Operating Limits - Lennox NEOSYS NAC 200 Application Manual

Air cooled chiller & heat pump 200 - 1000 kw
Table of Contents

Advertisement

OPERATING LIMITS

NAC
Min. outlet water temperature
Min. outlet water temperature with brine operation option
Max. inlet water temperature
Min. difference water inlet/outlet
Max. difference water inlet/outlet
Min. outside air temperature
Min. outside air temperature
Winter operation option
Maximum outside air temperature :
Full capacity operation
NAH
Cooling mode
Min. outlet water temperature
Max. inlet water temperature
Min. difference water inlet/outlet
Max. difference water inlet/outlet
Min. outside air temperature
Maximum outside air temperature :
Full capacity operation
Heating mode
Min. condenser outlet water temperature
Max. condenser outlet water temperature
Min. difference water inlet/outlet
Max. difference water inlet/outlet
Min. outside air temperature (Water outlet
temp. : 37°C)
Max. outside air temperature
Operating enveloppe
Cooling mode
50
45
40
35
30
25
20
15
Please consult us
10
5
0
-5
-10
-15
-20
-25
-12
-7
-2
Evaporator water outlet (°C) with Delta T = 3°C
Application Guide /NEOSYS-AGU-1801-E
NAH
200
°C
°C
°C
°C
°C
°C
NAH
200
°C
°C
°C
°C
°C
°C
NAH
3
8
13
18
200 >
420 -
380
340
480
°C
°C
°C
°C
°C
°C
°C
°C
46
43
46
480
>
5
20
(°C)
50
3
45
40
8
35
6
30
25
20
46
15
10
480
5
>
0
24
-5
-10
Brine operation option
50
-15
-20
3
-25
-12
8
- 12
Maximum outdoor air temperature = 43°C on NAC 380 / NAC 540
and NAC 1080
30
50°C
45°C
40°C
35°C
30°C
25°C
20°C
15°C
-10°C
-5°C
600 >
540
760
680
5
- 10
20
3
8
6
- 20
43
46
43
NAC
Operating enveloppe
Cooling mode
Glycol
Glycol
Winter cooling
+
operation option
-7
-2
3
8
Evaporator water outlet (°C) with Delta T = 3°C
NAH
Operating enveloppe
Heating mode
0°C
5°C
10°C
15°C
20°C
Outdoor air temperature (°C)
NAC
840 -
1080
960
46
43
(°C)
13
18
25°C
30°C
• 33 •