FPC-1 Fire Detection and Extinguishant Controller Installation Only authorised people should install the FPC-1. Install the unit on the top surface of the protected space or near the top as high as possible. Install the aerosol container according to the manufacturer's specification.
Page 3
FPC-1 due to regulations, local laws, or applicable standards. Ensure that the requirements and regulations relevant to the installed location do not prohibit such a system. The FPC-1 is intended for applications where relevant regulations do not specify a fire alarm and extinguishing system.
Page 4
FirePro Systems Ltd. Technical Manual Version 1, 01-07-2010 The FPC-1 operates by heat detection. Do not use the FPC-1 if smoke detection is required. In instances where the module's characteristics conflict with any standard, you should install a system that is fully compliant with the relevant standards. In such cases you...
A beep and three flash of the Trouble (yellow) LED every minute – a weak battery. Remote Activation Input The FPC-1 has a remote activation input that can be used in one of two ways: • A manual activation switch – remove the End of Line resistor and install it at the switch as shown in Figure 2.
Page 6
Version 1, 01-07-2010 Warnings and Limitations Please Note The FPC-1 module contains various elements, including a control module, and a heat detection sensor that are intended to activate a compatible extinguishing unit by triggering a pre-defined electric igniter. When used with an extinguishing device, proper planning of the system's configuration...
Page 7
Remote Activation End of Line Resistor 5.1 K Ohm Max current draw from open collector output 50mA All values are nominal. Specifications are subject to change without prior notice. products are manufactured by FirePro Systems Ltd FirePro ® Page 6 of 6...