Siemens SENTRON 3VL160X System Manual page 147

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Plug-in or withdrawable version:
Table 11- 21 Derating factors for electronic trip units (plug-in or withdrawable version)
Molded
case circuit
breaker
VL160
VL250
VL400
VL630
VL800
VL1250
VL1600
Example for VL250:
● I
● Ambient temperature = 60 °C
1. Fixed-mounted version:
2. Plug-in or withdrawable version:
Derating factor from the table "Derating factors of electronic trip units (fixed mounting)"
1)
Coefficient for plug-in or withdrawable version from the table "Derating factors for
2)
electronic trip units (plug-in or withdrawable version)"
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
Release
ETU
From [A]
63
125
200
315
--
--
1000
--
= 250 A at 50 °C
n
I
= 250 x 0.95
= 237 A
1)
n
Set I
to the next lowest value -> I
R
I
= 250 x 0.95
x 0.9
1)
2)
n
-> Calculation of overall derating = 0.95 x 0.9 = 0.885
-> Set I
to the next lowest value -> I
R
To [A]
40 °C
100
1
160
1
250
1
400
1
630
1
800
1
1250
1
1600
1
= 0.95 = 237 A
R
= 213 A
= 0.8 = 200 A
R
Technical data
11.4 Derating factors
Coefficient
at
50 °C
60 °C
1
1
0,9
0,9
0,9
0,9
0,9
0,9
0,85
0,85
0,9
0,9
0,95
0,95
0,8
0,8
70 °C
1
0,9
0,9
0,9
0,85
0,9
0,95
0,8
147