Page 3
• Mixed light measurement suitable for fluorescent lamps (FL/PL/ESL), halogen/incandescent lamps and LEDs • Integrated button • Different models: • 5TC1585 Motion detector for normal requirements • 5TC1586 For Master /Slave Switching. Proper Use • The detector controls the lighting.
If the detection area covered by a single detector is insufficient (in large rooms), then several detectors can be operated in parallel by connecting the P terminals. The master 5TC1585 measures brightness and controls the lighting. The other detectors, slaves 5TC1586, merely provide presence information.
Page 5
Flush-mounted installation With a standard flush-mounting box, size 1 (see illustration) Disconnect power source. Connect detector according to the wiring diagram (see section connection) Screw down the detector in the flush-mounted box Position the button and frame on the detector ...
Page 6
Setting the brightness (LUX) You can set different brightness values with the brightness potentiometer (factory setting 500 lx). Set potentiometer to desired switch-on brightness (5 to 1000 lux/on). On the on setting the detector always responds to movement, regardless of the brightness. ...
Page 7
Setting the MODE (fully or semi-automatic) with staircase light function Staircase light function – corridor off/corridor on With the corridor off staircase light function the light can be switched on and off manually using the button at any time. With corridor on it can be switched on manually but not switched off.
LED display Description Flashes a 1 second The detector is in the start -up phase intervals Flashes rapidly Error flashing, the detector has found an error Flickers for 20 s Teach-in via potentiometer is activated Lights up or flickers The detector is in walking test mode. irregularly Troubleshooting Fault...
Page 9
10 s (pulse) -30 min, (not with 5TC1586) Installation height 0.8 – 1.2 m Detection angle: 170° Detection area: – across 14 x 17 m – frontal 12 x10 m Rigid cable 10 mm * Note: for P terminal max 1,5mm2, solid rigid conductor. Dimensions 5TC1586 5TC1585...