Medium intensity red led obstruction lighting system (40 pages)
Summary of Contents for Flash Technology VANGUARD FTS 370d
Page 1
® VANGUARD FTS 370d, 370w, 370r LED Medium Intensity Obstruction Lighting System Reference Manual Part Number F7913702 SERIAL NUMBER Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 www.spx.com/en/flash-technology (615) 261-2000...
Page 5
The flashhead cable is properly secured to the tower so the insulation won’t become cut or damaged with wind and time. Using the Flash Technology’s two supplied tapes and the 2-3-4 layer method, secure the cable to the tower (Not exceeding 5’...
Page 6
Marker Interface Junction Box (SC 370d only) The Marker Interface Enclosure is mounted at the marker tier level. Flash Technology provided hardware used for mounting the Marker Interface Enclosure (4 points of contact to Universal Mounting brackets). Both latches are secured to prevent water intrusion.
Page 7
Flash Technology assumes no liability for damages resulting from any errors or omissions in this manual, or from the use of the information contained herein. Flash Technology reserves the right to revise this manual without obligation to notify any person or organization of the revision.
Page 8
Dangerous line voltages reside in certain locations in this equipment. Also, this equipment may generate dangerous voltages. Although Flash Technology has incorporated every practical safety precaution, exercise extreme caution at all times when you expose circuits and components, and when you operate, maintain, or service this equipment.
Table of Contents Front Matter ............................i Personnel Hazard Warning ........................ ii Table of Contents..........................iii List of Figures .............................v List of Tables ............................ vi Section 1 – Introduction and Operation ....................1 Introduction.............................1 System Overview ........................1 Specifications..........................2 SC 370.............................4 Operation Overview........................
Page 10
System X Firmware ........................67 USB Firmware Update........................68 Information Display Alarms ......................68 Section 4– Web Interface........................70 Web Interface (Optional) ......................70 System Access via WiFi .......................70 Lighting Inspection (LI)........................71 Mode Override ..........................72 Auxiliary Input..........................72 Event Log............................73 Configuration ..........................73 Section 5 – Maintenance and Troubleshooting.................77 Safety ............................77 Preventive Maintenance........................77 Storage ............................77...
Section 1 – Introduction and Operation Introduction FTS 370d and FTS 370w are LED connected to form one lighting system. Medium Intensity Obstruction Lighting Optional GPS synchronization is available Systems. FTS 370d series are Dual if additional SC 370s are required. Lighting Systems (red/white) for L- 864/865 applications.
Specifications Table 1-1 – Physical Specifications Equipment Model Physical Specifications SC 370 System Controller (Standard): Dimensions H x W x D (millimeters) 23.82 x 17.25 x 8.51 in (605 x 438.3 x 216.2) Weight (kilograms) 39 lb (18.1) SC 370 System Controller (Stainless Option): Dimensions H x W x D (millimeters) 23.00 x 17.13 x 6.44 in (584.2 x 435.1 x 163.6)
SC 370 Operation Overview the fuses or MOV. Fuse holders are An internal view of the SC 370 is shown hinged on the lower side. Pull down and in Figure 1-1. Component layout open the side cover to access the fuse. diagrams with part names and numbers are shown in Figures 6-1 (AC) and 6-2 (DC).
PCB1 Controller Board PCB1 controls and monitors operation of photo below, is discussed in the following the SC 370 and its associated flashhead. subheadings. Each section of PCB1, outlined in the Manual Status & Control OLED Override Alarm Interface Alarm LEDs Display Interface &...
PCB1 Information Display and User Interface A multi-line OLED (Organic Light- cursor position. The information display Emitting Diode) display provides system defaults to show the current system status status, alarm programming as well as the basic configuration for the information. Three pushbuttons located to unit.
Table 1-3 – Status & Alarm LEDs Indication Red to indicate one or more of the following conditions: 1. The connected beacon is experiencing a failure in Day mode. DAY ALARM 2. The beacon is not communicating with the SC 370. The Day Alarm will be accompanied by the Night Alarm and the Comm.
Alarm Interface & Mode Indicator Connections Dry contact alarm connections, located on an open contact between COM and NO PCB 1, are available regardless of any indicates the system is operating in Night additional monitoring method used. The mode and a closed contact indicates the available dry contact alarm outputs are system is operating in Day mode.
Page 21
P2 Auxiliary Input J4 Communication Cable Connection systems consisting of more than one SC 370 unit require connection communication cable between units. located on the lower The Auxiliary Input (previously labeled right of PCB1, provides LOW BAT) allows an external device, connection for two RJ such as a radar system, to inhibit the 45 connectors.
PCB3 Smart Board includes instructions and all components The optional PCB3 “Smart Board” (PN necessary for installation. Antenna 2424500) is installed on top of PCB1 of installation instructions are provided in the SC 370 programmed as System 1. It Section 2 “GPS Antenna” for systems provides an interface to the following ordered with GPS Sync factory installed.
FH 370d/w/r FH 370d/w/r, shown in Figure 1-6, is divided into two sections: light engine, and base assembly. The light engine is comprised of highly efficient LEDs which are focused by Fresnel optics to produce the required output per FAA specifications for the following types: L-864/865 (dual), L865 (white), L-866/885 (dual Catenary), L-885 (white Catenary) or L-866 (red...
Marker Interface Enclosure (SC 370d - L-864/865 only) termination point at the flashhead. Marker Operation Overview connections are provided at terminals J1 – The Marker Interface Enclosure mounting J4 located on the Marker Interface PCB. diagram is shown in Figure 2-14 (Stainless Steel option shown in Figure 2-15) and Marker programming, control and status the wiring diagram is shown in Figure 2-...
MKR 370 (SC 370d L-864/865 only) Red (620nm) LEDs and IR (850nm) LEDs MKR 370 DC, shown in Figure 1-8, is a ensures maximum visibility to pilots in all 24V DC LED L-810 marker. circumstances. innovative design combines three highly efficient LED’s and Fresnel optics into a Operational power is supplied by the compact cast aluminum base which is easy...
Upon completion of the system installation, panels are requested. Please contact the verify that the Information Display, located Flash Technology parts department at 1- on PCB1, shows the correct configuration 800-821-5825 if this option is desired. Revision 10 – 1/09/2015...
75’ are available. Also, the cable may be supplied with your equipment. spliced to provide additional length. The Flash Technology wiring diagrams define recommended minimum wire gauge is 16 only minimum requirements AWG if additional length is necessary.
simultaneously accommodate a Vanguard Ensure that installation Photodiode, Cellular Antenna, and GPS watertight. Antenna as shown in Figure 2-1. Note: See Cellular Antenna and GPS Antenna additional information Note: The antenna must be mounted regarding the Antenna Mounting Bracket outdoors to ensure optimal reception.
6. Tighten the cable strain relief on the 6. Mount the Antenna Mounting Bracket bottom of the SC 370 enclosure using one of the following methods: Wall securely. Mount: screws (not included) to mount to the outside GPS Antenna wall of a shelter.
Cellular Antenna PHD 512 Antenna Figure 2-1 – Antenna Mounting Bracket with PHD 512, Cellular and GPS Antennas (Body Mount Antenna shown) Magnetic Mount Antenna Body Mount Antenna Verizon Only AT&T or Verizon Figure 2-2 – Antenna Types Revision 10 – 1/09/2015 FTS 370d/w/r...
Communication Cable Kit supplied hardware kit. Figure 2-3 provides a pictorial of the installation. A CAT 5 cable provides the RS 485 Connection to the WiFi access point is communications link between the SC 370 discussed in Section 4. designated as System 1 and all subordinate units installed in the system.
Flash Technology recommends cable near the controller. monitoring contacts that are open in an alarm condition. Flashhead Cable Flash Technology cable (PN 4370000) provides optimal system performance while minimizing vulnerability Lightning and EMI (Electromagnetic Interference). The cable is comprised of two 8 AWG conductors with an overall aluminized Mylar shield and drain.
Page 34
Securing the Cable Flash Technology provides the material 3. Wrap four full turns of two-inch for securing the flashhead cable to a Scotchrap #50 tape, or the equivalent, skeletal structure with the following over the Scotchrap Filament #890 tape. technique.
through the strain relief and tighten the Marker Interface Enclosure dome nut. (FTS 370d L-864/865 only) 4. Connect the three conductor flashhead cable to the terminal strip TB1 using a Note: Complete instructions installing Marker Interface non-flared flat tip screwdriver: Enclosure, marker mounting brackets a.
The flashhead is mounted to the tower pedestal utilizing ½ inch galvanized or Note: Flash Technology’s “T”- Level stainless steel hardware. Four mounting (Optional Part # 11000013455) has two holes are provided on the flashhead base vials to simplify installation.
Wiring a. Connect the red wire to the terminal labeled DC+. NOTE: Install a 5’ service loop in the b. Connect the black wire to the cable near the flashhead. terminal labeled DC-. 1. With the flashhead securely mounted c. Connect the bare drain wire to the to the tower, unfasten the two latches terminal labeled GND.
LIGHTNING ROD MUST EXTEND 36" (MIN) ABOVE AND BE LOCATED 18" HORIZONTALLY AWAY FROM UPPERMOST FLASHHEAD(S) FLASHHEAD FH370d/w #8 AWG MIN GROUND WIRE FROM FLASHHEAD TO TOWER STEEL MARKER INTERFACE ENCLOSURE MKR 370 LED 1/2 OVERALL L-810 MARKERS TOWER HEIGHT #8 AWG MIN GROUND WIRE FROM MARKER INTERFACE...
LIGHTNING ROD MUST EXTEND 36" (MIN) ABOVE AND BE LOCATED 18" HORIZONTALLY AWAY FROM UPPERMOST FLASHHEAD(S) FLASHHEAD FH370d/w #8 AWG MIN GROUND WIRE FROM FLASHHEAD TO TOWER STEEL MARKER INTERFACE ENCLOSURE MKR 370 LED 3/4 OVERALL TOWER HEIGHT L-810 MARKERS #8 AWG MIN GROUND WIRE FROM MARKER INTERFACE...
SC 370 units connected. Assume 340 VA per SC 370. Also see Note 5. 2. Use only Flash Technology PN 4370000 to connect the flashhead to the SC 370. Splicing of the cable is not permissible on D1 and D2 systems. A 5’ service loop should be placed at the base of the tower near the controller and just below the flashhead.
340 VA per SC 370. Also see Note 5. 2. Use only Flash Technology PN 4370000 to connect the flashhead to the SC 370. Splicing of the cable is permissible only at the marker interface box (if installed). A 5’ service loop should be placed at the base of the tower near the controller, just below the flashhead and above and below the marker interface box (if installed).
SC 370 units connected. Assume 340 VA per SC 370. Also see Note 5. 2. Use only Flash Technology PN 4370000 to connect the flashhead to the SC 370. Splicing of the cable is not permissible on Catenary systems. A 5’ service loop should be placed at the base of the tower near the controller and just below the flashhead.
MODE COMM ALARM GPS SYNC ALARM PHOTO DIODE ALARM MARKER ALARM NIGHT ALARM DAY ALARM FROM EXTERNAL AC FAIL CONTROL AUX IN INTERFACE (OPTIONAL) Figure 2-22 – SC 370 (AC) Internal Wiring Standard System Revision 10 – 1/09/2015 FTS 370d/w/r...
PHOTO DIODE ALARM MODE COMM ALARM GPS SYNC ALARM PHOTO DIODE ALARM MARKER ALARM NIGHT ALARM DAY ALARM FROM EXTERNAL AC FAIL CONTROL AUX IN INTERFACE (OPTIONAL) Figure 2-23 – SC 370 (AC) Internal Wiring with Smart Board Option FTS 370d/w/r Revision 10 –...
MODE COMM ALARM GPS SYNC ALARM PHOTO DIODE ALARM MARKER ALARM NIGHT ALARM DAY ALARM FROM EXTERNAL AC FAIL CONTROL AUX IN INTERFACE (OPTIONAL) Figure 2-26 – SC 370 (AC) Internal Wiring with WiFi Option Revision 10 – 1/09/2015 FTS 370d/w/r...
MODE COMM ALARM GPS SYNC ALARM PHOTO DIODE ALARM MARKER ALARM NIGHT ALARM DAY ALARM AC FAIL AUX IN FROM EXTERNAL CONTROL INTERFACE (OPTIONAL) DC IN AC FAIL LOW BATT NO NC EHTERNET Figure 2-30 – SC 370 (DC) Internal Wiring with Modem &...
MODE COMM ALARM GPS SYNC ALARM PHOTO DIODE ALARM MARKER ALARM NIGHT ALARM DAY ALARM FROM EXTERNAL AC FAIL CONTROL AUX IN INTERFACE (OPTIONAL) DC IN AC FAIL LOW BATT NO NC Figure 2-31 – SC 370 (DC) Internal Wiring with WiFi Option FTS 370d/w/r Revision 10 –...
Section 3 – Information Display Navigating the Information Display Three pushbuttons to the right of the Table 3-1 describes the function of each information display provide access to button. The top level menu is described in navigate the system menus, configure the Table 3-2.
Marker Mode synchronize with previous generation Marker mode allows the L-810 markers to Flash Technology lighting systems on be programmed as steady burning or nearby towers. flashing. If the flashing option is selected, Revision 10 –...
Page 69
GPS Sync generating a photodiode alarm. This feature is particularly useful in areas that GPS Sync allows the FTS 370 system to are prone to periods of light or darkness wirelessly synchronize with other lighting that would exceed the 19 hour mode timer. systems without regard to distance.
Page 70
IR Enable IR Is Night Alarm This option allows the system to enable or When set to “Yes”, a detected malfunction disable IR (Infrared) output of IR capable in the IR circuit of the FH 370d IR will be beacons. Verify that the beacon(s) is an treated as a night alarm.
Page 71
Tower Type White Dual Number of Beacons 1 - 6 Steady Marker Mode Flashing Efficiency Red Flash Mode Legacy 20 FPM Flashes Per Minute Red 30 FPM 40 FPM GPS SYNC Enable/Disable Yes /No Load Default Value GPS Delay Yes Confirm? 0000 ms Valid Range 0-3000 Catenary Yes /No...
It also simplifies the replacement of marker fixtures by allowing different 4. Restore the source power to the models of Flash Technology approved lighting system. Only the SC 370 unit markers to be installed in the same system. selected in the previous step should be operational.
Page 73
Bind State Bound/Unbound (Status Only) Please Ensure All Other Systems Are Turned Off. Then Press Enter… Verify All Disabled Systems Twr Pwr Is Less Than 5V. Then Press Enter Accept Discover Tower Yes /No Cancel Yes Confirm? Discovering Yes /No Unbind Tower Yes Confirm? AOL Beacon...
SMART the settings should be as follows: card only and will be monitored through a customer supplied Ethernet IP Address Mode: Static connection by Flash Technology’s IP Address: 192.168.1.11 NOC. Subnet Mask: 255.255.255.0 Default Gateway: 192.168.1.10...
Page 75
Yes /No Load Factory Default Yes Confirm? Default of Primary / Alternate Monitoring Static IP Address Mode Dynamic Local Ethernet IP Address XXX.XXX.XXX.XXX Configuration Subnet Mask XXX.XXX.XXX.XXX Default Gateway XXX.XXX.XXX.XXX MAC Address XXXXXXXXXXXX Monitoring Method: Disabled Hours (Enter Value Ranging From 0 - 24) Autoupdate: XX Hours - XX Minutes Minutes (Enter Value Ranging From 0 - 59)
Monitoring Status The Test Connect option allows the user to The Monitoring Status menu is only manually test the unit’s ability to connect available on the unit programmed as to the monitoring system. All headings in System This menu provides the Monitoring Status menu, other than information such as signal strength, cell Test Connect, are informational only.
Page 77
Mode Override Mode Override 0D 0h 15M Site Event History Mode Override Mode Override 0d 0H 20M Days Operating SB Control: Month Day Year Firmware Revision Firmware [Version X.X] Temperature Controller A2D (Values) Tower Voltage Controller Photo Diode Value GPS Communications Antenna GPS (Status Only) Satellites In View...
Lighting Inspection (LI) results can be reviewed by selecting The Lighting Inspection (LI) menu allows Display Previous Results in the Auto the user to test the alarm function of the Fast LI menu. beacon in all modes, markers and the ...
Mode Override Mode Override allows the system to be Left displays amount time manually placed in any capable mode for a remaining in the current Override Mode. user definable period of up to 24 hours. Cancel Override returns the system to Once the mode override function has been normal operation with mode control activated, Override Mode will show the...
USB Firmware Update This feature allows any unit with an completed, the unit will reboot and the installed PCB3 Smart Board to be updated USB drive may be removed. via a USB drive. Insert the drive into the connected subordinate units will be USB port located on the lower edge of automatically updated once the USB drive PCB3 (see Figure 1-5).
Table 3-3 – Information Display Status and Alarm Definitions (continued) Alarm Definition System 1 only. The “BIND ALARM” can be generated by either of the following conditions: • One or more controllers are not bound correctly. A “SYS COMM” alarm will accompany the “BIND ALARM”. •...
Section 4– Web Interface Web Interface (Optional) The Web Interface provides a convenient way to configure the system, perform Lighting Inspections and temporarily control mode remotely. Additionally, useful information such as alarm and event history, cumulative runtime component temperature may be viewed via the web interface.
mode, the user must press “Cont.” Lighting Inspection (LI) (Continue) before the system will restore The following three options are available the alarms and advance to the next test. via the Web interface to perform a The results are displayed once all tests are Lighting Inspection: Auto Fast LI, Manual completed.
Mode Override Auxiliary Input The Force Mode Override menu, located If enabled, Auxiliary Input is shown below “Lighting Inspection” allows between “Force Mode Override” and manual selection of the system’s mode. “Beacon 1”. This menu is informational System control will return to automatic only and displays the configuration and after 30 minutes.
Event Log The headings following the pictorial The Event Log displays all events or provide a brief overview of each top level alarms (up to 500) affecting the operation Configuration menu option. of the SC 370. A few examples of events that may be found in the event log are: ...
Page 86
System “X” The System “X” Configuration menu is similar to the “Local Tower Config Menu” with one exception: the Bind and Unbind features are only available on single beacon systems (one SC 370 controller). Only the bind status will be displayed when more than one SC 370 is installed.
Page 87
Monitoring SNMP Labels The Monitoring menu allows selection of The SNMP Labels menu provides access the Primary and Alternate data monitoring for the end user to change the name and methods discussed Section severity of the SNMP trap based on their “Monitoring Configuration”.
Page 88
Cellular Modem This menu will be displayed only if an AT&T HSPA modem is detected in the system. It allows selection of the installed SIM card type as AT&T Direct or AT&T ROW. This menu option is not displayed for Verizon modems. See Section 3 “Monitoring Configuration”...
The SC 370 has built in diagnostic Carry out the following inspection and capabilities to assist in troubleshooting the cleaning procedures at least once a year: system. Flash Technology recommends 1. Verify that moisture that a full system diagnostic test is run...
Troubleshooting procedures are provided in Component Follow the troubleshooting steps in the Removal and Replacement. tables below as applicable. Repair Table 5-1 – Troubleshooting – Initial Inspection Step Check/Test/Action Action Is the flashhead flashing? Go to Step 1.b Go to Step 2.a Is the failure related to a connected tier of L810 Go to Step 4.a side markers (marker alarm)?
Table 5-3 – Troubleshooting - Flashhead. Step Check/Test/Action Action Is the correct voltage present in the flashhead? Go to Step 3.b Measure at flashhead terminal block DC+ & DC- Inspect flashhead cable and (60 VDC). connections. Note: If a marker tier is connected between the SC 370 and the flashhead, verify that the correct input and output voltage is present on TB1 of the marker interface box before proceeding to the...
Table 5-5 – Troubleshooting – Marker Interface Box Step Check/Test/Action Action Is the correct voltage present at TB1 in the Marker Go to Step 5.b Interface box? Check flashhead cable between Measure at TB1 DC+ & DC- (60 VDC). SC 370 and Marker Interface Box.
Component Removal and Replacement Note the location and color of all wires 2. Completely remove or relocate these that you disconnect when troubleshooting components. or replacing components. Verify that the 3. Disconnect wiring wiring agrees with the applicable figure in component that you want to replace.
Table 6-3 – FH 370 Replacement Parts Reference Description Part Number FH 370d L-864/L-865, L-866/L-885 LED FLASHHEAD 1370150 FH 370w L-865 & L-866 LED FLASHHEAD 1370140 FH 370r L-885 LED FLASHHEAD 1370130 FH 370d IR L-864/L-865, L-866/L-885 LED FLASHHEAD with IR 1370151 FH 370d FH 370d LIGHT ENGINE REPLACEMENT...
Appendix A: Vanguard (v3.1) SNMP V2c INFORM TRAPs Vanguard supports SNMP V2c INFORM TRAPs to notify SNMP managers of field events. Any INFORM that is not acknowledged within 20 minutes will be resent every 20 minutes until it is acknowledged; up to 24 hours. SNMP TRAPs do not require acknowledgement.
Table A-1 – Critical INFORMs Default Name Description Severity White Day Alarm (DAY ALARM): whiteDayAlarmNotify Critical The connected flash head is exhibiting a white .1.3.6.1.4.1.9882.1.2.1.1.1 day alarm. White Night Alarm (WNIGHT ALARM): whiteNightAlarmNotify Critical The connected flash head is exhibiting a white .1.3.6.1.4.1.9882.1.2.1.1.2 night alarm.
Table A-2 – Warning INFORMs Default Name Description Severity Infrared Alarm (IR ALARM): infraredAlarmNotify Warning The connected flash head is exhibiting an IR .1.3.6.1.4.1.9882.1.2.1.1.27 alarm. System GPS Sync Alarm (GPS ALARM): System 1 only. GPS synchronization has not occurred for a period of one hour or more. Possible causes are: •GPS antenna is obstructed or does not have a systemGPSSyncAlarmNotify...
Table A-3 – Informational INFORMs Default Name Description Severity System Communication Alarm (SYS COMM): General communications failure indication. Any communication failure in the system will generate a SYS COMM failure on System 1. The SYS COMM alarm will be accompanied by a specific communication alarm if the failure is systemCommunicationAlarmNotify Info...
Appendix B: Vanguard Modbus Specification Map (V8). Modbus RTU over RS485 The Vanguard system master controller (VSMC) is configured to be a Modbus slave device. It is statically configured as follows: Station ID Parity None Baud Rate 9600 Stop Bits Data Bits Flow Control None...
Page 107
Tower Configuration Registers Register Address Read/Write Register Name Description / Values GPS Delay 0-3000 (milliseconds) Tower Type Red (1), White (2), Dual (3) Beacons 0-6, Reads total Number of non-zero Marker’s Per Tier Marker Tiers below Markers Per Tier 1 Markers Per Tier 2 Markers Per Tier 3 Markers Per Tier 4...
Page 108
QLI Test and Results Registers (Continued) Register Address Read/Write Register Name Description / Values 1 – QLI Inactive 2 – QLI Set Day Mode 3 – QLI Beacon Day Pretest 4 – QLI Beacon Day Alarm 5 – QLI Beacon Day Alarm Check 6 –...
Page 109
QLI Test and Results Registers (Continued) Register Address Read/Write Register Name Description / Values 81 – SEQQLI Beacon 5 Day Pretest 82 – SEQQLI Beacon 5 Day Alarm 83 – SEQQLI Beacon 5 Day Alarm Check 84 – SEQQLI Beacon 5 Day Restore 85 –...
Page 110
QLI Test and Results Registers (Continued) Register Address Read/Write Register Name Description / Values 146 – SEQQLI Beacon 5 Red Night Restore 147 – SEQQLI Beacon 5 Red Night Restore Check 148 – SEQQLI Beacon 6 Red Night Pretest 149 – SEQQLI Beacon 6 Red Night Alarm 150 –...
Page 111
QLI Test and Results Registers (Continued) Register Address Read/Write Register Name Description / Values Bit 0 – Beacon 1 not tested (0), was tested in White Day (1) Bit 1 – Beacon 1 passed pretest (0), failed pretest (1) Bit 2 – Beacon 1 passed inhibit (0), failed inhibit (1) Bit 3 –...
Page 112
Tower Monitoring Interface Register Address Read/Write Register Name Description / Values 0-254 (Increments indicate a reportable status event such Tower Status State as an alarm occurred) 0-254 (Increments indicate a tower configuration change Tower Configuration State occurred) Bit 0: Indicates system powered up Bit 1: Indicates power to the tower is off (POWER FAIL) Bit 2: Reserved Bit 3: Indicates low tower DC power (LOW DC)
Page 113
Vanguard Controller Board Diagnostics Register Address Read/Write Register Name Description / Values Vanguard Controller Select 1-6, indicates/selects which system data is reflected below Register Reboots all controllers for the entire site. Only applicable System wide reboot on controller 1 (as set in register 90). Writing any value will cause the reboot.
Page 114
Beacon Settings and Diagnostics Register Address Read/Write Register Name Description / Values 1-6, indicates/selects which system beacon data is Beacon Select Register reflected below Beacon Firmware Revision 162 – 192 ASCII string, null terminated String Beacon Universally Unique 193 – 208 Binary data identifier Identifier An A2D value representing White String 0 Voltage.
Page 115
Marker Settings and Diagnostics Register Address Read/Write Register Name Description / Values 1-6, indicates/selects which system Marker Tier data is Marker Tier Select Register reflected below Marker Board Firmware 242 – 272 ASCII string, null terminated Revision String Marker Board Universally 273 –...
Page 116
Auxiliary Interface Registers Register Address Read/Write Register Name Description / Values Auxiliary Interface Control Type 0: Disabled, 1: Modbus, 2: DC Input Command Lights On/Off 0: Lights on, 1: Lights off 0: Idle 1: Pending (Command has been sent to Beacon) 2: ON Success (Beacon has confirmed a Lights On command) Lights-On Confirmation...
REASON (SUBJECT TO THE WARRANTY POLICY), PLEASE FOLLOW THE PROCEDURE BELOW: Note: An RMA number must be requested from Flash Technology prior to shipment of any product. No returned product will be processed without an RMA number. This number will be the only reference necessary for returning and obtaining information on the product’s progress.
Page 118
• All returned products should be packaged in a way to prevent damage in transit. Adequate packing should be provided taking into account the method of shipment. Note: Flash Technology will not be responsible for damaged items if product is not returned in appropriate packaging.