional grounding of the server chassis to the earth ground of the
rack is required. Screw holes for use with your grounding lugs and grounding wires are supplied on the
chassis rear panel.
Note
The grounding points on the chassis are sized for M5 screws. The grounding points are spaced at 0.625
inches (15.86 mm). You must provide your own screws, grounding lug, and grounding wire. The
grounding lug required is a Panduit LCD10-14AF-L or equivalent. The grounding cable that you provide
must be 14 AWG (2 mm), minimum 60° C wire, or as permitted by the local code.
See
Cisco UCS C240 M3 NEBS Server Service Note
2
The DC-power version of the server is certified for NEBS Level 3 compliance.
The AC-power version of the server is certified for NEBS Level 1 compliance.
The server is certified for NEBS Level 1 compliance when using these AC power supplies.
These power supplies are hot-swappable with 1+1 redundancy when two power supplies are present.
See
Power Supply Specifications, page
See the
Cisco UCS C240 Server Installation and Service Guide,
replacing a power supply.
The server is certified for NEBS Level 3 compliance when using these DC power supplies.
These power supplies are hot-swappable with 1+1 redundancy when two power supplies are present.
See
Power Supply Specifications, page
See the
Cisco UCS C240 Server Installation and Service Guide,
replacing a power supply.
Figure 1-1
for the location of the grounding lug screw-holes on the chassis rear panel.
6, for information about these power supplies.
Chapter 3, for information about
6, for information about these power supplies.
Chapter 3, for information about
OL-28629-01