Receiving / Unpacking / Handling / Storage; Inspection And Maintenance During Storage - Greenheck BIDW Installation, Operation And Maintenance Manual

Centrifugal,industrial process,filtered supply
Table of Contents

Advertisement

Receiving
Upon receiving the product check to make sure all items
are accounted for by referencing the delivery receipt or
packing list. Inspect each crate for shipping damage
before accepting delivery. Notify the carrier if any
damage is noticed. The customer will make a notation
of damage (or shortage of items) on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. If damaged, immediately contact your local
representative. Any physical damage to the unit after
acceptance is not the responsibility of manufacturer.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Fans are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce the ability of the
fan to resist corrosion. Fans should never be lifted by
the shaft, fan housing, motor, belt guard or accessories.
Storage
• Rotate fan wheel monthly and purge bearings once
every three months.
• Energize fan motor once every three months.
• Store belts flat to keep them from warping and
stretching.
• Store unit in location which does not have vibration.
• After storage period, purge grease before putting fan
into service.
If storage of fan is in a humid, dusty or corrosive
atmosphere, rotate the fan and purge the bearings once
a month. Improper storage which results in damage to
the fan will void the warranty.
Fans are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the fan and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR -
The ideal environment for the storage of
fans and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
2
Centrifugal, Industrial and Filtered Supply
should be evenly maintained between 30°F to 110°F
(-1°C to 43°C). Wide temperature swings may cause
condensation and "sweating" of metal parts. All
accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice or snow
and wipe dry before moving to indoor storage. To avoid
"sweating" of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR -
Fans designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the fan. The fan should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all fan parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Fan wheels should be blocked to prevent spinning
caused by strong winds.
Inspection & Maintenance during Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe clean thoroughly
®
with Tectyl
506 (Ashland Inc.) or the equivalent.
For hard to reach internal surfaces or for occasional
use, consider using Tectyl
WD-40
or the equivalent.
®
®
511M Rust Preventive or