Epaq-9150 Specifications; Input/Output Functions (Maximum); Input Power; Communications - QEI ePAQ-9150 User Manual

Substation terminal node
Table of Contents

Advertisement

e-PAQ-9150
____________________________________________________________________________

1.2 ePAQ-9150 Specifications

1.2.1

Input/Output Functions (maximum):

Analog Inputs:
Status Inputs:
Control Outputs: 128
Analog Outputs:
For detailed I/O Specifications, please refer to the applicable panel User's Guide.
The number of I/O functions listed above is the maximum number supported by the ePAQ-
9100 module. However the size of the rack used will dictate the actual number of I/O points
provided.
Each Status Input used as an Accumulator or PDM input reduces the total number of Status
Inputs available by the same amount.
1.2.2

Input Power:

1.0 Amp @ 120 VAC, 60 Hz, Single Phase
1.0 Amp @ 125 VDC
1.5 Amps @ 48 VDC
3.0 Amps @ 24 VDC
Note:
a.
The input power is connected via a 3-position terminal block located at the rear panel of the ePAQ-
9100 module. There is a power surge of 5.0 Amps when power is turned on.
b.
Some ePAQ-9150s may use one of the Sentinel-21, 6PCP6 family of power supplies. Please refer
to the 6PCP6 User's Guide, UG-1007 for more details.
1.2.3

Communications:

Standard:
Option 1:
Option 2:
1.2.4

Environment:

Temperature:
Humidity:
1.2.5

Physical Configurations, typical:

Cabinet Model:
Material:
Rating:
Mounting:
Dimensions (HxWxD):
4
Section 1
128
256 - Convertible to Accumulator or PDM Inputs
32 - Using an external 6DA1 or 6SP1 card(s)
RS-232 or RS-485 serial ports
Ethernet via external Network Interface Card (6NIA1, UG-1040)
202T type modem(s) with 4 or 2-wire options over telephone
(600 ohms) leased lines as per FCC type 3002 channels
Standard:
32 ºF to 158 ºF (0 ºC to 70 ºC)
5% to 95% @ 158 ºF, non-condensing
19" Rack
Aluminum and Steel
Indoor Use Only
Floor
84.00 x 20.00 x 15.00 (inches)
Remote Terminal Unit
Copyright © 2016 QEI