Siemens SENTRON 3VL160X System Manual page 145

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Thermal-magnetic overcurrent release + RCD module
Fixed mounting:
Table 11- 18 Derating factors for thermal-magnetic overcurrent release + RCD module (fixed
Molded
case
circuit
breaker
VL160X
VL160
VL250
VL400
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
mounting)
I
Cross-
n
section Cu
At 50 °C
[mm
] min.
2
[A]
16
2,5
20
2,5
25
4
32
6
40
10
50
10
63
16
80
25
100
35
120
50
160
70
50
10
63
16
80
25
100
35
125
50
160
70
200
95
250
120
200
95
250
120
315
185
400
240
Cross-
Max. rated uninterrupted current according to the
section Al
[mm
] min.
2
40 °C
4
1
4
1
6
1
10
1
10
1
16
1
25
1
35
1
50
1
70
1
95
1
16
1
25
1
35
1
50
1
70
1
95
1
120
1
185
1
120
1
185
1
2x120
1
2x150
1
Technical data
11.4 Derating factors
ambient temperature x I
n
50 °C
60 °C
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,93
1
0,86
1
0,86
1
0,86
1
0,86
1
0,86
1
0,86
70 °C
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8