PHOENIX RECOMMENDED CABLES
A 3-conductor will typically be used with the FSR100.
Cable
Plenum
Function
Type
Rated
2C
No
24 Vac power to
Round
LOSEA or
Pneumatic (110'
max at load
24 Vac power to
HiSea (288' max
at load
2C
Yes
24 Vac power to
Round
LOSEA or
Pneumatic (110'
max at load
24 Vac power to
HiSea (288' max
at load
TP
No
FTT-10 (4500')
TP1250 (425')
FTT-10 (8800')
TP
Yes
FTT-10 (4500')
TP1250 (425')
FTT-10 (8800')
3C
No
Signal
Round
3C or
Yes
Signal
4C
Round
4C
No
Signal
Round
5C
No
Signal
Round
8C
No
Signal
8C
Yes
Signal
3C
No
Shielded
MS/TP
©2010 Phoenix Controls Specifications subject to change without notice.
Wire
Gauge
Vendor/Part #
18
Belden 9409
1, 2
)
14
Belden 9411
1, 2
)
18
Belden 82740
1, 2
)
14
Windy City
NP007960
1, 2
)
22
Windy City 107500
16
Windy City 109600
22
Windy City 105500
16
Windy City 109500
22
Belden 8443
22
Belden 88444
22
Belden 8444
22
Belden 8445
22
Belden 9421
22
Comtran 4956
22
Belden 3106A
(120 ohm)
Primary
Alternate
Vendor/Part #
Windy City
NP002360
Connect Air
W221P-1002
Connect Air
W221P-2001
Windy City
004380
Manhatten
M13304
Manhatten
M13305
Manhatten
M13308
See specifications
below for alternate
cable solutions
Rev. 5/10
MKT-0266
MPC-1480
Color Code
1: Red
2: Black
1: Red
2: Black
1: White/Blue stripe
2: Blue/White stripe
1: White/Blue stripe
2: Blue/White stripe
1: Red
2: Black
3: Green
1: Red
2: Black
3: Green
4: White (not used as 3C)
1: White
2: Green
3: Black
4: Red
1: White
2: Brown
3: Black
4: Red
5: Green
1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
1: White
2: Orange
3: Black
4: Red
5: Green
6: Yellow
7: Blue
8: Brown
1: White with Orange stripe
2: Orange with White stripe
3: Blue with White stripe
F
S
R
AN
TATIC
ESET
Notes
Must be
stranded
Must be
stranded
For more
alternatives
visit:
echalon.com
For more
alternatives
visit:
echalon.com
Must be
stranded
Must be
stranded
Must be
stranded
Must be
stranded
No
substitutes
No
substitutes
Shielded with
drain
K