132 VAC or 170 VAC to 264 VAC. However, the flame signal strength will be affected somewhat with An AC or DC signal is applied to the Model 600 Ultra AC voltage changes. This should not be a problem be-...
The Model 600 Ultra will operate equally well in sev- If the “3” or “4” digits are on most of the time, the gain eral configurations: flame rod only, flame rod with igni- should be increased by moving P2 to a higher gain posi- tion coil, and flame rod with ignition transformer.
Page 4
Relay On FOULED POOR SIGNAL Relay Off POWER SELECT FOR LINE INPUT TO XFMR TURN IGN ON LINE INPUT 230 VAC 50/60 HZ XFMR XFMR 115 VAC 50/60 HZ .28" 3.25" 2.98" FIGURE 1 - MODEL 600 ULTRA FLAME ROD CONTROLLER...
Page 5
COIL COIL GAIN 2 GAIN 2 NO JMPR = MAX GAIN 4 NO JMPR = MAX GAIN 4 FLAME ROD ONLY GOOD SIGNAL Relay On MODEL 600 ULTRA FLAME ROD WEAK FAULT SIGNAL Relay On FOULED POOR SIGNAL Relay Off...
Page 6
SPECIFICATIONS FOR MODEL 600 ULTRA FLAME ROD ELECTRICAL Primary Input Power – 85 to 132 VAC, or 170 to 264 VAC, 50 or 60 Hz Input Current, Monitoring only – .07 A at 115VAC, .035 A at 230 VAC Input Current, Ignition on –...