Safety Devices; Cooler Protection; Relief Devices - Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

Table 43 Thermistor Temperatures vs
Resistance, Motor Temperature Thermistors
TEMP
TEMP
(F)
(C)
–22
–30
–13
–25
–4
–20
5
–15
14
–10
23
–5
32
0
41
5
50
10
59
15
68
20
77
25
86
30
95
35
104
40
113
45
122
50
131
55
140
60
149
65
158
70
167
75
176
80
185
85
194
90
203
95
212
100
221
105
230
110
239
115
248
120
NOTE: Motor temperature thermistor values must be verified using resistance.
Voltage drop cannot be used.
Table 44 — Thermistor
(Liquid Level Sensor) Depth
UNIT MODEL
NUMBER
30GX080-090
30GX105-115
30GX125-136
30GX150,151
30GX160,161
30GX175,176
30GX205-226
30GX250-265
30GX281-350
30HXA,C076-086
30HXA,C096
30HXA,C106
30HXA,C116-126
30HXA,C136-146
30HXA,C161-171
30HXA,C186
30HXA,C206
30HXA,C246-271
Table 45 — Calibrating Pressure Transducers
(Pressure Gage Installed)
KEYPAD ENTRY
CALIBRATION
OFFSET
CIRCUIT A
PRESSURE
Discharge Pressure
84.2 PSI
Discharge Pressure
ENTER
85.0 PSI
Safety Devices —
The 30GX/HX chillers contain many
safety devices and protection logic built into the electronic
control. Following is a description of the major safeties.
RESISTANCE
(Ohms)
88,480.0
65,205.0
48,536.0
36,476.0
27,663.0
21,163.0
16,325.0
12,696.0
9,949.5
7,855.5
6,246.0
5,000.0
4,028.4
3,265.7
2,663.2
2,184.2
1,801.2
1,493.1
1,243.9
1,041.4
875.8
739.7
627.6
534.9
457.7
393.3
339.3
293.8
255.3
222.6
194.8
THERMISTOR DEPTH
"X"-in. (mm)
6.00 (152.4)
4.25 (108.0)
5.56 (141.2)
6.00 (152.4)
4.25 (108.0)
4.25 (108.0)
3.94 (100.0)
4.82 (122.4)
5.00 (127.0)
5.13 (130.3)
6.00 (152.4)
4.25 (108.0)
5.13 (130.3)
6.00 (152.4)
4.25 (108.0)
5.56 (141.2)
3.94 (100.0)
4.82 (122.4)
DISPLAY
COMMENTS
RESPONSE
Current reading is
displayed.
Enter gauge pressure
reading to nearest
tenth. Control will
allow offset of up to
6 psig. Transducer
calibration is now
complete.
COMPRESSOR PROTECTION
Motor Overload — The compressor protection modules
(CPM) protect each compressor against overcurrent. Do not
bypass the current transducers or make any changes to the
factory-installed and configured 8 pin headers. The configura-
tion of these headers defines the Must Trip Amps (MTA) at
which the CPM will turn the compressors off. Determine the
cause for trouble and correct the problem before resetting the
CPM. See Appendix A for setting of MTAs and configuration
headers.
Each CPM board also reads the status of each compressor's
high-pressure switch. All compressors have factory-installed
high-pressure switches. For 30GX units, the switch is set to trip
at 303 ± 7 psig (2089 ± 48 kPa). The setting for 30HXA units is
275 ± 7 psig (1896 ± 48 kPa) and for 30HXC units the setting
is 191 ± 7 psig (1317 ± 48 kPa). If the switch opens during op-
eration, the compressor will be shut down. The CPM will reset
automatically when the switch closes, however, a manual reset
is required to restart the compressor.
OIL SEPARATOR HEATERS (30GX) — Each oil separator
circuit has a heater mounted on the underside of the vessel.
The heater is energized with control circuit power. Oil heaters
are energized when the discharge gas temperature falls below
105 F (40.6 C). The heaters are deenergized when the dis-
charge gas temperature rises above 110 F (43.3 C). The control
will allow the chiller to attempt to start with the heaters ener-
gized and will keep the heaters on, even when running, until
the discharge gas temperature reaches 110 F (43.3 C). Note
that the oil heaters are deenergized if the oil level switch is
open.

COOLER PROTECTION

Low Water Temperature — Microprocessor is programmed
to shut the chiller down if the leaving fluid temperature drops
below 34 F (1.1 C) for water or more than 8° F (4.4° C) below
set point for brine units. When the fluid temperature rises 6° F
(3.3° C) above the leaving fluid set point, the safety resets and
the chiller restarts. Reset is automatic as long as this is the first
occurrence of the day.
IMPORTANT: If the unit is installed in an area where
ambient temperatures fall below 32 F (0° C), cooler
heaters and inhibited ethylene glycol or other suitable
solution must be used in the chilled fluid circuit.
Relief Devices —
cuit (30GX only) between the condenser and the liquid line
shutoff valve.
PRESSURE RELIEF VALVES — Valves are installed in each
circuit and are located on all coolers. One relief valve is also
installed on each 30HXC condenser. Both circuits' oil separa-
tors on 30GX and 30HXA units have factory-installed relief
valves as well. These valves are designed to relieve if an
abnormal pressure condition arises. Relief valves on all coolers
and 30HXC condensers relieve at 220 psi (1517 kPa). Relief
valves on 30GX and 30HXA oil separators relieve at 320 psi
(2206 kPa). All 30HXA, HXC units with factory-installed suc-
tion service valves also have a relief valve in each compressor
discharge line. These valves are designed to relieve at 350 psig
(2413 kPa). These valves should not be capped. If a valve
relieves, it should be replaced. If the valve is not replaced, it
may relieve at a lower pressure, or leak due to trapped dirt
from the system which may prevent resealing.
Pressure relief valves located on cooler and condenser shells
and 30HXA oil separator shells have
for relief. The 30GX oil separators have
nections. Some local building codes require that relieved gases
be removed. This connection allows conformance to this
requirement.
64
Fusible plugs are located in each cir-