The PCT feature consists of seven independent timers. Each timer has the following setpoints (setpoints shown are for
PCT #1):
• Programmable Cycle Timer #1 Activation Day of the Week. This permits independent selection of each day
(Sun >Sat) that the timer will activate
• Programmable Cycle Timer #1 Activation Start Time. The time of day (in hours and minutes) that the timer will
activate
• Programmable Cycle Timer #1 Active Time. The duration (in hours and minutes) for which the timer will be
active (up to 24 hours)
• Programmable Cycle Timer #1 Output #1 Activation Configuration. Determines the first output will be activated
when this timer is active
• Programmable Cycle Timer #1 Output #2 Activation Configuration. Determines the second output will be
activated when this timer is active.
Output #1 is used to run the generating set. Output #2 can be used to drive relay output 8.

4.6.1 PCT Status

The status of the PCTs can be found within the menu structure at:
MAIN MENU > CONTROL > PROG CYCLE TIMER
The top row displays the seven PCTs (#1 to #7).
The middle row is for OUTPUT #1.
The bottom row is for OUTPUT #2.

4.6.2 Controlling The Outputs

The status of each output is indicated by a 1, 0 or - in the PROG CYCLE column under #1 to #7.
"1" The PCT is configured and currently driving the output.
"0" The PCT is configured but not currently driving the output.
"-" The PCT has not been configured:

4.6.3 PCT Example:

• PCT #1 is ACTIVE, "1" – Output #1. Output #2 is not enabled (the "-" in the bottom row)
• PCT #2 is NOT active, "0" – however, when it is active, it activates both Output #1 and Output #2. The two
zeros show that this PCT will enable both outputs when it becomes active
• PCT #3 is not active. When it becomes active it will only activate Output #2
• PCT #4, PCT #5, PCT #6 and PCT# 7 are disabled. They will not activate Output #1 or Output #2.
PROG CYCLE
OUTPUT 1
OUTPUT 2
: 1 2 3 4 5 6 7
: 1 0 - - - - -
: - 0 0 - - - -